What it means
F34950 is raised when the Voltage Sensing Module (VSM) detects an internal software error. The drive coasts down (OFF2), and the fault is only cleared at power up — the converter will not restart until it has been switched off and on again. The manual gives no customer-level detail about what failed inside the module: the fault value identifies the fault source, but the manual states it is Only for internal Siemens troubleshooting
.
Why it appears
- An internal software error has occurred inside the Voltage Sensing Module (VSM).
What to check
- If the fault occurs, check whether a later firmware version is available for the Voltage Sensing Module (VSM) and upgrade the module's firmware if necessary.
- If the error persists, contact Technical Support and quote the fault value from r0949, interpreted as a decimal number — the manual designates this information for internal Siemens troubleshooting, so it is the support engineer who can evaluate it.
Reading the message value
- The drive stores information about the fault source in r0949; the manual instructs to interpret the value as a decimal number.
- No bit or value decoding is printed for this code — the content is intended only for internal Siemens troubleshooting, so there is no self-help reading of the value.
Parameters the manual names
- r0949 — read the fault value of F34950 here; for this code it holds the fault source as a decimal number and is only meaningful to Siemens Technical Support.
Acknowledging and restarting
This fault belongs to the POWER ON acknowledge class: it cannot be cleared with an ordinary acknowledge, only by switching the converter power supply off and on again. After the power-up reset the drive can be restarted. If F34950 returns, follow the remedy above — upgrade the VSM firmware if a later version exists, otherwise contact Technical Support.
The same on every family
Every manual that describes F34950 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 | POWER ON | Hardware/software error (1) | Voltage Sensing Module (VSM) | SINAMICS S120, S150 List Manual · p. 3196 |
| G130, G150 | OFF2 | POWER ON | Hardware/software error (1) | Voltage Sensing Module (VSM) | SINAMICS G130, G150 List Manual · p. 1866 |
The drives this code lives on
F34950 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F34950 mean on a SINAMICS drive?
It reports an internal software error in the Voltage Sensing Module (VSM). The drive coasts down (OFF2) and stays blocked until it has been reset at power up.
How do I clear fault F34950?
Only by switching the power supply off and on again (POWER ON acknowledge). If the fault comes back, upgrade the VSM firmware to a later version if available, or contact Technical Support.
What does the fault value of F34950 in r0949 tell me?
It identifies the fault source and is to be interpreted as a decimal number. The manual states the information is only for internal Siemens troubleshooting, so there is no decoding you can act on yourself.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F34xxx group · SINAMICS manuals · Siemens manuals