| Document type | Operation Guide |
|---|---|
| Document number | 160.95-O1 |
| Equipment | YK Centrifugal Chiller |
| Brand | YORK |
| Revised | 2026-01-21 |
| File size | 9.1 MB |
Fault codes in this document
Troubleshooting — Table 4: Operation analysis chart
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| 1. Issue: abnormally high discharge pressure | The temperature difference between the condensing temperature and water off condenser is higher than normal. | Air is in the condenser. | 34 | |
| 1. Issue: abnormally high discharge pressure | The temperature difference between the condensing temperature and water off condenser is higher than normal. | Condenser tubes dirty or scaled. | Clean condenser tubes. Check water conditioning. | 34 |
| 1. Issue: abnormally high discharge pressure | High discharge pressure. | High condenser water temperature. | Reduce condenser water inlet temperature. Check cooling tower and water circulation. | 34 |
| 1. Issue: abnormally high discharge pressure | The temperature difference between condenser water on and water off is higher than normal, with normal evaporator pressure. | Insufficient condensing water flow. | Increase the quantity of water through the condenser to proper value. | 34 |
| 2. Issue: abnormally low suction pressure | Insufficient charge of refrigerant. | Check for leaks and charge refrigerant into system. | 34 | |
| 2. Issue: abnormally low suction pressure | The temperature difference between the leaving chilled water and the refrigerant in the evaporator is greater than normal with high discharge temperature. | Variable orifice problem. | Remove obstruction. | 34 |
| 2. Issue: abnormally low suction pressure | The temperature difference between the leaving chilled water and the refrigerant in the evaporator is greater than normal with normal discharge temperature. | Evaporator tubes dirty or restricted. | Clean evaporator tubes. | 34 |
| 2. Issue: abnormally low suction pressure | The temperature of chilled water is too low with low motor amperes. | Insufficient load for system capacity. | Check the motor operation of the PRV and check the setting of the low water temperature cutout. | 34 |
| 3. Issue: high evaporator pressure | PRVs fail to open. | Check the PRV motor positioning circuit. | 34 | |
| 3. Issue: high evaporator pressure | High chilled water temperature. | System overload. | Ensure the vanes are wide open (without overloading the motor) until the load decreases. | 34 |
| 4. Issue: no oil pressure when system start button pushed | Low oil pressure is displayed on the control center; the compressor does not start. | Oil pump running in wrong direction. | Check rotation of oil pump (Electrical Connections). | 34 |
| 4. Issue: no oil pressure when system start button pushed | Low oil pressure is displayed on the control center; the compressor does not start. | Oil pump not running. | Troubleshoot electrical problem with oil pump VSD. | 34 |
| 5. Issue: unusually high oil pressure develops when oil pump runs | Unusually high oil pressure is displayed when the oil pressure display key is pressed when the oil pump is running. | High oil pressure. The transducer is defective. | Replace low or high oil pressure transducer. | 34 |
| 6. Issue: oil pump vibrates or is noisy | Oil pump vibrates or is extremely noisy with some oil pressure when pressing the Oil Pressure display key. Note: When the oil pump is run without an oil supply, it vibrates and becomes extremely noisy. | Oil not reaching pump suction inlet in sufficient quantity. | Check oil level. | 34 |
| 6. Issue: oil pump vibrates or is noisy | Oil pump vibrates or is extremely noisy with some oil pressure when pressing the Oil Pressure display key. | Worn or failed oil pump. | Repair or, if necessary, replace the oil pump. | 34 |
| 7. Issue: reduced oil pump capacity | Oil pump pumping capacity. | Excessive end clearance pump. Other worn pump parts. | Inspect and replace worn parts. | 34 |
| 7. Issue: reduced oil pump capacity | Oil pump pumping capacity. | The oil supply inlet is partially blocked. | Check the oil inlet for blockage. | 34 |
| 8. Issue: oil pressure gradually decreases as noted by observation of daily log sheets | When the oil pump VSD frequency increases to 55 + Hz to maintain target oil pressure. | Oil filter is dirty. | Change oil filter. | 34 |
| 9. Issue: oil pressure system ceases to return an oil/refrigerant sample | Oil refrigerant return not functioning. | Filter-drier in oil return system dirty. | Replace old filter-drier with new. | 34 |
| 9. Issue: oil pressure system ceases to return an oil/refrigerant sample | Oil refrigerant return not functioning. | Jet or orifice of oil return jet clogged. | Remove jet, inspect for dirt. Remove dirt using solvent and replace. | 34 |
| 10. Issue: oil pump fails to deliver oil pressure | No oil pressure registers when pressing the Oil Pressure display key when the oil pump runs. | Faulty oil pressure transducer. | Replace oil pressure transducer. | 35 |
| 10. Issue: oil pump fails to deliver oil pressure | No oil pressure registers when pressing the Oil Pressure display key when the oil pump runs. | Faulty wiring or connectors. | Replace oil pressure transducer. | 35 |
Safety shutdowns and warnings
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| Leaving Chilled Liquid – Low Temperature Control | Safety control that shuts down the chiller. | The load continues to decrease, after the PRVs are entirely closed. | 15 | |
| oil pressure safety cutout | Actuates and stops the system. | Refrigerant boiling out of the oil as the pressure is lowered on starting causes violent oil foaming; if this foam reaches the oil pump suction, the bearing oil pressure fluctuates with possible temporary loss of lubrication. | Refer to OptiView Control Center – Operation Manual (160.76-O2). | 27 |
| high oil temperature (HOT) | The unit is shutting down on high oil temperature. | Incorrect lubrication, brought about by restricted oil lines, passages, or dirty oil filters. | Change the oil filter element. Examine the oil filter element for the presence of aluminum particles; if aluminum particles continue to accumulate, contact Johnson Controls Service. | 40 |
| low oil pressure (OP) | The unit is shutting down on low oil pressure. | Incorrect lubrication, brought about by restricted oil lines, passages, or dirty oil filters. | Change the oil filter element. Examine the oil filter element for the presence of aluminum particles; if aluminum particles continue to accumulate, contact Johnson Controls Service. | 40 |
| warning message to re-lubricate | OptiView panels provide a warning message to re-lubricate beginning at a programmed number of operating hours (the default value is 1000 hours). At the programmed value plus 400 hours this feature shuts down the chiller if re-lubrication is not addressed. | Programmed number of operating hours reached. | Re-lubricate the motor bearings; if re-lubrication is not addressed, the chiller shuts down at the programmed value plus 400 hours. | 43 |
| bearing temperature warning — 149°F (65°C) | If the temperature exceeds 149°F (65°C), a warning is issued. | Either the bearings are in need of lubrication or that something is wrong. | Operation should be checked. | 47 |
| bearing RTD shutdown — 194°F (90°C) | Bearing RTDs are normally set to shut down the motors at 194°F (90°C), although when this temperature is reached, the bearings most likely have already been compromised. | Motors shut down by bearing RTDs at 194°F (90°C). | 44 | |
| quarterly maintenance warning item | Monthly items appear on OptiView as a quarterly maintenance warning item. | Monthly items are still required. | Perform the monthly maintenance procedures. | 20 |
Every row above cites the page of this document it came from, and each one is re-read against that page by an automatic check before publication.
Manufacturer document, published here as reference material for equipment we supply. The original lives at docs.johnsoncontrols.com. The rights holder may ask us to take it down — we will.
