On the display
The panel prints the message as Evaporator - Low pressure - Smart freeze. The same protection also appears as Evaporator - Low pressure - Smart Freeze, with a capital F. The two spellings mark two stages of one trip: the lowercase spelling is the cycling fault in the cycling fault list, while the capitalized spelling is the safety fault in the safety fault messages list. On controls with software YOPT.01.03A.3085 and earlier, the lowercase-named message is itself listed as a safety fault.
What it means
For Y.OPT.01.04.3085 and later, the message means that the evaporator pressure has decreased to the capacity control low pressure override with the Warning - Evaporator - Low press limit active, and capacity control has not been able to increase the evaporator pressure within 2 minutes. As a cycling fault it shuts the chiller down if it was running and then lets it restart by itself. When this cycling fault has happened three times within 90 min, the control sets the safety fault Evaporator - Low pressure - Smart Freeze, and the chiller stays off until that fault is cleared.
On controls with software YOPT.01.03A.3085 and earlier, Evaporator - Low pressure - Smart freeze is a safety fault with a different trigger: Smart Freeze protection is enabled and has shut down the chiller because the evaporator refrigerant temperature has been below the Smart Freeze threshold for greater than the allowable number of seconds before freezing. The number of seconds allowed is based on how far the evaporator refrigerant temperature is below the freeze threshold.
Why it appears
- Evaporator pressure fell to the capacity control low pressure override while the Warning - Evaporator - Low press limit was active, and capacity control could not raise the evaporator pressure within 2 min (cycling fault, Y.OPT.01.04.3085 and later).
- Three occurrences of the Smart freeze cycling fault within 90 min set the safety fault Evaporator - Low pressure - Smart Freeze.
- Evaporator refrigerant temperature below the Smart Freeze threshold for greater than the allowable number of seconds before freezing (safety fault, YOPT.01.03A.3085 and earlier).
Setpoints and thresholds
- 2 min: the time capacity control is given to increase the evaporator pressure out of the low pressure override before the cycling fault is set.
- Three times within 90 min: the count of cycling faults that sets the safety fault.
- Freeze threshold, software YOPT.01.03A.3085 and earlier: 32.8°F (0.4°C) when the evaporator refrigerant temperature sensor RT7 is enabled; 34.0°F (1.1°C), the evaporator saturation temperature derived from the evaporator pressure transducer, when RT7 is not enabled.
Reset and restart
The cycling fault needs no manual action: if the chiller was running, it automatically shuts down and then restarts. The safety fault Evaporator - Low pressure - Smart Freeze is cleared by hand once the pressure condition has gone. You can restart the chiller after the evaporator pressure has increased above the override threshold and the Clear button is pressed next to the listed event on the Systems Details Screen.
On the other control center the same step is described as pressing the CLEAR FAULT key on the display. No separate clear procedure is printed for the earlier-software safety fault of the same name.
Questions engineers ask
What does Evaporator - Low pressure - Smart freeze mean on a YORK YK?
The evaporator pressure dropped to the capacity control low pressure override with the Warning - Evaporator - Low press limit active, and capacity control could not raise the pressure within 2 min. If the chiller was running, it shuts down and then restarts automatically.
How do I clear the Smart Freeze safety fault on a YORK YK?
After the evaporator pressure has increased above the override threshold, press the Clear button next to the listed event on the Systems Details Screen; the other control center manual words this as pressing the CLEAR FAULT key on the display.
Why does my YORK YK set the Evaporator - Low pressure - Smart Freeze safety fault?
The safety fault is set when the Smart freeze cycling fault has happened three times within 90 min, so the low evaporator pressure condition keeps returning.
What is the Smart Freeze freeze threshold on a YORK YK?
On controls with software YOPT.01.03A.3085 and earlier the freeze threshold is 32.8°F (0.4°C) with sensor RT7 enabled, or 34.0°F (1.1°C) derived from the evaporator pressure transducer when RT7 is not enabled.
Messages next to this one
The same message on other models
Source
Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: