Fault · YORK YK · Water-cooled centrifugal chiller

YORK YKLCSSS - Phase loss

On the display

The control center shows LCSSS - Phase loss; some manuals print it in capitals as LCSSS - PHASE LOSS. It belongs to the liquid cooled solid state starter (LCSSS) message group listed for this chiller on the OptiView™ control center.

What it means

The LCSSS logic/trigger board has detected that the line-to-line RMS voltage in any phase has decreased to less than or equal to 30% of the lowest value of the programmed voltage range — in other words, any one of the three phases of input line voltage has dropped below the threshold value. The manual treats this message as a cycling shutdown. If the programmed voltage range is disabled, a value of 60 VAC is used as the threshold; for a 440-480 VAC range the manual gives 132 VAC as the example.

Why it appears

  • A supply disturbance — the manual notes that many times this is a normal fault related to a storm or lightning.
  • One of the three phases of input voltage absent; the manual points out that an input fuse may be open.
  • An improper voltage range selected on the OptiView™ control center.

Setpoints and thresholds

  • Shutdown threshold: line-to-line RMS voltage in any phase at or below 30% of the lowest value of the programmed voltage range.
  • If the programmed voltage range is disabled, the threshold is 60 VAC.
  • Manual example: 132 VAC for the 440-480 VAC range.

Reset and restart

This shutdown clears itself — the manual describes no separate reset step. The chiller automatically restarts when the line voltage is greater than the shutdown threshold; as a cycling shutdown it is an automatic restart after coastdown if the shutdown is no longer active and the compressor switch is still in the run position.

Questions engineers ask

What does LCSSS - Phase loss mean on a YORK YK chiller?

The liquid cooled solid state starter logic/trigger board has detected that the line-to-line RMS voltage in any phase has fallen to 30% or less of the lowest value of the programmed voltage range. If the voltage range is disabled, the threshold used is 60 VAC.

What causes LCSSS - Phase loss?

The manual lists a storm or lightning event, one of the three input phases being absent (an input fuse may be open), or an improper voltage range selected on the OptiView™ control center.

Will a YORK YK restart by itself after LCSSS - PHASE LOSS?

Yes. It is a cycling shutdown: the chiller restarts automatically after coastdown when the line voltage is above the shutdown threshold, provided the shutdown is no longer active and the compressor switch is still in the run position.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: