SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Fault · SINAMICS S120, S150

F01275Hardware description error

What it means

F01275 "Hardware description error" is raised by the Control Unit when an error occurs while it accesses the hardware description file on the CompactFlash card. The manual stores this file as DESC0000 in the folder ADDON/SINAMICS/DATA/HW_DESC, inside a subfolder that names the respective drive-object type. The decimal value in r0949 identifies the exact problem, from a missing or unreadable file to an inconsistency in the recorded numbers of adapters and modules. The manual designates the remedy for internal Siemens troubleshooting only, so no on-site measure is described for this fault.

Why it appears

  • An error occurred while the Control Unit was accessing the hardware description file DESC0000 on the CompactFlash card (ADDON/SINAMICS/DATA/HW_DESC, in the subfolder for the drive-object type) — the file may be missing, unreadable, wrongly formatted, of the wrong version or internally corrupt.
  • The hardware description itself is not consistent: the number of Power Stack Adapters (PSA), Sensor Module Cabinets (SMC), Voltage Sensing Modules (VSM), Terminal Modules (TM) or Terminal Boards (TB) recorded there does not fit (fault values 60 to 64).

Reading the message value

The drive writes the following decimal values into r0949 for this fault:

  • 22: File not found.
  • 24: File read access error.
  • 26: Format error.
  • 28: Version error.
  • 30: Internal reader error.
  • 40: Contents error.
  • 45: Hardware description not consistent.
  • 60: Inconsistency: Number of Power Stack Adapters (PSA).
  • 61: Inconsistency: Number of Sensor Module Cabinets (SMC).
  • 62: Inconsistency: Number of Voltage Sensing Modules (VSM).
  • 63: Inconsistency: Number of Terminal Modules (TM).
  • 64: Inconsistency: Number of Terminal Boards (TB).

Parameters the manual names

  • r0949 — fault value: read it as a decimal number and compare it with the list above to see which error occurred while the hardware description file was accessed.

Acknowledging and restarting

The drive is brought to a standstill by this fault and will not restart until it has been acknowledged. Acknowledging requires switching the drive power supply off and on again (POWER ON). Because the manual reserves the correction of the underlying data error for internal Siemens troubleshooting, no further field-side measure is described; if the fault reappears after the restart, the description data on the CompactFlash card must be corrected by Siemens.

The same on every family

Every manual that describes F01275 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: OFF2 Servo: OFF3 Vector: OFF3 Hla: OFF3POWER ONHardware/software error (1)Control Unit (CU)SINAMICS S120, S150 List Manual · p. 2586

The drives this code lives on

F01275 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F01275 mean on a SINAMICS drive?

The Control Unit could not properly access the hardware description file DESC0000 on the CompactFlash card, stored under ADDON/SINAMICS/DATA/HW_DESC. The decimal value in r0949 identifies the specific error, for example 22 for file not found or 45 for a description that is not consistent.

How is F01275 acknowledged?

Only by switching the drive power supply off and on again (POWER ON). If the fault comes back, the hardware description data must be corrected — the manual reserves this for internal Siemens troubleshooting.

What does fault value 60 in F01275 mean?

Fault values 60 to 64 signal an inconsistency in the recorded number of Power Stack Adapters (PSA), Sensor Module Cabinets (SMC), Voltage Sensing Modules (VSM), Terminal Modules (TM) or Terminal Boards (TB).

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F01xxx group · SINAMICS manuals · Siemens manuals