AI helper
Describe the task — I'll match 3 WIKA models in 30 seconds
DPT-20 1
DPT-20
On order
WIKA · Pressure measurement · Family DPT

Differential pressure transmitter

Differential pressure transmitter with high accuracy and multiple output signals, suitable for industrial applications including process, chemical, and petrochemical industries.
Range
-16…16 bar
Output
4-20 mA · 4-20 mA HART
Accuracy
See specifications by range
Protection
IP65
CENACEintrinsic safetyflameproof enclosure
Price
On request
Depends on configuration
Request a quote
+38 (067) 285-77-70·info@avigan.com.uaViberTelegram

Description

The model DPT-20, with its 4 ... 20 mA, 4 ... 20 mA HART ® , FOUNDATION™ Fieldbus or PROFIBUS ® PA output signals, combined with the intrinsic safety or flameproof enclosure ignition protection type, is ideally suited for application in appropriate systems. The development of the transmitter in accordance with the demands of SIL (Safety Integrated Level) IEC 61508 also makes it applicable for plants with special safety requirements.

Special features

  • High measurement accuracy
  • Freely scalable measuring ranges
  • Developed in accordance with the SIL 2 requirements
  • Seven different case variants
  • Configuration via DTM (Device Type Manager) in accordance with the FDT (Field Device Tool) concept (e.g. PACTware™)
Identification
ModelDPT-20
Product familyDPT
SubcategoryDifferential pressure transmitter
Measuring range
Pressure ranges-0.01…0.01 bar · -0.03…0.03 bar · -0.1…0.1 bar · -0.5…0.5 bar · -3…3 bar · -16…16 bar · -0.15…0.15 psi · -1.5…1.5 psi · -7.5…7.5 psi · -45…45 psi · -240…240 psi
Accuracy
Accuracy classSee specifications by range
Accuracy standardIEC 62828, IEC 61298
Safety integrity level (SIL)SIL 2 (IEC 61508)
Process conditions
Process connection
½ NPT¼ NPTG 1/2M20x1.5
Process temperature−40…+85 °C
Electrical characteristics
Output signal4-20 mA · 4-20 mA HART · FOUNDATION™ Fieldbus · PROFIBUS® PA
Power supply10...30 V DC
Electrical connectionM20 x 1.5
Materials
Case materialplastic, aluminium, stainless steel (316L)
Wetted parts material316L, Hastelloy
Sealing materialFKM, EPDM, FPM, NBR
Operating environment
Ambient temperature−40…+85 °C
IP ratingIP65
Weight1.5 kg
Certifications and approvals
Certifications
CENACE
Explosion protection
intrinsic safetyflameproof enclosure
Additional details
Datasheet languagesEN, DE, ES, FR
Tables from datasheet
Accuracy specifications
Measuring deviation determined using the limit point method IEC 62828/IEC 61298 1)
Differential pressureMeasuring ranges 10 and 30 mbar [0.15 and 0.45 psi]■ TD ≤ 5:1 ±0.1 %of span ■ TD > 5:1 ±0.02%xTD
Measuring range 100 and 500 mbar [1.5 and 7.5 psi]■ ToTD 10:1 ±0.065 %of span ■ TD > 10:1 ±0.035 %+0.01%xTD
Measuring range 3 bar [45 psi]■ ToTD 10:1 ±0.065 %of span ■ >TD 10:1 ±0.015 %+0.005%xTD
Measuring range 16 bar [240 psi]■ ToTD 10:1 ±0.065 %of span ■ >TD 10:1 ±0.035 %+0.01%xTD
Static pressure< ±0.1 %(scaling with static pressure is not possible)
Adjustability, differential pressure
Pressure value of zero point-120 ...+120 %of the nominal measuring range (with -100 ...+100 mbar [-1.5 ... +1.5 psi] measuring range, 100 mbar [1.5 psi] is the nominal measuring range)
Pressure value of spanZero point + (-240 …+240 %)
Adjustability, level
Percentage value-10…+100%
Pressure value-120…+120%
Adjustability, flow
Pressure value of zero point-120…+120%
Pressure value of span-120…+120%
Influence of mounting position< 0.35 mbar [0.003 psi] per 10° inclination from the vertical
Influence of the medium and ambient temperature
-10 ...+60 °C [14 ... 140 °F]Measuring range 10 mbar [0.15 psi]< ±0.15%+0.2%xTD
Measuring range 30 mbar [ 0.45 psi]< ±0.15%+0.1%xTD
