AI helper
Describe the task — I'll match 3 WIKA models in 30 seconds
TCS 1
TCS
On order
WIKA · Temperature measurement · Family Process Compact Series

Compact temperature switch

Mechatronic temperature switch for safety-critical applications in process industries, with direct or remote mounting and intrinsic safety Ex ia option.
Range
-30…250 °C
Protection
IP66
RoHSEACKOSHACEEx ia IIC T6/T4 GaEx ia I MaEx ia IIIC T85/T135 Da IP66ATEX II 1 GDIECExEx ia IIIC T85/T135 Da
Price
On request
Depends on configuration
Request a quote
+38 (067) 285-77-70·info@avigan.com.uaViberTelegram

Description

These high-quality temperature switches have been developed especially for safety-critical applications. The high quality of the products and manufacturing in accordance with ISO 9001 ensure reliable monitoring of your plant. In production, the switches are traced by quality assurance software at every step and subsequently are 100 % tested.

In order to ensure as flexible operation as possible, the temperature switches are fitted with micro switches, which enable the switching of an electrical load of up to AC 250 V, 15 A directly. For lower switching power ratings, such as for PLC applications, micro switches with gold-plated contacts can be selected as an option.

for further approvals see page 4

Special features

  • Case aluminium, epoxy resin coated
  • Ingress protection IP 65, NEMA 4
  • Ambient temperature -40 ... +85 °C
  • 1 switch point, SPDT or DPDT with a high contact rating of up to 15 A / AC 250 V
  • Capillary up to 10 m
Identification
ModelTCS
Product familyProcess Compact Series
SubcategoryTemperature switch
Measuring range
Temperature ranges−30…+10 °C · −15…+40 °C · +10…+70 °C · +40…+100 °C · +70…+120 °C · +90…+160 °C · +130…+190 °C · +160…+250 °C
Accuracy
Safety integrity level (SIL)SIL 2 per IEC 61508
Process conditions
Process connection
½ NPT male¾ NPT maleG ½ A maleG ¾ A male½ NPT female¾ NPT femaleM 20 x 1.5G ¾ female
Process temperature−40…+280 °C
Electrical characteristics
Electrical connection½ NPT female
Materials
Probe materialstainless steel, stainless steel 316L
Operating environment
Ambient temperature−40…+85 °C
IP ratingIP66
Weight1 kg
Certifications and approvals
Certifications
RoHSEACKOSHACE
Explosion protection
Ex ia IIC T6/T4 GaEx ia I MaEx ia IIIC T85/T135 Da IP66ATEX II 1 GDIECExEx ia IIIC T85/T135 Da
Additional details
Sensor typebimetal
Probe length125 mm
Probe diameter9.5 mm
Datasheet languagesEN
Tables from datasheet
Contact versionElectrical rating (resistive load)Suitable for Ex ia option
ACDC
A1 x SPDT, silver250 V, 15 A24 V, 2 A, 125 V, 0.5 A, 220 V, 0.25 ANo
B1 x SPDT, silver, hermetically sealed, argon gas filling 2)250 V, 15 A24 V, 2 A, 220 V, 0.5 AYes
C1 x SPDT, gold-plated, hermetically sealed, argon gas filling 2)125 V, 1 A24 V, 0.5 AYes
G1 x DPDT, silver250 V, 5 A24 V, 0.5 ANo
H1 x DPDT, silver, hermetically sealed, air filling250 V, 5 A24 V, 0.5 AYes
Maximum values
Voltage U iDC 30V
Current l i100mA
Power P i0.75W
Internal capacitance C i0 μF
Internal inductance L i0mH
SAMA class 1)Stem∅D inmmActive length X inmmInsertion length Y inmm
IIC9.565125 2)
IIA9.555125 2)
Setting rangeWorking rangeProof temperatureFixed dead band for contact versionSAMA class
in °Cin °Cin °C1 contact SPDT A, B, C in °C1 contact DPDT G in °C1 contact DPDT H in °C
-30 ...+10-40 ...+6090≤ 2≤ 2≤ 8IIC
-15 ...+40-40 ...+6090≤ 1.5≤ 2≤ 8IIC
10 ... 70-40 ...+7090≤ 1.5≤ 2≤ 8IIC
40 ... 100-40 ...+120140≤ 1.5≤ 2≤ 8IIC
70 ... 120-40 ...+170180≤ 1.5≤ 4≤ 16IIA 1)
90 ... 160-40 ...+170180≤ 2≤ 4≤ 16IIA
130 ... 190-40 ...+190210≤ 2.5≤ 4≤ 16IIA
160 ... 250-40 ...+280300≤ 2.5≤ 4≤ 16IIA
View all (6)
LogoDescriptionCountry
EU declaration of conformity ■ Low voltage directive ■ RoHS directive ■ ATEX 4) directive (option) I M1 (only available with stainless steel 316L switch enclosure) II1GDEuropean Union
IECEx 4) (option) Ex ia I Ma (only available with stainless steel 316L switch enclosure) Ex ia IIC T6/T4 5) Ga Ex ia IIIC T85/T135 5) Da IP66International
EAC (option) Hazardous areasEurasian Economic Community
KOSHA (option) Hazardous areasSouth Korea
LogoDescription
SIL 2 rating (option) , per IEC 61508 Functional safety The electrical rating for DC applications is limited to 30V / 100 mA.