Safety shutdown · YORK YK · Water-cooled centrifugal chiller

YORK YKOil - High supply temperature

On the display

The panel shows the message as Oil - High supply temperature; some manuals print it in capitals as OIL - HIGH SUPPLY TEMPERATURE. It is grouped with the safety fault messages of the control center, not with the ordinary display warnings, so it is a stop fault for the machine.

What it means

This is a safety fault of the oil cooling control function, and it is armed only when oil cooling control is enabled on the unit. When it trips, the chiller is stopped on a safety fault: it cannot be started again until the oil supply temperature has fallen back below the trip threshold and the fault has been cleared by hand.

Why it appears

  • Oil cooling control is enabled. The manuals state that this safety message appears when oil cooling control is enabled on the unit.
  • The oil supply temperature ran high. After the minimum running time — one manual states 5 minutes of chiller running, the other 30 minutes — the oil supply temperature, as sensed by the oil supply temperature thermistor, rose 15°F (8.3°C) above the service-programmable oil supply temperature setpoint.
  • The excess lasted long enough. The temperature stayed above that margin for 1 continuous minute, and the safety fault was issued.

Setpoints and thresholds

  • Oil supply temperature setpoint: service-programmable, default 120°F (48.9°C).
  • Trip threshold: oil supply temperature setpoint + 15°F (8.3°C) — the same margin is printed in the second manual as setpoint + 15.0°F.
  • Trip timing: the excess temperature must persist for 1 min, counted from the minimum running time (5 min in one manual, 30 minutes in the other).
  • Clear threshold: the oil supply temperature must be lower than the oil supply temperature setpoint + 15.0°F again before the fault can be released.
  • Mode requirement: oil cooling control must be enabled for this fault to be active.

Reset and restart

This fault needs a manual clear — it does not reset on its own. Let the oil supply temperature fall back below the trip threshold (setpoint + 15°F / 15.0°F); the chiller stays locked out until then. The manual's wording for the restart: The chiller can be started after the temperature decreases below the trip threshold and the Clear button is pressed next to the listed event on the Systems Details Screen. The second manual describes the same manual clear: once the oil supply temperature is lower than the oil supply temperature setpoint + 15.0°F, the fault is released when the Clear Fault key is pressed. After clearing, the chiller can be started again.

Questions engineers ask

What does the YORK YK message 'Oil - High supply temperature' mean?

It is a safety fault of the oil cooling control function. It trips when the oil supply temperature, sensed by the oil supply temperature thermistor, stays 15°F (8.3°C) above the oil supply temperature setpoint for 1 continuous minute after the minimum running time, and the chiller stops.

How do I clear the 'Oil - High supply temperature' fault on a YORK YK?

Wait until the oil supply temperature drops back below the trip threshold (setpoint + 15°F), then press the Clear button next to the listed event on the Systems Details Screen; the other manual calls this key Clear Fault. The chiller can be started after that.

What is the oil supply temperature setpoint on a YORK YK?

It is service-programmable and defaults to 120°F (48.9°C). The safety fault trips when the measured supply temperature exceeds this setpoint by 15°F (8.3°C).

How long must the chiller run before this fault can appear?

The manuals give different minimum running times: one states the fault occurs after 5 minutes of running, the other after 30 minutes. In both cases the excess temperature must then persist for 1 continuous minute.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: