SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Fault · SINAMICS G130, G150, S120, S150

F01952CU DRIVE-CLiQ: Synchronization of component not supported

What it means

F01952 means that the DRIVE-CLiQ components connected to the CU do not all support the synchronization between the basic clock cycle, the DRIVE-CLiQ clock cycle and the application clock cycle, although the existing system configuration requires exactly this. The drive switches off and the fault must be acknowledged before it can be restarted.

Why it appears

  • The existing system configuration requires that the connected DRIVE-CLiQ components support the synchronization between the basic clock cycle, the DRIVE-CLiQ clock cycle and the application clock cycle.
  • However, not all DRIVE-CLiQ components have this functionality — the fault is raised when a component in the configuration lacks it.

What to check

  1. Read the fault value in r0949 to find the component number of the first faulty DRIVE-CLiQ component (interpret the value decimal).
  2. Upgrade the firmware of the component specified in the fault value.
  3. If required, also upgrade additional components in the DRIVE-CLiQ line.

Reading the message value

  • The message value holds the component number of the first faulty DRIVE-CLiQ component; it is stored in r0949 and must be interpreted as a decimal number.

Parameters the manual names

  • r0949 — fault value: read the component number of the first faulty DRIVE-CLiQ component here and interpret it decimal to identify the component whose firmware must be upgraded.

Acknowledging and restarting

Once the firmware of the component named in the fault value has been upgraded, acknowledge the fault immediately. If required, also perform a POWER ON — switch the drive off and back on — before restarting.

The same on every family

Every manual that describes F01952 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2 (NONE)IMMEDIATELY (POWER ON)Internal (DRIVE-CLiQ) communication error (12)NoneSINAMICS S120, S150 List Manual · p. 2720
G130, G150OFF2 (NONE)IMMEDIATELY (POWER ON)Internal (DRIVE-CLiQ) communication error (12)NoneSINAMICS G130, G150 List Manual · p. 1496

The drives this code lives on

F01952 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F01952 mean?

It means that not all connected DRIVE-CLiQ components support the synchronization between the basic clock cycle, the DRIVE-CLiQ clock cycle and the application clock cycle that the existing system configuration requires.

How do I find the faulty component with F01952?

The fault value in r0949 contains the component number of the first faulty DRIVE-CLiQ component; interpret the value as a decimal number.

How is fault F01952 cleared?

Upgrade the firmware of the component specified in the fault value and, if required, also upgrade additional components in the DRIVE-CLiQ line. Then acknowledge the fault immediately; if required, perform a POWER ON before restarting.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F01xxx group · SINAMICS manuals · Siemens manuals