What it means
A49171 is an alarm from the drive's cooling unit monitoring: the conductivity of the cooling liquid has exceeded the level configured as the alarm threshold. The manuals print two slightly different cause wordings for this alarm depending on the drive object, but the remedy is the same in every case. Depending on the drive configuration, the same condition can also be signalled as a message with no reaction (N). The alarm itself causes no trip: the drive keeps its operating state and no acknowledgement is required.
Why it appears
- For one group of drive objects the manual states the cause directly: the conductivity of the cooling liquid has exceeded the selected alarm threshold (p0269[1]). The note printed with it says the threshold cannot be set higher than the fault threshold specified in the equipment description.
- For the other drive objects the manual words the cause as: conductivity monitoring is set for the cooling liquid, visible in bit 7 of the cooling unit status word (r0267.7), with the feedback signal source taken from p0266[7].
What to check
- The remedy the manuals give for this alarm, for every drive object, is:
Check the device to de-ionize the cooling liquid.
No other corrective steps are specified.
Parameters the manual names
- p0269[1] — the selected alarm threshold for the cooling liquid conductivity whose exceedance this alarm reports.
- r0267 — cooling unit status word; bit 7 (r0267.7) shows that conductivity monitoring is set for the cooling liquid.
- p0266 — BI: Cooling unit feedback signals signal source (RKA fdbk S_src); for this alarm the feedback signal source is taken from p0266[7].
- p0262 — Cooling unit fault conductivity delay time (RKA cond t_del); the manual cross-references this parameter for the alarm.
- p0261 — Cooling unit starting time 2 (RKA start time 2); the manual cross-references this parameter for the alarm.
Acknowledging and restarting
No acknowledgement is required; the manuals specify none for this alarm. It is issued with no reaction, so nothing has to be acknowledged or reset at the drive before it continues. Under the alternative configuration (N) the same condition appears as a message with no reaction, likewise without acknowledgement.
The same on every family
Every manual that describes A49171 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | NONE | NONE | Auxiliary unit faulted (20) | None | SINAMICS G130, G150 List Manual · p. 1933 |
| S120, S150 | NONE | NONE | Auxiliary unit faulted (20) | None | SINAMICS S120, S150 List Manual · p. 3290 |
| G130, G150 | NONE | NONE | Auxiliary unit faulted (20) | None | SINAMICS G130, G150 List Manual · p. 1933 |
| S120, S150 | NONE | NONE | Auxiliary unit faulted (20) | None | SINAMICS S120, S150 List Manual · p. 3289 |
The drives this code lives on
A49171 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A49171 in SINAMICS mean?
The cooling unit monitoring reports that the conductivity of the cooling liquid has exceeded the selected alarm threshold (p0269[1]). On some drive objects the manual words the same cause as conductivity monitoring being set for the cooling liquid (r0267.7, from p0266[7]).
How do I fix A49171?
The remedy the manuals print is to check the device to de-ionize the cooling liquid. No further corrective steps are specified for this alarm.
Does A49171 stop the drive or need an acknowledgement?
No. The alarm is issued with no reaction, so the drive keeps its operating state, and no acknowledgement is required. Depending on the configuration, the same condition can also appear as a message with no reaction (N).
Which parameters belong to A49171?
The alarm threshold p0269[1], the cooling unit status word r0267 with bit 7, and the feedback signal source p0266[7]. The manual also cross-references p0261 and p0262 for this alarm.