Fault · YORK YK · Water-cooled centrifugal chiller

YORK YKLeaving Chilled Liquid - Flow Switch Open

On the display

The panel reads Leaving Chilled Liquid - Flow Switch Open; some manual tables and displays print it as Leaving chilled liquid - Flow switch open. It is one of the cycling faults of this chiller and is also recorded on the History Screen.

What it means

This is a chilled water flow switch cycling shutdown: flow through the evaporator was not proven while the machine was running or during its pre-lube period. The chiller stops, but the shutdown is not a lockout. While it is active, the evaporator pump relay contacts — also called the Chilled Water Pump contacts — (TB2-44/45) remain closed, so the pump keeps running until the chiller is given a stop command or trips on another fault.

Why it appears

  • The chilled liquid flow switch has remained open for 5 continuous seconds while the chiller was running (with software version C.OPT.01.15A.xxx and earlier, the running threshold is 2 continuous seconds).
  • The flow switch failed to close during the last 5 seconds of the system pre-lube period.

Setpoints and thresholds

  • Running open-time threshold: 5 continuous seconds in current software; 2 continuous seconds with software version C.OPT.01.15A.xxx and earlier.
  • Pre-lube requirement: the switch must close during the last 5 seconds of the system pre-lube period.
  • This extended flow switch delay is implemented for both ANALOG and DIGITAL flow sensor selections.

Reset and restart

The manuals describe no manual reset for this message. They state the recovery directly: The chiller will automatically restart when the flow switch closes. Until that happens, the pump contacts (TB2-44/45) stay closed while the shutdown is active, and they only open when a stop command is given or another fault occurs.

Questions engineers ask

What does Leaving Chilled Liquid - Flow Switch Open mean on a YORK YK?

It is a cycling shutdown raised because the chilled liquid flow switch stayed open for 5 continuous seconds while the chiller was running, or failed to close during the last 5 seconds of the pre-lube period.

How do I clear the YORK YK Leaving Chilled Liquid - Flow Switch Open fault?

No manual reset is described. The chiller automatically restarts when the flow switch closes.

Does the chilled water pump keep running during this shutdown?

Yes. The pump contacts (TB2-44/45) remain closed while the chiller is shut down on this cycling shutdown, until the chiller is given a stop command or has another fault.

What is the flow switch time delay on the YORK YK?

The switch must remain open for 5 continuous seconds to trip, or 2 continuous seconds with software version C.OPT.01.15A.xxx and earlier; it must also close during the pre-lube period.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: