Fault · SINAMICS G130, G150, S120, S150

F34851VSM DRIVE-CLiQ (CU): Sign-of-life missing

What it means

F34851 is raised when the Voltage Sensing Module (VSM) involved fails to set its sign-of-life to the Control Unit. The drive treats this as a DRIVE-CLiQ communication error from the VSM to the Control Unit: in the receive telegram, the sign-of-life bit is not set, which the manual records as fault cause 10 (= 0A hex).

Why it appears

  • A DRIVE-CLiQ communication error between the involved VSM and the Control Unit: the DRIVE-CLiQ component did not set its sign-of-life to the Control Unit.
  • Fault cause 10 (= 0A hex) — the sign-of-life bit in the receive telegram was not set.

What to check

  1. Identify the component involved: the drive codes the component number in the message value (0000yyxx hex, readable in r0949 or r2124); the yy portion is the component number.
  2. Carry out the remedy the manual specifies: upgrade the firmware of the component involved.

Reading the message value

  • The message value contains two items: the component number (%1) and the fault cause (%2).
  • Coding in r0949 (fault value) and r2124 (alarm value): 0000yyxx hex — yy = component number, xx = error cause.
  • Error cause 10 (= 0A hex): the sign-of-life bit in the receive telegram is not set.

Parameters the manual names

  • r0949 (fault value): holds the coded message value 0000yyxx hex for this fault — read the component number (yy) of the affected VSM and the error cause (xx) from it.
  • r2124 (alarm value): the manual names this parameter alongside r0949 as the place where the same coded message value of this message is stored.

Acknowledging and restarting

This fault is acknowledged IMMEDIATELY — acknowledge it directly as soon as it appears. The manual describes no further restart or reset procedure for this code; if the sign-of-life error occurs again after the acknowledgement, upgrade the firmware of the component involved.

What differs between the drive families

Straight from the manuals' own fields — F34851 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: OFF2 (NONE, OFF1) Servo: NONE (OFF1, OFF2) Vector: NONE (OFF1, OFF2) Hla: NONE (OFF1, OFF2)Internal (DRIVE-CLiQ) communication error (12)Voltage Sensing Module (VSM)SINAMICS S120, S150 List Manual · p. 3189
G130, G150Vector: NONE (OFF1, OFF2) Infeed: OFF2 (NONE, OFF1)IMMEDIATELYInternal (DRIVE-CLiQ) communication error (12)Voltage Sensing Module (VSM)SINAMICS G130, G150 List Manual · p. 1859

The drives this code lives on

F34851 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F34851 mean on a SINAMICS drive?

A Voltage Sensing Module (VSM) did not set its sign-of-life to the Control Unit over DRIVE-CLiQ. Fault cause 10 (= 0A hex) means the sign-of-life bit in the receive telegram is not set.

How do I find out which VSM triggered F34851?

The drive codes the component number in the message value 0000yyxx hex, readable in r0949 (fault value) or r2124 (alarm value); the yy portion is the component number.

How is F34851 cleared?

Acknowledge the fault IMMEDIATELY; the only remedy the manual gives is to upgrade the firmware of the component involved.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.