A2G-85 1
A2G-85
On order
WIKA · Temperature measurement · Family A2G

Ventilation duct sensor for CO 2 and temperature

Ventilation duct sensor for CO2 and temperature with integrated temperature measurement and electrical output signals.
Range
0…50 °C
Output
DC 0 ... 10 V · 4 ... 20 mA
Accuracy
< 0.5 °C
Protection
IP54
CERoHS
Price
On request
Depends on configuration
Request a quote
+38 (067) 285-77-70·info@avigan.com.uaViberTelegram

Description

The model A2G-85 ventilation duct sensor with an integrated temperature measurement is suitable for direct mounting on circular ventilation pipes or rectangular ventilation ducts.

The A2G-85 is a high-quality product solution for ventilation and air-conditioning applications. This ventilation duct sensor measures carbon dioxide (CO2 ) in accordance with the NDIR measuring principle, and in addition also temperature. Due to the combination of these two measurement parameters in one single instrument, the material and mounting cost is considerably reduced.

Ventilation duct sensor, model A2G-85, without LC display

The adjustable mounting flange enables a quick installation. The illuminated LC display provides good readability, even from a distance. The screwless cover enables fast wiring and commissioning.

The measurement of the CO2 and the air temperature as the basis of demand-orientated control/regulation is gaining ever more importance in the ventilation and air-conditioning industry. The sensor signals for both measurement parameters are transmitted to the control/regulation or building automation with analogue output signals (0 ... 10 V, 4 … 20 mA) or digital Modbus ® protocol.

Special features

  • Electrical output signal DC 0 … 10 V, 4 … 20 mA or Modbus ®
  • Simple installation
  • Compact and robust design
  • Maintenance-free
Identification
ModelA2G-85
Product familyA2G
SubcategoryVentilation duct sensor
Measuring range
Temperature ranges+0…+50 °C
Accuracy
Accuracy class< 0.5 °C
Process conditions
Process connectionAdjustable mounting flange
Process temperature+0…+50 °C
Electrical characteristics
Output signalDC 0 ... 10 V · 4 ... 20 mA · Modbus · Modbus®
Power supplyAC 24 V or DC 24 V ±10 %
Electrical connectionCable gland M16, Screw terminals, Max. 1.5 mm²
Materials
Probe materialABS, Polycarbonate
Operating environment
Ambient temperature−20…+70 °C
IP ratingIP54
Weight0.15 kg
Certifications and approvals
Certifications
CERoHS
Additional details
Sensor typeNTC
ThermowellNo
Datasheet languagesEN
Tables from datasheet
Ventilation duct sensor for CO 2 and temperature, model A2G-85
Version■ Version without LC display ■ Version with LC display
Measuring range
CO 2400 …2,000 ppm
Temperature0 …50°C[32 …122 °F]
Accuracy
CO 2±40 ppm +2 %of reading value
Temperature< 0.5 °C [0.9 °F]
Power supply U BAC 24V or DC 24V ±10%
Power consumptionMax.230mA
Electrical connectionCable gland M16 Screw terminals Max.1,5mm 2
Output signal■ DC 0 ... 10 V, load min. 1 kΩ ■ 4 …20mA, load R min. 20 Ω, max.500Ω ■ Modbus ®
Material
CasePlastic (ABS)
CoverPolycarbonate
Sensor sleevePlastic (ABS)
Mounting flangeLLPDP
Permissible temperatures
Operating0 …50°C[32 …122 °F] (at sensor)
Ambient-20 …+70 °C [-4 …+158 °F]
Relative humidity0 ... 95 %, non-condensing
Ingress protection per IEC/EN 60529IP54
Weight150 g
MountingBy means of adjustable mounting flange
Modbus ® communication
ProtocolModbus ® via serial interface
Transfer modeRTU
InterfaceRS-485
Byte format(11 bits) in RTU mode Coding system: 8 bits binary Bits per byte: - 1 start bit - 8 data bits, least significant bit is sent first - 1 bit for parity - 1 stop bit
Baud rate9,600, 19,200, 38,400 - adjustable in the configuration
Modbus ® addresses1 …247 addresses - adjustable in the configuration
C Dimensions in mm[in]
ABCDEFØ GHI
119 [4.69]45 [1.77]5.2 [0.2]70 [2.76]15 [0.59]186 [7.32]12 [0.47]95.5 [3.76]88.5 [3.48]
DescriptionCountry
EU declaration of conformityEuropean Community
EMV directive
RoHS directive
WEEE directive