Control panel with integrated room sensor
Description
The model A2G-200 control panel with integrated room sensor was developed specifically for requirements in the ventilation and air-conditioning industry. Different versions measure the key parameters of relative humidity, room air temperature and carbon dioxide (CO 2 ).
The large touch LC display makes the operation and readability easy and clear. The integrated switching output enables a direct control command to higher-level systems or can be used for the direct switching on of a ventilation/ air-conditioning unit or fan. For this, the switch relay can be configured with all three parameters (relative humidity, ambient air temperature and CO 2 ).
Fig. top: with display Fig. bottom: without display
The measuring results are transmitted with an analogue output signal (0 ... 10 V or 4 ... 20 mA) or digitally via Modbus output.
To prevent incorrect operation or manipulation, the LC display can be locked via setting a jumper on the PCB and then only has the function of a display and measuring instrument.
Special features
- Electrical output signal, DC 0 … 10 V, 4 … 20 mA or Modbus ®
- Touchscreen
- Integrated switching output
| Model | A2G-200 |
| Product family | A2G |
| Subcategory | Room sensor with display and switching output |
| Temperature ranges | +0…+50 °C |
| Accuracy class | < 0.5 °C |
| Output signal | 0/2...10 V · 4...20 mA · Modbus · Modbus® |
| Power supply | AC/DC 24 V ±10 % |
| Electrical connection | 5 screw terminals (24 V, GND, CO2, rH, T), cable gland M20, max. 1.5 mm² |
| Ambient temperature | −20…+70 °C |
| IP rating | IP20 |
| Weight | 0.15 kg |
| Certifications | CERoHSWEEE |
| Sensor type | Pt1000 |
| Thermowell | No |
| Datasheet languages | EN |
| Parameter | |||
|---|---|---|---|
| CO 2 | Temperature | Relative humidity | |
| Version | ■ With LC display ■ Without LC display ■ With LC display and switching output | ||
| Measuring element | Non-dispersive infrared (NDIR) | Pt1000 | Capacitive thermosetting polymer sensor element |
| Measuring range | 400 …2,000 ppm | 0 …50°C[32 …122 °F] | 0 ...90% |
| Accuracy | ±40 ppm + 2 %of reading value | < 0.5 °C [0.9 °F] | max.±4% |
| Units | ppm | 5 °C | ±4 %r.h. |
| Output signal | ■ 0/2 ... 10 V, R >1 kΩ ■ 4 ... 20 mA, R <500Ω ■ Modbus ® | ||
| Electrical connection | 5 screw terminals (24 V, GND,CO 2 , rH, T) Cable gland M20 Max.1.5mm 2 | ||
| Supply voltage U B / Current consumption | AC/DC 24 V, ±10% 90 mA, +10 mAfor each voltage output / +20 mAfor each current output | ||
| LC display | 77.4 x 52.4 mm[3.0 x 2.1 in] | ||
| Case | Plastic (ABS) | ||
| Permissible temperatures | |||
| Ambient | -20 …+70 °C [-4 …158 °F] | ||
| Operating | 0 …50°C[32 …122 °F] | ||
| Relative humidity | 0 …95%,non-condensing | ||
| Ingress protection per IEC/EN 60529 | IP20 | ||
| Mounting | Via three screw holes (slotted screws) with Ø3.8 mm[0.2 in] | ||
| Weight | 150 g |
| Protocol | RTU mode, RS 485 An additional analogue output for a selected measured value 0 ... 10 V, 2 …10V, R > 1 kΩ 4 …20mA, R < 500Ω |
|---|---|
| Transmission mode | RTU |
| Interface | RS-485 |
| Switching output | SPDT relay, 250 …30V, 6 A 3 screw terminals (NC, COM, NO) |
| Power supply U B | AC 24V or DC 24V ±10% |
| Modbus ® addresses | 1 …247 addresses selectable in the configuration menu |
| Description | Country |
|---|---|
| EC declaration of conformity | European Union |
| EMCdirective | |
| Low voltage directive | |
| RoHS conformity | |
| WEEE directive |