Mini temperature switch
Description
These high-quality temperature switches have been developed especially for safety-critical applications. The high quality of the products and manufacturing in accordance with ISO 9001 ensure reliable monitoring of your plant. In production, the switches are traced by quality assurance software at every step and subsequently are 100 % tested.
In order to ensure as flexible operation as possible, the temperature switches are fitted with micro switches, which enable the switching of an electrical load of up to AC 250 V, 5 A directly. For lower switching power ratings, such as for PLC applications, micro switches with gold-plated contacts can be selected as an option.
Special features
- No power supply needed for switching of electrical loads
- Setting ranges from -15 ... +20 °C to 180 ... 250 °C
- Repeatability of the set point ≤ 1 % span
- 1 set point, SPDT, high switching power up to AC 250 V, 5 A
- Direct mounting or remote mounting with capillary ≤ 10 m
| Model | TXA |
| Product family | Process Mini Series |
| Subcategory | Temperature switch |
| Temperature ranges | −15…+20 °C · +5…+70 °C · +55…+140 °C · +130…+190 °C · +180…+250 °C |
| Accuracy class | ≤ 1 % of span |
| Process connection | ½ NPT male¾ NPT maleG ½ A maleG ¾ A male |
| Process temperature | −40…+300 °C |
| Electrical connection | Connection cable 1.5 m, 0.5 mm², silicone insulation |
| Probe material | stainless steel, Stainless steel 316 |
| Ambient temperature | −40…+85 °C |
| IP rating | IP66 |
| Weight | 0.8 kg |
| Certifications | CEKOSHARoHSREACHEACEAC Ex |
| Explosion protection | Ex d I MbEx d IIC T6/T4 GbEx tb IIIC T85/T135 Db |
| Sensor type | bimetal |
| Probe length | 125 mm |
| Probe diameter | 9.5 mm |
| Thermowell | No |
| Datasheet languages | EN |
| Contact version | Electrical rating (resistive load) | ||
|---|---|---|---|
| AC | DC | ||
| E | 1 x SPDT, silver, hermetically sealed | 250 V, 5 A | 24 V, 5 A |
| J | 1 x SPDT, gold-plated, hermetically sealed | 250 V, 0.5 A | 24 V, 1 A |
| Measuring range | Setting range depending on the switching direction in °C | Working range | Proof temperature | Max. dead band | SAMA class | |
|---|---|---|---|---|---|---|
| in °C | Rising | Falling | in °C | in °C | in °C | |
| -15 ... +20 | -10 ...+20 | -15 ...+15 | -40 ...+50 | 70 | ≤ 5 | IIC |
| 5 ... 70 | 11 ... 70 | 5 ... 64 | -40 ...+95 | 120 | ≤ 6 | IIC |
| 55 ... 140 | 61 ...140 | 55 ... 134 | -40 ...+160 | 190 | ≤ 6 | IIC |
| 130 ... 190 | 142 ... 190 | 130 ... 178 | -40 ...+215 | 230 | ≤ 12 | IIA |
| 180 ... 250 | 192 ... 250 | 180 ... 238 | -40 ...+300 | 330 | ≤ 12 | IIA |
| Logo | Description | Country |
|---|---|---|
| EC declaration of conformity ■ Low voltage directive ■ ATEX 1) IM2 II2GD | European Community | |
| IECEx 1) per IEC 60079-0, IEC 60079-1, IEC 60079-26, IEC 60079-31 Ex d I Mb Ex d IIC T6/T4 2) Gb Ex tb IIIC T85/T135 2) Db | IECEx member states | |
| EAC (option) Hazardous areas | Eurasian Economic Community | |
| KOSHA (option) Hazardous areas | South Korea |