Fault · SINAMICS S120, S150

F37025HF Damping Module: Chip overtemperature

What it means

F37025 reports that the chip temperature of the HF Damping Module has risen above the permissible limit value. The drive trips with OFF2 — the pulses are disabled and the motor coasts down — and the fault must be acknowledged immediately before the drive will start again. The manual describes this fault for SINAMICS S120 and S150 and notes that the measured condition can be followed in r0037 and in the fault value r0949.

Why it appears

  • The chip temperature has exceeded the permissible limit value.
  • The permissible load duty cycle was not maintained.
  • Cooling is insufficient — for example, a fan has failed.
  • The module is overloaded.
  • The ambient temperature is too high.
  • The pulse frequency is too high.

What to check

  1. Adapt the load duty cycle so that the permissible load duty cycle is maintained.
  2. Check whether the fan is running.
  3. Check the fan elements.
  4. Check that the ambient temperature is within the permissible range.
  5. Check the motor load.
  6. If the set pulse frequency is higher than the rated pulse frequency, reduce it.

Reading the message value

  • The drive stores the temperature difference between the heat sink and the chip in r0949.
  • Interpret the fault value as a decimal number; it is given in steps of 0.01 °C.

Parameters the manual names

  • r0949 — fault value: for this fault it contains the heat-sink-to-chip temperature difference; read it as a decimal number in 0.01 °C.
  • r0037 — the note to this fault refers to this parameter; it displays the Control Unit temperature (CU temp).

Acknowledging and restarting

Acknowledge the fault immediately. The drive coasts down and must be acknowledged before it will start again; remove the cause first so the fault does not reoccur.

The same on every family

Every manual that describes F37025 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELYPower electronics faulted (5)NoneSINAMICS S120, S150 List Manual · p. 3263

The drives this code lives on

F37025 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F37025 on a SINAMICS S120 or S150 mean?

The chip temperature of the HF Damping Module has exceeded the permissible limit value. The drive trips with OFF2 and the fault must be acknowledged immediately.

What is in r0949 when F37025 is active?

The temperature difference between the heat sink and the chip of the HF Damping Module, in steps of 0.01 °C, interpreted as a decimal number.

How do I clear F37025?

Check whether the fan is running and check the fan elements, keep the ambient temperature in the permissible range, check the motor load, adapt the load duty cycle and reduce the pulse frequency if it is above the rated pulse frequency. Then acknowledge the fault.

Which parameter does the manual reference for F37025?

The note to this fault refers to r0037, which displays the Control Unit temperature (CU temp).

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F37xxx group · SINAMICS manuals · Siemens manuals