Safety shutdown · YORK YK · Water-cooled centrifugal chiller

YORK YKOil - High viscosity

On the display

The panel prints the message as Oil - High viscosity; one of this chiller's manuals lists it in capitals as OIL - HIGH VISCOSITY. Both spellings name the same event, which the manual classifies as an immediate safety fault.

What it means

This is an immediate safety fault of the YK: the oil kinematic viscosity has been greater than the programmed high viscosity trip limit for long enough for the control to trip. The message is armed only when the Oil Quality Protection AND Oil Cooling control features are both enabled — if either feature is disabled, this fault does not apply. It can be cleared only after the chiller has stopped.

Why it appears

  • The fault only applies when the oil quality protection and oil cooling control are both enabled.
  • The chiller has been running for 30 min and, at the same time, the oil kinematic viscosity has been greater than the JCI Service programmable High Viscosity Trip Threshold (default 30.0 cSt) for 5 min.

Setpoints and thresholds

  • High Viscosity Trip Threshold — programmable through JCI Service; default is 30.0 cSt.
  • Running time before the trip condition applies: 30 min of chiller running.
  • Time the viscosity must stay above the threshold to trip: 5 min.
  • Feature gate: Oil Quality Protection AND Oil Cooling control must both be enabled.

Reset and restart

The fault clears only after the chiller has stopped. Once the machine is stopped, press the Clear button next to the listed event on the Systems Details Screen, or select the Clear Fault key — the model's manuals describe the same action with different key names. One of them states: The fault can be cleared after the chiller has stopped and the Clear Fault key is selected.

Questions engineers ask

What does OIL - HIGH VISCOSITY mean on a YORK YK chiller?

It is an immediate safety fault: the chiller has been running for 30 min and the oil kinematic viscosity has been greater than the JCI Service programmable High Viscosity Trip Threshold (default 30.0 cSt) for 5 min. It applies only when Oil Quality Protection AND Oil Cooling control are enabled.

How do I clear the Oil - High viscosity fault on a YORK YK?

Only after the chiller has stopped. Then press the Clear button next to the listed event on the Systems Details Screen, or select the Clear Fault key, depending on which manual describes your control.

What is the high viscosity trip threshold on a YORK YK?

It is programmable through JCI Service and defaults to 30.0 cSt. The fault is set when the oil kinematic viscosity stays above it for 5 min once the chiller has run for 30 min.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: