WIKA · SF6 gas solutions · Family GIR
Gas detector
Gas detector based on infrared technology for locating and quantifying SF6 gas leaks, with high sensitivity down to 0.6 ppmv and immunity to moisture and VOCs.
Range
0…2000 ppmv
Output
Visual alarm · Audible alarm
Price
On request
Depends on configuration
Description
The model GIR-10 gas detector is used to detect even the smallest concentrations of SF6 gas, making it ideally suited for locating leakage and determining the size of it.
Special features
- Even the smallest concentrations of down to 0.6 ppmv can be detected
- Responds only to SF 6 gas and is therefore insensitive to moisture and the usual volatile organic compounds (VOC)
- Easy operation
- Fast response time
- Calibration ex-works using certified test gases
Identification
| Model | GIR-10 |
| Product family | GIR |
| Subcategory | Gas detector |
Measuring range
| Pressure ranges | 0…2000 ppmv · 0…50 ppmv · 0…1000 ppmv |
Process conditions
| Process connection | Connection hose |
Electrical characteristics
| Output signal | Visual alarm · Audible alarm |
Materials
| Wetted parts material | Infrared sensor with gas sample chamber, Particle filter |
Operating environment
| Ambient temperature | +0…+50 °C |
| Weight | 3 kg |
Additional details
| Datasheet languages | EN |
Tables from datasheet
Basic information
| Measurement principle | Non-dispersive infrared technology (NDIR) |
|---|---|
| Voltage supply | ■ Lithium-ion rechargeable battery for approx. 8 hours operating time ■ Battery charger AC 100 ... 265 V, 50/60 Hz |
| Calibration cycle | After 1,200 hours of operation or at least every 2 years |
| Permissible temperature ranges | |
| Storage temperature | -10 ...+60 °C [14 ... 140 °F] |
| Operating temperature | 0 ... 50 °C [32 ... 122 °F] |
| Dimensions | |
| Console | 285 x 195 x 80 mm[11.22 x 7.67 x 3.14 in] |
| Hand-held | 210 x 110 x 90 mm[8.26 x 4.33 x 3.54 in] |
| Weight | |
| Console | 2.5 kg [5.51 lb] |
| Hand-held | 0.5 kg [1.1 lb] |
Sensor (SF₆ gas version, 0 ... 2,000 ppm v )
| Application area | Leakage detection |
|---|---|
| Medium | SF₆ gas |
| Measuring range | 0 ... 2,000 ppm v |
| Detection limit 1) | 3 ppm v |
| Detectable leakage rate (cal- culated) | 3 g/year (corresponds to 1.81 x 10 -5 mbar x l/s) |
| Accuracy 2) | |
| ≤ 100 ppmv | ±3 ppm v |
| ≥ 100 ...≤ 2,000 ppmv | ±2 %of end value |
| Resolution | 1 ppm v |
| Measuring units | ■ ppm v ■ g/y ■ cc/s |
| Response time T90 | < 1 second |
| Alarm signal | Visual and audible |
Sensor (SF₆ gas version, 0 ... 50 ppm v )
| Application area | Integral leakage testing |
|---|---|
| Medium | SF 6 gas |
| Measuring range | 0 ... 50 ppm v |
| Detection limit 1) | 0.6 ppm v |
| Detectable leakage rate (cal- culated) | 0.34 g/year (corresponds to 1.81 x 10 -6 mbar x l/s) |
| Accuracy | |
| ≤ 10 ppm v | ±0.5 ppm v |
| > 10 ppm v | ±2% |
| Resolution | 0.1 ppm v |
| Measuring units | ppm v |
| Response time T90 | < 12 seconds |
| Alarm signal | Visual and audible |
Sensor (CO 2 version, 0 ... 1,000 ppm v )
| Application area | Integral leakage testing |
|---|---|
| Medium | CO 2 |
| Measuring range | 0 …1,000 ppm v |
| Detection limit 1) | 10 ppm v |
| Detectable leakage rate (calcu- lated) | 3.43 g/year (corresponds to 1.81 x 10 -5 mbar x l/s) |
| Accuracy | ±50 ppm v |
| Resolution | 1 ppm v |
| Measuring unit | ppm v |
| Response time T90 | < 1 second |
| Alarm signal | Visual |
View all (5)
| Description | Order number |
|---|---|
| Particle filter | 14005140 |
| Transparent filter cap | 14005999 |
| O-ring | 14004754 |
| Measuring tip with injection needle | 14093643 |
| Sampling bag, 5 litres | 14029961 |
Application areas not described yet
Describe your operating conditions — our engineer will suggest a model and use case.
Couldn't find the answer in the documentation? An engineer will reply within a business day.