Fault · YORK YK · Water-cooled centrifugal chiller

YORK YKSurge Avoidance Surge Detected

On the display

The panel shows the label Surge Avoidance Surge Detected. It is an LED on the VGD screen of the control center. It illuminates only momentarily — it lights for the moment a surge is detected and then goes out again. On this model it replaces the LED formerly labeled Surge Detected, and on units running older software versions the manuals list the same indication under that earlier name, so an older panel may show Surge Detected for the same condition.

What it means

The LED illuminates momentarily when a surge is detected by the Surge Protection feature. Its scope depends on the drive fitted: on a unit equipped with a VSD or MV VSD, it reports only the surges detected while the drive is running at maximum frequency. Surges that occur while the drive runs below maximum frequency are not shown by this LED; the manual records them in the separate ACC Surge Count, which increments when a surge is detected while the drive is running at less than maximum frequency. The LED state is available as data slot 8319 (Surge Avoidance Surge Detected), with the associated counter in slot 8238 (Surge Avoidance Surge Count). The fault table entry for this condition lists no action.

Why it appears

  • Full speed surges detected — the fault table lists this as the cause: the compressor surged while running at full speed, which on VSD or MV VSD units means at maximum drive frequency.

Setpoints and thresholds

  • Surge Margin Adjust — listed by the manufacturer with this LED on the surge avoidance screens; this value determines how close the frequency reduction will be allowed to get to the surge line.
  • Surge Map Count — displays the total number of data points in the surge map.
  • Surge Avoidance Surge Count — the associated surge counter, held in slot 8238; the LED signal itself is slot 8319.

Questions engineers ask

What does the Surge Avoidance Surge Detected LED mean on a YORK YK?

It illuminates momentarily when a surge is detected by the Surge Protection feature. On units with a VSD or MV VSD it only reports surges detected while the drive is running at maximum frequency.

Why does my YK show Surge Avoidance Surge Detected?

The manual's fault table gives one cause: full speed surges detected, meaning the machine surged while running at full speed. Each detected surge lights the LED only momentarily.

Is Surge Avoidance Surge Detected the same as the old Surge Detected LED?

It replaces the former Surge Detected LED on the VGD screen. On units with older software versions the same indication is displayed under the name Surge Detected.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: