YORK YLAAMP / HPCO FAULT

On the display

The panel shows MP / HPCO FAULT. This is the only form of the message the YLAA manuals print — there is no second spelling or variant to watch for.

What it means

The message reports that a protective device in the compressor circuit has opened or failed. The manual's fault table lists five conditions behind it: the compressor internal motor protector (MP) is open, an external overload has tripped, the HPCO switch is open, the HPCO switch is defective, or the CR relay is defective. The message itself does not tell you which of the five it is — the checks below separate them.

Why it appears

  • The compressor internal motor protector (MP) is open.
  • An external overload has tripped.
  • The HPCO switch is open.
  • The HPCO switch is defective.
  • The CR relay is defective.

What to check

  1. If the compressor internal motor protector (MP) is the open device, verify that the refrigerant charge is not low.
  2. For the same MP condition, verify the superheat setting is 10°F to 15°F (5.6°C to 8.3°C).
  3. Also for the MP condition, verify that the compressor rotation is correct.
  4. Complete the MP checks by verifying that the compressor is not overloaded.
  5. If an external overload has tripped, determine the cause and reset it.
  6. If the HPCO switch is open, see the separate “High Press. Disch.” fault entry.
  7. Replace a defective HPCO switch.
  8. Replace a defective CR relay.

Setpoints and thresholds

  • Superheat setting: 10°F to 15°F (5.6°C to 8.3°C) — verify this setting as part of the checks for an open compressor internal motor protector (MP).

Reset and restart

The manual gives one reset instruction for this fault, and it applies to a tripped external overload: Determine cause and reset. The other recoveries it names are component replacement — a new HPCO switch or a new relay — and, for an open HPCO switch, the separate “High Press. Disch.” fault entry.

Questions engineers ask

What does MP / HPCO FAULT mean on a YORK YLAA chiller?

It reports that a protective device in the compressor circuit has opened or failed: the compressor internal motor protector (MP), an external overload, or the HPCO switch — or that the HPCO switch or CR relay is defective.

What causes MP / HPCO FAULT on a YORK YLAA?

The manual lists five causes: compressor internal motor protector (MP) open, external overload tripped, HPCO switch open, defective HPCO switch, and defective CR relay.

How do I clear MP / HPCO FAULT on a YORK YLAA?

For a tripped external overload, determine the cause and reset it. Replace a defective HPCO switch or CR relay, and follow the separate “High Press. Disch.” fault entry when the HPCO switch is open.

What superheat setting should I verify for this fault?

10°F to 15°F (5.6°C to 8.3°C). The manual calls for verifying this setting when the compressor internal motor protector (MP) is open.