Mini temperature switch
Description
These high-quality temperature switches have been developed especially for safety-critical applications. The high quality of the products and manufacturing in accordance with ISO 9001 ensure reliable monitoring of your plant. In production, the switches are traced by quality assurance software at every step and subsequently are 100 % tested.
In order to ensure as flexible operation as possible, the temperature switches are fitted with micro switches, which enable the switching of an electrical load of up to AC 250 V, 5 A directly. For lower switching power ratings, such as for PLC applications, micro switches with gold-plated contacts can be selected as an option.
Special features
- Case from AISI 316 (1.4401)
- Ingress protection IP 66, NEMA 4
- Ambient temperature -40 ... +85 °C
- 1 switch point, SPDT, up to 5 A / AC 250 V
- Directly connected or via capillary (up to 10 m capillary)
| Model | TXS |
| Product family | Process Mini Series |
| Subcategory | Temperature switch |
| Temperature ranges | −15…+20 °C · +5…+70 °C · +55…+140 °C · +130…+190 °C · +180…+250 °C |
| Accuracy class | ≤ 1 % of span |
| Process connection | ½ NPT male¾ NPT maleG ½ A maleG ¾ A male |
| Process temperature | −40…+330 °C |
| Electrical connection | Connection cable, 1.5 m, 0.5 mm², silicone insulation |
| Probe material | Stainless steel 316, AISI 316 |
| Ambient temperature | −40…+85 °C |
| IP rating | IP66 |
| Weight | 0.8 kg |
| Certifications | CEEACRoHSREACH |
| Explosion protection | Ex ia I MaEx ia IIIC T85/T135 DaEx ia IIC T6/T4 GaEx ia IIC T6/T4 |
| Sensor type | bimetal |
| Probe length | 125 mm |
| Probe diameter | 9.5 mm |
| Thermowell | No |
| Datasheet languages | EN, DE |
| Measuring range | Setting range depending on the switching direction in °C | Working range | Proof temperature | Max. dead band | SAMA class | |
|---|---|---|---|---|---|---|
| in °C | Rising | Falling | in °C | in °C | in °C | |
| -15 ... +20 | -10 ...+20 | -15 ...+15 | -40 ...+50 | 70 | ≤ 5 | IIC |
| 5 ... 70 | 11 ... 70 | 5 ... 64 | -40 ...+95 | 120 | ≤ 6 | IIC |
| 55 ... 140 | 61 ...140 | 55 ... 134 | -40 ...+160 | 190 | ≤ 6 | IIC |
| 130 ... 190 | 142 ... 190 | 130 ... 178 | -40 ...+215 | 230 | ≤ 12 | IIA |
| 180 ... 250 | 192 ... 250 | 180 ... 238 | -40 ...+300 | 330 | ≤ 12 | IIA |
| Voltage U i | DC 30V |
|---|---|
| Current l i | 100mA |
| Power P i | 0.75W |
| Internal capacitance C i | 0 μF |
| Internal inductance L i | 0mH |
| Electrical rating (resistive load) | Suitable for Ex ia option | |
|---|---|---|
| AC | DC | |
| 250 V, 5 A | 24 V, 5 A | Yes |
| 250 V, 0.5 A | 24 V, 1 A | Yes |
| Logo | Description | Country |
|---|---|---|
| EC declaration of conformity ■ Low voltage directive ■ ATEX 1) (option) IM1 II1GD | European Community | |
| IECEx 1) per IEC 60079-0, IEC 60079-11, IEC 60079-26 (option) Ex ia I Ma Ex ia IIC T6/T4 2) Ga Ex ia IIIC T85/T135 2) Da | IECEx member states | |
| EAC (option) Hazardous areas (option) | Eurasian Economic Community | |
| KOSHA (option) Hazardous areas | South Korea |
Couldn't find the answer in the documentation? An engineer will reply within a business day.