Measuring range 100 mbar [1.5 psi]< ±0.15 %+0.15%xTD
Measuring range 500 mbar [7.5 psi]< ±0.15 %+0.05%xTD
Measuring range 3 bar [45 psi]< ±0.15 %+0.05%xTD
Measuring range 16 bar [240 psi]< ±0.15 %+0.15%xTD
-40 …-10 °C [-40 ...+14 °F] / 60 …85°C[140 ... 185 °F]Measuring range 10 mbar [0.15 psi]< ±0.4%+0.3%xTD
Measuring range 30 mbar [ 0.45 psi]< ±0.2 %+0.15%xTD
Measuring range 100 mbar [1.5 psi]< ±0.15%+0.2%xTD
Measuring range 500 mbar [7.5 psi]< ±0.2 %+0.06%xTD
Measuring range 3 bar [45 psi]< ±0.2 %+0.06%xTD
Measuring range 16 bar [240 psi]< ±0.15%+0.2%xTD
Long-term stability
Differential pressure■ < 0.065 %xTD(1 year) ■ < 0.1 %xTD(5 years) ■ < 0.15 %xTD(10 years)
Static pressure■ < ±0.065 %(1 year) ■ < ±0.1 %(5 years) ■ < ±0.15 %(10 years)
Thermal change of zero point and output span depending on the static pressure
Measuring ranges 10 and 30 mbar [0.15 and 0.45 psi]To nominal pressure40 bar [600 psi]
Influence on the zero point< ±0.1%xTD
Influence on the span< ±0.1%
Measuring ranges 100 and 500 mbar [1.5 and 7.5 psi]To nominal pressure160 bar [2,400 psi]
Influence on the zero point< ±0.1%xTD
Influence on the span< ±0.1%
Accuracy specifications
Measuring ranges 3 and 16 bar [45 and 240 psi]To nominal pressure400 bar [5,800 psi]
Influence on the zero point< ±0.25%xTD
Influence on the span< ±0.25%
Thermal changeChange of the current output with 4 ...20 mAsignals: 0.05 %per 10 K based on 20 °C [68 (maximum 0.15 %at set measuring span) in the ambient temperature range -40 …+80 °C [-40 …+176 °F]
Reference conditions per IEC 61298-1
Temperature+18 ...+30 °C [64 ... 86 °F]
Air pressure860 ... 1,060 mbar [86 ... 106 kPa, 12.5 ... 15.4 psig]
Air humidity45 ... 75 %r.h.
Characteristic curve determinationTerminal method per IEC 61298-2
Curve characteristicsLinear
Reference mounting positionVertical, i.e. vertical process assembly (connections are on the side)
Measuring range
Measuring range 1)-10 mbar ... +10 mbar [-0.15 ... +0.15 psi]-30 mbar ... +30 mbar [-0.45 ... +0.45 psi]-100 mbar ... +100 mbar [-1.5 ...+1.5 psi]-500 mbar ... +500 mbar [-7.5 ...+7.5 psi]-3 bar ...+3 bar [-45 ...+45 psi]-16 bar ... +16 bar [-240 ... +240 psi]
Maximum operating pressure40 bar [600 psi]160 bar [2,400 psi] (option: 400 bar [5,800 psi])
Lowest static pressure 2)1 mbar abs.[0.015 psi], with application for oxygen the static pressure should not be lower than 10 mbar abs. [0.15 psi]
Turndown ratioMaximum permissible turndown is unlimited (max. 20:1 is recommended)
Overload, on one side40 bar [600 psi]160 bar [2,400 psi] (option: 400 bar [5,800 psi])
Overload, on both sides60 bar [900 psi]240 bar [6,300 psi] (option: 630 bar [9,100 psi])
ConnectionMountingMaterialEquipment
¼-18 NPT IEC 615187/16-20 UNFAISI 316L (1.4404)2 vent valves 1)
¼-18 NPT IEC 615187/16-20 UNFHastelloy C276 (2.4819)2 vent valves 1)
View all (14)
ConnectionMountingMaterialEquipment
¼-18 NPT IEC 615187/16-20 UNFAISI 316L (1.4404)2 vent valves, 4 plug screws 1)
¼-18 NPT IEC 615187/16-20 UNFHastelloy C276 (2.4819)2 vent valves, 4 plug screws 1)
Output signal
Signal type4 …20mA, 2-wire, (option: 4 ... 20 mA, 2-wire with superimposed communication signal HART ® , FOUNDATION™ Fieldbus, PROFIBUS ® PA)
Permissible max. loadR A = (U B - U Bmin )/0.023 A
Dead time■ 160 ms (10 and 30 mbar [0.15 and 0.45 psi]) ■ 130 ms (remaining measuring ranges)
Time constant (90 %)■ 115 ms (10 and 30 mbar [0.15 and 0.45 psi]) ■ 95 ms (100 mbar [1.5 psi]) ■ 75 ms (500 mbar [7.5 psi]) ■ 60 ms (3 bar [45 psi] and 16 bar [240 psi])
Damping (63 %of the input variable)0 …999 s, adjustable
Deviation through interferenceStrong, high-frequency fields can influence the current output with 4 …20mA, within the scope of EN 61326-1, by up to ±80 µA.
