Fault · SINAMICS G130, G150, S120, S150

F03590TM: Module not ready

What it means

F03590 means TM: Module not ready: the Terminal Module (TM) involved does not send a ready signal and no valid cyclic data. The fault value identifies which Terminal Module is affected. Depending on how the drive is configured, the same condition can also be output as an alarm (A) or without any reaction (N).

Why it appears

  • The affected Terminal Module is not sending a ready signal.
  • The affected Terminal Module is not sending valid cyclic data.

What to check

  1. Check the 24 V power supply.
  2. Check the DRIVE-CLiQ wiring.
  3. Check whether the sampling time of the affected drive object is not equal to zero — see p4099[0].

Reading the message value

  • The drive stores the fault value in r0949. Interpreted as a decimal number, it is the drive object number of the Terminal Module involved.

Parameters the manual names

  • r0949 (fault value): read the fault value of this message here; interpreted as a decimal number it gives the drive object number of the affected Terminal Module.
  • p4099 (inputs/outputs sampling time, I/O t_samp): for this fault, check index [0] of the affected drive object — the sampling time must not be 0.

Acknowledging and restarting

Acknowledge the fault immediately; a POWER ON also clears the message. Because the fault is present as long as the Terminal Module sends no ready signal and no valid cyclic data, remove the cause first — 24 V power supply, DRIVE-CLiQ wiring, sampling time p4099[0] — and then acknowledge and restart.

What differs between the drive families

Straight from the manuals' own fields — F03590 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: OFF2 (NONE) Servo: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2) Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Hla: OFF2 (NONE)IMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 2745
G130, G150Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Infeed: OFF2 (NONE)IMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1517

The drives this code lives on

F03590 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F03590 mean?

It means 'TM: Module not ready': the Terminal Module involved does not send a ready signal and no valid cyclic data. The fault value in r0949 tells you which Terminal Module is affected.

How do I clear fault F03590?

Check the 24 V power supply, check the DRIVE-CLiQ wiring, and check with p4099[0] that the sampling time of the affected drive object is not equal to zero. Then acknowledge the fault immediately; a POWER ON also clears it.

What is the fault value of F03590?

r0949, interpreted as a decimal number, contains the drive object number of the Terminal Module involved.

Is F03590 always a fault?

No. Depending on how the drive is configured, the same condition can also be output as an alarm (A) or without any reaction (N).

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.