Trouble condition · YORK YLAA · Air-cooled scroll chiller

YORK YLAACOMPRESSOR(S) WON'T START

On the display

The panel reads COMPRESSOR(S) WON'T START. This is the exact wording the YLAA troubleshooting tables print for this condition; the manuals list no other variant of the message.

What it means

The message states that the unit's compressors are not starting. The manual treats this first as a question of demand rather than a fault: when the cooling demand is not great enough, the compressors simply stay off, and the action the manual gives for that case is No problem, pointing to the Installation Manual for an understanding of compressor operation and capacity control. Only when a demand for cooling exists does the message point to hardware: a defective water temperature sensor, a contactor/overload failure, or a compressor failure.

Why it appears

  • Demand not great enough — the compressors stay off because the call for cooling is too small; the manual marks this case as no problem.
  • Defective water temperature sensor.
  • Contactor/Overload failure.
  • Compressor failure.

What to check

  1. Decide first whether demand is simply not great enough. If it is, there is no problem; the manual directs you to the Installation Manual to understand compressor operation and capacity control.
  2. Compare the temperature shown on the display with a thermometer. The two readings should be within +/- 2 degrees of each other.
  3. Refer to the RWT/LWT temperature/voltage table in the Service section (Table 26) for the water temperature sensor's expected values.
  4. If the cause is a contactor/overload failure, replace the defective part.
  5. If the cause is compressor failure, diagnose the cause of the failure and replace the compressor.

Setpoints and thresholds

  • Display-to-thermometer agreement for the water temperature sensor: within +/- 2 degrees.
  • Reference for the sensor check: the RWT/LWT temperature/voltage table (Table 26) in the Service section.

Questions engineers ask

Why won't the compressors start on my YORK YLAA?

The manual lists four causes in order: demand not great enough, a defective water temperature sensor, a contactor/overload failure, or a compressor failure. The first is not a fault — the compressors stay off until the demand for cooling is great enough.

Is COMPRESSOR(S) WON'T START a fault on the YLAA?

Not necessarily. The manual's first listed cause is demand not great enough, and its action for that case is that there is no problem; the remaining causes are the water temperature sensor, the contactor/overload, and the compressor.

How do I check the water temperature sensor on a YLAA?

Compare the display reading with a thermometer — the two should agree within +/- 2 degrees. Then use the RWT/LWT temperature/voltage table (Table 26) in the Service section for the sensor's expected values.

What needs replacing when the YLAA shows COMPRESSOR(S) WON'T START?

For a contactor/overload failure, the manual says to replace the defective part. For a compressor failure, diagnose the cause of the failure and replace the compressor.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YLAA; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:

All YORK YLAA messages: fault codes · YORK YLAA documentation · YORK manuals