Fault · YORK YK · Water-cooled centrifugal chiller

YORK YKLCSSS - Phase locked loop

On the display

The panel shows LCSSS - Phase locked loop. The manual also prints the same shutdown in capitals, LCSSS - PHASE LOCKED LOOP. It belongs to the Liquid cooled solid state starter messages of this chiller.

What it means

The phase locked loop circuit on the LCSSS logic/trigger board was unable to maintain lock with phase A of the power line — the error signal of the synchronization circuit became too large and synchronization with the 'A' phase voltage was lost. If synchronization is not maintained, the SCRs will misfire and damage the chiller, which is why the shutdown is raised while the condition is present.

Why it appears

  • Storms or other power problems make the frequency of the 'A' phase voltage change too rapidly; a power line anomaly can cause the sag or jitter that breaks the lock.
  • During generator operation, the JP1 jumper has not been cut on a Rev. C or earlier Logic/Trigger Board.
  • During generator operation, the generator responds slowly to load changes.

What to check

  1. Note whether a storm or other power problem coincided with the shutdown; such anomalies can sag or jitter the power line and break the lock with phase A.
  2. If the shutdown occurred during generator operation, ensure that the JP1 jumper has been cut (on Rev C. or earlier Logic/Trigger Boards).
  3. If the problem occurs during generator operation, add some standby load to the generator so that it responds more quickly to load changes.

Setpoints and thresholds

  • The phase locked loop tolerates a power line frequency jitter of up to 3 Hz/s; faster changes in the line frequency can break the lock with phase A.

Reset and restart

No manual reset is described for this shutdown. The chiller automatically restarts when lock has resumed. The manual adds that the restart is Automatic restart after coastdown if the shutdown is no longer active and the compressor switch is still in the run position.

Questions engineers ask

What does LCSSS - Phase locked loop mean on a YORK YK chiller?

The phase locked loop circuit on the LCSSS logic/trigger board lost lock with phase A of the power line — the error signal of the synchronization circuit became too large. If synchronization is not maintained, the SCRs will misfire and damage the chiller.

Does the chiller restart by itself after LCSSS - Phase locked loop?

Yes. The chiller automatically restarts when lock has resumed, with automatic restart after coastdown if the shutdown is no longer active and the compressor switch is still in the run position.

Why does LCSSS - Phase locked loop appear during generator operation?

Either the generator is responding slowly to load changes, or the JP1 jumper has not been cut on a Rev. C or earlier Logic/Trigger Board. Adding standby load to the generator helps it respond more quickly.

How much line frequency change can the phase locked loop tolerate?

A power line frequency jitter of up to 3 Hz/s can be tolerated. Storms or power problems can make the 'A' phase voltage frequency change too rapidly and break the lock.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: