Compact temperature switch, flameproof enclosure Ex d
Description
These high-quality temperature switches have been developed especially for safety-critical applications. The high quality of the products and manufacturing in accordance with ISO 9001 ensure reliable monitoring of your plant. In production, the switches are traced by quality assurance software at every step and subsequently are 100 % tested.
In order to ensure as flexible operation as possible, the temperature switches are fitted with micro switches, which enable the switching of an electrical load of up to AC 250 V, 15 A directly. For lower switching power ratings, such as for PLC applications, micro switches with gold-plated contacts can be selected as an option.
Special features
- Case aluminium, epoxy resin coated
- Ingress protection IP 65, NEMA 4
- Ambient temperature -40 ... +85 °C
- 1 switch point, SPDT or DPDT with a high contact rating of up to 15 A / AC 250 V
- Capillary up to 10 m
| Model | TCA |
| Product family | Process Compact Series |
| Subcategory | Temperature switch |
| Temperature ranges | −30…+10 °C · −15…+40 °C · +10…+70 °C · +40…+100 °C · +70…+120 °C · +90…+160 °C · +130…+190 °C · +160…+250 °C |
| Safety integrity level (SIL) | SIL 2 per IEC 61508 |
| Process connection | ½ NPT male¾ NPT maleG ½ A maleG ¾ A male |
| Process temperature | −40…+280 °C |
| Power supply | No power supply needed |
| Electrical connection | ½ NPT female (standard), ¾ NPT, M 20 x 1.5, G ½, G ¾ female, cable glands (armoured/non-armoured, Ex d, nickel-plated brass or stainless steel) |
| Probe material | stainless steel, Stainless steel 316L |
| Ambient temperature | −40…+85 °C |
| IP rating | IP66 |
| Weight | 1 kg |
| Certifications | CERoHSEACINMETROPESOKOSHA |
| Explosion protection | Ex db I MbEx db IIC T6/T4 GbEx tb IIIC T85/T135 Db IP66Ex db IIC T6/T4Ex tb IIIC T85/T135 GbATEX II 2 GD |
| Sensor type | vapour pressure system |
| Probe length | 125 mm |
| Probe diameter | 9.5 mm |
| Thermowell | No |
| Datasheet languages | EN, DE |
| Contact version | Electrical rating (resistive load) | ||
|---|---|---|---|
| AC | DC | ||
| A | 1 x SPDT, silver | 250 V, 15 A | 24 V, 2 A, 125 V, 0.5 A, 220 V, 0.25 A |
| B | 1 x SPDT, silver, hermetically sealed, argon gas filling 2) | 250 V, 15 A | 24 V, 2 A, 220 V, 0.5 A |
| C | 1 x SPDT, gold-plated, hermetically sealed, argon gas filling 2) | 125 V, 1 A | 24 V, 0.5 A |
| G | 1 x DPDT, silver | 250 V, 5 A | 24 V, 0.5 A |
| H | 1 x DPDT, silver, hermetically sealed, air filling | 250 V, 5 A | 24 V, 0.5 A |
| SAMA class 1) | Stem∅D inmm | Active length X inmm | Insertion length Y inmm |
|---|---|---|---|
| IIC | 9.5 | 65 | 125 2) |
| IIA | 9.5 | 55 | 125 2) |
| SAMA class 1) | Bulb | Insertion length inmm | Capillary length K inm | ||
|---|---|---|---|---|---|
| Stem ∅D inmm | Active length X inmm | Y min | Y max | ||
| IIC | 9.5 | 71 | 100 | 350 | 2 |
| 84 | 130 | 900 | 5 | ||
| 124 | 170 | 1,800 | 10 | ||
| IIA 3) | 9.5 | 55 | 100 | 350 | 2 |
| 55 | 100 | 900 | 5 | ||
| 55 | 100 | 1,800 | 10 |
| Setting range | Working range | Proof temperature | Fixed dead band for contact version | SAMA class | ||
|---|---|---|---|---|---|---|
| in °C | in °C | in °C | 1 contact SPDT A, B, C in °C | 1 contact DPDT G in °C | 1 contact DPDT H in °C | |
| -30 ...+10 | -40 ...+60 | 90 | ≤ 2 | ≤ 2 | ≤ 8 | IIC |
| -15 ...+40 | -40 ...+60 | 90 | ≤ 1.5 | ≤ 2 | ≤ 8 | IIC |
| 10 ... 70 | -40 ...+70 | 90 | ≤ 1.5 | ≤ 2 | ≤ 8 | IIC |
| 40 ... 100 | -40 ...+120 | 140 | ≤ 1.5 | ≤ 2 | ≤ 8 | IIC |
| 70 ... 120 | -40 ...+170 | 180 | ≤ 1.5 | ≤ 4 | ≤ 16 | IIA 1) |
| 90 ... 160 | -40 ...+170 | 180 | ≤ 2 | ≤ 4 | ≤ 16 | IIA |
| 130 ... 190 | -40 ...+190 | 210 | ≤ 2.5 | ≤ 4 | ≤ 16 | IIA |
| 160 ... 250 | -40 ...+280 | 300 | ≤ 2.5 | ≤ 4 | ≤ 16 | IIA |
View all (6)
| Logo | Description | Country |
|---|---|---|
| EU declaration of conformity ■ Low voltage directive ■ RoHS directive ■ ATEX 1) directive I M2 (only available with stainless steel 316L switch enclosure) II2GD | European Union | |
| IECEx 1) Ex db I Mb (only available with stainless steel 316L switch enclosure) Ex db IIC T6/T4 2) Gb Ex tb IIIC T85/T135 2) Db IP66 | International | |
| EAC (option) Hazardous areas 1) | Eurasian Economic Com- munity | |
| KOSHA (option) Hazardous areas 1) | South Korea | |
| INMETRO (option) ■ Metrology, measurement technology ■ Hazardous areas 1) | Brazil | |
| - | PESO (option) Hazardous areas 1) | India |
| Logo | Description |
|---|---|
| SIL 2 rating (option) , per IEC 61508 Functional safety The electrical rating for DC applications is limited to 30V / 100 mA. |
Couldn't find the answer in the documentation? An engineer will reply within a business day.