Voltage supply
Supply voltage4 ...20mAInactive backlightingDC 11 ...35V
Active backlightingDC 16 ...35V
4 ... 20 mAwith a superimposed HART ® communication signalInactive backlightingDC 11 ...35V
Active backlightingDC 16 ...35V
PROFIBUS ® PA (max. 32 BUS instruments)Inactive backlightingDC 9 ...32V
Active backlightingDC 13.5…32V
FOUNDATION™ Fieldbus (max. 32 BUS instruments)Inactive backlightingDC 9 ...32V
Active backlightingDC 13.5…32V
Electrical safetyOvervoltage category III, protection class II
Electrical connection
Spring-loaded terminalsWire cross-section■ Wire or strand: 0.2 ... 2.5 mm² (AWG 24 ... 14) ■ Strand with end splice: 0.2 ... 1.5 mm² (AWG 24 ... 16)
Cable glands M20 x 1.5
Sealed with blind plug
Plastic, PASealingNBR
Cable diameter■ 5 ... 9 mm[0.2 ... 0.35 in] ■ 6 ... 12 mm[0.24 ... 0.47 in] ■ 10 ... 14 mm[0.39 ... 0.55 in]
Brass, nickel-platedSealingNBR
Cable diameter■ 5 ... 9 mm[0.2 ... 0.35 in] ■ 6 ... 12 mm[0.24 ... 0.47 in]
Stainless steelSealingNBR
Cable diameter7 ... 12 mm[0.28 x 0.47 in]
Cable glands ½ NPT
Sealed with blind plug
Plastic, PACable diameter■ 5 ... 9 mm[0.2 x 0.35 in] ■ 6 ... 12 mm[0.24 ... 0.47 in] ■ 10 ... 14 mm[0.39 ... 0.55 in]
Brass, nickel-platedCable diameter■ 5 ... 9 mm[0.2 ... 0.35 in] ■ 6 ... 12 mm[0.24 ... 0.47 in]
Electrical safetyReverse polarity protection
Material
Material (wetted)
Process connection316L (1.4404) (option: Hastelloy C276 (2.4819))
Diaphragm316L (1.4435) (option: Hastelloy C276 (2.4819)
SealingFKM (option:EPDM, copper)
Case material
Single chamber case, plasticPBT, polyester
Single chamber case, aluminiumDie-casting AlSi10Mg, powder-coated on PE basis
Single chamber case, cast stainless steelStainless steel 316L
Single chamber case, electropolished stainless steel, deep-drawnStainless steel 316L
Double chamber case, plasticPBT, polyester
Double chamber case, aluminiumDie-casting AlSi10Mg, powder-coated on PE basis
Double chamber case, cast stainless steelStainless steel 316L
Pressure transmission medium 1)Silicone oil (halocarbon oil for oxygen applications)
Display and operating unit (option)
BacklightingYes
BackgroundGrey, black digits
UpgradableYes (for order numbers, see &#x27;Accessories&#x27;)
Menu languagesGerman English French SpanishPolish Italian Dutch JapaneseTurkish
Display size5-digit measured value display, adjustable (option: bar graph display) Max. 5 digits, size 7 x 13 mm[0.28 x 0.51 in]
Ingress protection (IP code) per IEC 60529■ IP20 (loose) ■ IP40 (built-in without cover)
MaterialCase from ABS, window from polyester film
Operating conditions
Permissible temperature ranges
Ambient■ -40 …+80 °C [-40 ...+176 °F] (without display) ■ -20 …+70 °C [-4 ...+158 °F] (with display)
Storage and transport-60 …+80 °C [-40 ...+176 °F]
Restrictions to medium temperature due to the sealing material
FKM-20 …+85 °C [-4 ...+185 °F]
EPDM, copper-40 …+85 °C [-40 ...+185 °F]
FKM, oil- and grease-free-10 …+85 °C [14 ... 185 °F]
For oxygen applications (max. static pressure: 160 bar [2,400 psi])Copper-20 …+60 °C [-4 ...+140 °F]
EPDM-10 …+60 °C [-4 …+140 °F]
FKM-10 …+60 °C [14 ... 140 °F]
Temperature limitsWith differential pressure lines longer than 100 mm:-40 …+120 ° [-40 ... 248 °F]
Vibration resistance per IEC 60068-2-6 1)4 g (5 …200 Hz), vibration under resonance
Shock resistance per IEC 60068-2-2750 g for 2.3 ms, mechanical shock
Ingress protection (IP code) per IEC 60529IP66/67 (standard case)
WeightApprox. 4.2 …4.5 kg [9.26 ... 9.92 lbs] depending on the process connection and case variant
LogoDescriptionCountry
EU declaration of conformityEuropean Union
