What it means
F31806 tells you that the initialization of encoder 1 (Sensor Module Encoder 1) did not complete successfully. The drive stores in r0949, as a bit pattern, exactly which step of the initialization failed; on G130 and G150 the manual prints this value as the placeholder %1. One List Manual asks for the value to be read in binary, the other in hexadecimal — the bit assignments are the same in both. Depending on how the drive is configured, the same condition can also be output as an alarm or without any drive reaction.
Why it appears
- The encoder did not get through its initialization; the fault value in r0949 identifies the stage at which it failed.
What to check
- Acknowledge the fault first — often this alone clears it.
- If the fault comes back, read the bits of the fault value in r0949 and follow the steps that match.
- Bits 2 ... 9 set: check the encoder power supply.
- Bits 2 ... 14 set: check the cable belonging to the affected track.
- Bit 15 and no other bit: check track R and the settings in p0404.
- Bit 28 set: check the cable between the EnDat 2.2 converter and the measuring unit.
- Bits 29 ... 31 set: replace the defective measuring unit.
Reading the message value
- Bit 0, 1 — initialization was attempted while the motor was already turning and failed: the coarse and the fine position disagree, measured in encoder pulses/4.
- Bits 2 ... 9 — mid-voltage matching did not succeed for the track concerned: bit 2 track A, bit 3 track B, bit 4 the acceleration input, bit 5 safety track A, bit 6 safety track B, bit 7 track C, bit 8 track D, bit 9 track R.
- Bits 10 ... 14 — the mid-voltage spread between two tracks exceeds 0.5 V: bit 10 between A and B, bit 11 between C and D, bit 12 between safety A and safety B, bit 13 between A and safety B, bit 14 between B and safety A.
- Bit 15 — the standard deviation of the calculated mid-voltages is above 0.3 V.
- Bits 16 ... 18 — internal faults of the matching stage: bit 16 reading a register (CAFE), bit 17 writing a register (CAFE), bit 18 no mid-voltage matching available.
- Bit 19 — internal error, the ADC could not be accessed.
- Bit 20 — internal error, no zero crossover was found.
- Bit 28 — starting up the EnDat 2.2 measuring unit failed.
- Bits 29 ... 31 — a problem with the EnDat 2.2 measuring unit: bit 29 its data cannot be read out, bit 30 its EEPROM checksum is wrong, bit 31 its data is inconsistent.
- Hardware note — bits 0 and 1 are reported on hardware up to 6SL3055-0AA00-5*A0; bits 2 ... 20 apply from 6SL3055-0AA00-5*A1 onward.
Parameters the manual names
- r0949 — holds the fault value for this message; read it bit by bit to see which stage of the encoder initialization failed.
- p0404 — the effective encoder configuration; when bit 15 is the only bit set, check the settings here.
- p0491 — the manual cross-references this parameter (motor encoder fault response ENCODER) because it governs how the drive responds to an encoder fault of this kind.
Acknowledging and restarting
The first remedy is simply to acknowledge the fault. If it reappears immediately, the cause has not been removed — work through the bit-specific checks above (power supply, cable, p0404 settings or measuring unit) before acknowledging again.
What differs between the drive families
Straight from the manuals' own fields — F31806 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: OFF2 (NONE) Servo: ENCODER (IASC/DCBRK, NONE) Vector: ENCODER (IASC/DCBRK, NONE) Hla: ENCODER (NONE) | PULSE INHIBIT | Actual position/speed value incorrect or not available (11) | Sensor Module Encoder 1 | SINAMICS S120, S150 List Manual · p. 3063 |
| G130, G150 | Vector: ENCODER (IASC/DCBRK, NONE) Infeed: OFF2 (NONE) | PULSE INHIBIT | Actual position/speed value incorrect or not available (11) | Sensor Module Encoder 1 | SINAMICS G130, G150 List Manual · p. 1747 |
The drives this code lives on
F31806 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F31806 mean on a SINAMICS drive?
Encoder 1 on the Sensor Module could not be initialized. The fault value in r0949 names, bit by bit, the stage at which initialization stopped — from the power-supply-related mid-voltage checks to internal and EnDat 2.2 errors.
How do I clear F31806?
Acknowledge the fault. If it will not clear, check the encoder power supply (bits 2 ... 9), the cable of the affected track (bits 2 ... 14), track R and p0404 (bit 15 alone), the EnDat 2.2 cable (bit 28), or replace the measuring unit (bits 29 ... 31).
Which hardware reports bits 0 and 1 in the F31806 fault value?
Only hardware up to 6SL3055-0AA00-5*A0. From 6SL3055-0AA00-5*A1 onward, the mid-voltage checks in bits 2 ... 20 are used instead.
Does F31806 always stop the drive?
No. The same condition can also be output as an alarm or with no reaction, depending on how the drive is configured.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F31xxx group · SINAMICS manuals · Siemens manuals