Electronic ventilation duct temperature sensor
Description
The model A2G-60 electronic ventilation duct temperature sensor is used for temperature measurement in heating, ventilation, air-conditioning and refrigeration systems and is primarily used in air ducts.
Mounting is performed using a mounting flange. In conjunction with an additional thermowell, the A2G-60 can also be used for temperature measurement in liquid media.
Electronic ventilation duct temperature sensor, model A2G-60
By selecting the appropriate measuring elements, the ventilation duct temperature sensor is compatible with all commonly used control systems. The A2G-60 is available with a Pt1000 or Ni1000 sensor, but also with an integrated transmitter (0 ... 10 V or 4 ... 20 mA).
Special features
- Simple mounting, including mounting flange
- Compact and robust design
- Direct mounting on circular ventilation pipes or rectangular ventilation ducts
- Pt1000 or Ni1000 sensor
- Also available with electrical output signal (0 … 10 V or 4 … 20 mA)
| Model | A2G-60 |
| Product family | A2G |
| Subcategory | Ventilation duct sensor |
| Temperature ranges | −50…+160 °C · −50…+50 °C · −20…+80 °C · −15…+35 °C · +0…+50 °C · +0…+100 °C · +0…+250 °C · +0…+160 °C · −10…+120 °C · +10…+120 °C |
| Accuracy class | ±0.5 K |
| Process temperature | −80…+260 °C |
| Output signal | 4-20 mA · 0-10 V · 0-5 V |
| Power supply | 15 ... 24 V = (±10 %) or 24 V ~ (±10 %) SELV |
| Electrical connection | Removable plug-in terminal, max. 2.5 mm² / Flextherm M20 |
| Probe material | Stainless steel 1.4571 |
| Thermowell material | brass (MS63), stainless steel (V4A) |
| Ambient temperature | −35…+90 °C |
| IP rating | IP65 |
| Weight | 0.15 kg |
| Certifications | CERoHSWEEEEMC |
| Sensor type | Pt1000, Ni1000 |
| Probe length | 450 mm |
| Probe diameter | 6 mm |
| Thermowell | Yes |
| Thermowell form | fabricated |
| Datasheet languages | EN, DE |
| Electronic ventilation duct temperature | sensor, model A2G-60 | |
|---|---|---|
| Version | Temperature probe (passive) | |
| Transmitter (active) | Voltage output | |
| Current output | ||
| Measuring range | ||
| Temperature probe | -50 ...+160 °C [-58 ...+320 °F] | |
| Transmitter | 0 …160 °C [32 ... 320 °F] | |
| Other measuring ranges adjustable at the transmitter: -50 ...+50 °C [-58 ...+122 °F] -20 ...+80 °C [-4 ...+176 °F] -15 ...+35 °C [5 ... 95 °F] -10 ...+120 °C [14 ... 248 °F] 0 ... 50 °C [32 ... 122 °F] 0 ... 100 °C [32 ... 212 °F] 0 ... 250 °C [32 ... 482 °F] | ||
| Accuracy | ||
| Temperature probe | Pt1000 | ±0.3 K |
| Ni1000 | ±0.4 K | |
| Transmitter | ±0.5 K | |
| Output / Sensor | ||
| Temperature probe | ■ Pt1000 ■ Ni1000 Available in 2-, 3- or 4-wire connection | |
| Transmitter, voltage output | 0 ...10V or 0 ... 5 V, min. load 5 kΩ | |
| Transmitter, current output | 4 ... 20 mA, max. load 500 Ω(2-wire) | |
| Power consumption | ||
| Transmitter, voltage output | 0.4W(24V =), 0.8VA (24V ~) | |
| Transmitter, current output | 0.5W(24V =) | |
| Electrical connection, cable entry | Removable plug-in terminal, max. 2.5 mm² / Flextherm M20, for cables with Ø4.5 …9mm[0.18 ... 0.35 in], removable | |
| Insertion length | ■ 50 …300 mm[1.97 ...11.81 in] (in 50 mmincrements / in 1.97 in increments) ■ 450 mm[17.72 in] | |
| Material | ||
| Probe sleeve | Stainless steel 1.4571 | |
| Case | Polycarbonate, pure white | |
| Mounting clip | Polycarbonate, pure white | |
| Relative humidity | 0 …85%,not permanently condensing | |
| Permissible temperatures | ||
| Head | Temperature probe Transmitter | -35 …+90 °C [-31 ...+194 °F] -35 …+70 °C [-31 ...+158 °F] |
| Probe sleeve | ■ -50 …+160 °C [-58 ...+320 °F] ■ -80 …+260 °C [-112 ...+500 °F] | |
| Ingress protection per IEC/EN 60529 | IP65 | |
| Supply voltage U B | ||
| Transmitter, voltage output | 15 …24V=(±10 %) or 24V ~ (±10 %) SELV | |
| Transmitter, current output | 15 …24V=(±10 %) SELV | |
| Mounting | Mounting clip (included in delivery) → Other mounting options see 'Accessories' | |
| Weight | 150 g |
| Description | Country |
|---|---|
| EU declaration of conformity | European Union |
| EMCdirective | |
| RoHS conformity | |
| WEEE directive |
| Description | Order number |
|---|---|
| Mounting base | 40440263 |
| Mounting flange | 40440225 |
| Syringe with thermal compound | 40440262 |
| Thermowell brass (MS63) | |
| Insertion length of the sensor L = 50 mm[1.97 in] | 40440161 |
| Insertion length of the sensor L = 100 mm[3.94 in] | 40440164 |
| Insertion length of the sensor L = 150 mm[5.91 in] | 40440165 |
| Insertion length of the sensor L = 200 mm[7.87 in] | 40440166 |
| Insertion length of the sensor L = 250 mm[9.84 in] | 40440167 |
| Insertion length of the sensor L = 300 mm[11.81 in] | 40440168 |
| Insertion length of the sensor L = 450 mm[17.72 in] | 40440169 |
| Thermowell stainless steel (V4A) | |
| Insertion length of the sensor L = 50 mm[1.97 in] | 40440171 |
| Insertion length of the sensor L = 100 mm[3.94 in] | 40440172 |
| Insertion length of the sensor L = 150 mm[5.91 in] | 40440173 |
| Insertion length of the sensor L = 200 mm[7.87 in] | 40440174 |
| Insertion length of the sensor L = 250 mm[9.84 in] | 40440175 |
| Insertion length of the sensor L = 300 mm[11.81 in] | 40440176 |
| Insertion length of the sensor L = 450 mm[17.72 in] | 40440177 |