YK Centrifugal Chiller - Software Enhancements (V23), Control Panel

Document typeService Information Letter
Document numberSI0252
EquipmentYK Centrifugal Chiller
BrandYORK
File size0.4 MB

Fault codes in this document

VGD Screens

Code / displayMeaningCauseActionPage
Surge Avoidance Surge DetectedLED on the VGD screen (replaces the former "Surge Detected" LED). Illuminates when full speed surges are detected.Full speed surges detected.1
ACC Surge DetectedLED added to the VGD screen; present when the Motor Drive Type setpoint is set to VSD and the Motor Communications Protocol setpoint is set to MODBUS. Illuminates when running at less than full speed.Running at less than full speed.1

OIL SYSTEM

Code / displayMeaningCauseActionPage
Oil – Low Temperature DifferentialStart inhibit. In this software version the condition is checked only when the chiller is stopped; previously it was checked while the chiller was stopped and during the first 10 seconds of Pre-lube. It is no longer checked during Pre-lube.2
Warning - Standby Lube – Low Oil PressureWarning. In addition to the existing required conditions, it is now set when either the Pump Oil Pressure or the Sump Oil Pressure is less than 2 PSIG.Pump Oil Pressure or Sump Oil Pressure less than 2 PSIG (with the existing required conditions also met).Manual reset warning — cleared using the WARNING RESET key; the acknowledgement is entered in the Security Log.2

FAULTS

Code / displayMeaningCauseActionPage
VSD – High Phase (X) Instantaneous FaultVSD Cycling fault.If this Cycling fault occurs 3 times in 10 minutes, the third shutdown becomes a Safety fault.2

Warnings

Code / displayMeaningCauseActionPage
Warning – Harmonic Filter – Not RunningNew warning added in this software version.Set when ALL of the following are true for 20 continuous seconds: chiller is running; filter is enabled; filter present status is true; run time greater than 20 seconds; filter operating mode is "stopped".The warning is released when the chiller is stopped, but will be displayed until manually cleared using the WARNING RESET key when logged in at Operator (or higher) Access Level.2

PUMP CONTROL

Code / displayMeaningCauseActionPage
Leaving Chilled Liquid – Flow Switch OpenCycling shutdown. With this software version, the Chilled Water Pump contacts (TB2-44/45) remain closed while the chiller is shutdown on this cycling shutdown.While the chiller is shutdown on this cycling shutdown, the Chilled Water Pump contacts (TB2-44/45) remain closed until the chiller is given a stop command or has another fault.3
Condenser – Flow Switch OpenCycling shutdown. With this software version, the Condenser Pump contacts (TB2-150/151) remain closed while the chiller is shutdown on this cycling shutdown.While the chiller is shutdown on this cycling shutdown, the Condenser Pump contacts (TB2-150/151) remain closed until the chiller is given a stop command or has another fault.3

SECURITY LOG – MANUAL RESET WARNINGS

Code / displayMeaningCauseActionPage
Condenser or Evaporator Transducer WarningManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Reset using the WARNING RESET key.4
Standby Lube Low Oil Pressure WarningManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Pump Oil Pressure or Sump Oil Pressure less than 2 PSIG (in addition to the existing required conditions).Reset using the WARNING RESET key.4
Excess Surge Detected WarningManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Reset using the WARNING RESET key.4
Condenser or VGD Sensor Failure warningManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Reset using the WARNING RESET key.4
Conditions Override VGD Warning ResetManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Reset using the WARNING RESET key.4
Purge High Pressure WarningManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Reset using the WARNING RESET key.4
Purge Float Switch Error WarningManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Reset using the WARNING RESET key.4
Excess Purge WarningManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Reset using the WARNING RESET key.4
Purge canister #X Full WarningManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Reset using the WARNING RESET key.4
Setpoint Override WarningManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Reset using the WARNING RESET key.4
Filter Not Running WarningManual reset warning. When acknowledged (by pressing the WARNING RESET button), the actual warning message being reset is now entered in the Security Log; previous versions logged a generic "Warning Reset" message.Set when all of the following are true for 20 continuous seconds: chiller is running; filter is enabled; filter present status is true; run time greater than 20 seconds; filter operating mode is "stopped".Released when the chiller is stopped; displayed until manually cleared using the WARNING RESET key when logged in at Operator (or higher) Access Level.4