EMCdirective, interference emission (group 1, class B) and immunity per EN 61326-1:2013 (industrial application), EN 61326-2-3:2013 1)
Pressure equipment directive
RoHS directive
LogoDescription
SIL IEC 61508 / IEC 6151SIL 2 (option) Functional safety ■ 1-channel operation up to SIL 2
-NAMUR recommendations NE 021 - Electrical compatibility of equipment NE 043 - Signal level for failure information NE 053 - Compatibility of field instruments
Certificates
Certificates■ 2.2 test report per EN 10204 (e.g. state-of-the-art manufacturing, material proof, indication accuracy) ■ 3.1 inspection certificate per EN 10204 (e.g. material proof for wetted metal parts, indication accuracy, calibration certificate)
CalibrationDAkkS calibration certificate (traceable and accredited in accordance with ISO/IEC 17025)
DescriptionOrder number
Display module, model DIH52-F 5-digit display, 20-segment bar graph, without separate power supply, with additional HART ® functionality. Automatic adjustment of measuring range and span. Secondary-master functionality: Setting the measuring range and unit of the connected transmitter possible using HART ® standard commands. Optional: Explosion protection per ATEXOn request
HART ® modem for USB interface, specifically designed for use with notebooks (model 010031)11025166
HART ® modem for RS-232 interface (model 010001)7957522
HART ® modem for Bluetooth interface Ex ia IIC (model 010041)11364254
PowerXpress HART ® modem, with optional power supply (model 010031P)14133234
3-valve manifold, form A, ½NPTfemale (IEC 61518-A) Stainless steel, PN 420, form A, NACE-compliant, 3.1 material certificate13382498
3-valve manifold, form A, 1/4 NPT female (IEC 61518-A) Stainless steel, PN 420, form A, NACE-compliant, 3.1 material certificate13382510
5-valve manifold, form A, ½NPTfemale (IEC 61518-A) Stainless steel, PN 420, form A, NACE-compliant, 3.1 material certificate13382552
5-valve manifold, form A, 1/4 NPT female (IEC 61518-A) Stainless steel, PN 420, form A, NACE-compliant, 3.1 material certificate13382561
Oval flange, 1/4 NPT, stainless steel (2 pieces) Stainless steel, PN 420, form A, NACE-compliant, 3.1 material certificate13382609
Oval flange, ½NPT, stainless steel (2 pieces) Stainless steel, PN 420, form A, NACE-compliant, 3.1 material certificate13382595
Set of sealing plugs, 1/4 NPT, 316L (2 pieces) For the vents at the differential pressure sensor Included in delivery with lateral venting, except for process connection from Hastelloy14035620
Set of vent valves, 1/4 NPT, 316L (2 pieces) For the vents at the differential pressure sensor Included in delivery, except for process connection from Hastelloy14368975
Instrument mounting bracket for wall or pipe mounting with mounting bracket and screws, stainless steel11553945
Overvoltage protection For transmitters, 4 ... 20 mA, M20 x 1.5, series connection14002489
For transmitters, PROFIBUS ® PA, M20 x 1.5, series connection14013659
Model DI-PT-R display and operating module, case cover aluminium with window12298884
Model DI-PT-R display and operating module, case cover electropolished cast stainless steel with window13315269
Model DI-PT-R display and operating module, case cover plastic with window13315277
Model DI-PT-R display and operating module, case cover cast stainless steel with window for single chamber case12298906
Model DI-PT-R display and operating module, case cover cast stainless steel with window for double chamber case14045598
Model DI-PT-E external display and operating module, aluminium case12354954
Model DI-PT-E external display and operating module, cast stainless steel case12355101
Model DI-PT-E external display and operating module, plastic case14134247