Safety shutdown · YORK YK · Water-cooled centrifugal chiller

YORK YKLCSSS - 105% motor current overload

On the display

The control center shows LCSSS - 105% motor current overload; the other manual for this chiller prints the same message in capitals as LCSSS - 105% MOTOR CURRENT OVERLOAD. It belongs to the liquid cooled solid states starter safety fault messages and it is a safety shutdown, so the compressor is stopped rather than left running with the overload present. If the panel is showing a different message, the manual directs you back to the starter fault message list.

What it means

The highest of the three phase RMS currents has exceeded 100% FLA × 1.05 — put another way, the highest phase of the compressor motor current rose above 105% of the programmed 100% chiller FLA — and stayed above that level continuously for 40 seconds. Once the overload current is maintained for those 40 seconds, the starter trips this safety shutdown.

Why it appears

  • The programmed FLA is incorrect on the OptiView™ control center.
  • The output CT's are not reading current correctly.
  • The output current is unbalanced.
  • The pre-rotation vanes or the slide valve are not working properly.

What to check

  1. Verify that the FLA programmed into the OptiView™ control center is correct.
  2. Verify that the output CT's are reading current correctly.
  3. Ensure that the output current is balanced.
  4. Verify that the pre-rotation vanes or slide valve are working properly.

Setpoints and thresholds

  • Trip level: the highest phase of the compressor motor current must rise above 105% of the programmed 100% chiller FLA, which the manual also expresses as 100% FLA × 1.05.
  • Trip delay: the current has to stay above that level continuously for 40 seconds before the safety shutdown occurs.
  • The FLA reference is a programmed value on the control center, and an incorrect programmed FLA is one of the listed possible problems.

Reset and restart

This trip is a safety shutdown: the SCR gate outputs turn off, a coastdown starts — 150 seconds on this centrifugal chiller — and the K1 relay de-energizes. After the coastdown times out, place the Compressor Switch in Stop/Reset, then Start and release; the chiller will start if no faults are active. The other manual describes the recovery from the display side: The chiller can be started after the Clear button is pressed next to the listed event on the Systems Details screen.

Questions engineers ask

What does LCSSS - 105% motor current overload mean on a YORK YK chiller?

It means the highest of the three phase RMS currents has run above 105% of the programmed 100% chiller FLA (100% FLA × 1.05) continuously for 40 seconds, which trips a starter safety shutdown.

How do I clear LCSSS - 105% motor current overload and restart the chiller?

After the 150-second coastdown times out, press the Clear button next to the listed event on the Systems Details screen, or place the Compressor Switch in Stop/Reset, then Start and release. The chiller will start if no faults are active.

What causes the 105% motor current overload trip on a YK?

The manual lists four possible problems: an incorrect programmed FLA on the control center, output CT's not reading current correctly, unbalanced output current, or pre-rotation vanes or a slide valve not working properly.

How long can the motor current stay above 105% before the YK shuts down?

40 seconds. The trip only occurs when the highest phase current stays above the 105% level continuously for 40 seconds.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: