SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

LA 716 силовой модуль

The LA 716 provides 16 channels for switching resistive loads. Up to 650 W can be used per output channel.

Дизайн

  • Connection of heat radiation devices over 8-pole front connector (not included in scope of supply →see documentation)
  • Mains infeed over 3-pole terminal (Lx/N/Ly) on the front
  • 16 channel fuses in accessible holders
  • Cooling is possible using an optional fan unit

Функции

Output power

  • 16 power channels, each 230 V (8 outputs per phase)
  • Up to 650 W switching capacity per output with 100% concurrence
  • Up to 10400 W switching capacity per module
  • Zero-crossing power triacs
  • Protection of triacs and opto-triacs by transil diodes against overvoltage

Forced ventilated

Depending on the switching capacity and ambient temperature, the power output may require forced ventilation. For this purpose, an optional fan unit is available as an accessory (see accessories). For further details, see the manual.

Temperature monitoring

For monitoring the heat-sink temperature, there is an NTC thermistor on the heat sink. In the event of overheating, this temperature dependent resistor outputs an alarm to the higher-level control system.

Fuses

For each channel of the LA 716, a 5 A fusible link for protection of the power triacs is accessible externally. A safety cover is provided for protection against finger touch.

Diagnostic capability

Diagnostic functions are available as standard for detecting the following faults:

  • Triac circuit-breaker, high-resistance or fused junction
  • Channel fuse on module defective
  • External fault such as fuse rupture, break in radiation device or wire

Технические данные

Supply voltage
for control section provided internally over the bus module
Power outputs
Number per power output 16
Galvanic isolation
- to control section through opto-triac and opto-coupler which are specified in acc. with VDE 0884
- between power outputs No
Load voltage
- Rated value 230 V AC
- Permissible range 187 ... 264 V (TN network)
- Frequency 50/60 Hz (47 ... 63 Hz)
Output voltage full-wave switched at zero crossover
Output current per channel
- Rated value 2.82 A
- Permissible range 0.1 ... 2.82 A
- Residual current ≤ 10 mA
Maximum switching power per channel without ventilation and with ventilation (rate of flow ≥ 2 m/s) 650 W at 230 V
Loads
- Load type Resistive load with a maximum of 15-times the cold current in the first half-wave
- Overload Five-times rated current for 20 ms
Protective measures
- Thermal monitoring Yes (through NTC thermistor)
- Short-circuit protection One 5 A/250 V F fuse per output
- Overvoltage protection Yes
Connecting cables
- Resistance max. 14 Ohm(to guarantee short-circuit protection)
- Length 100 m unshielded500 m shielded
Mechanical data
Dimensions W x H (mm) 237 x 233.4
Degree of protection to DIN 40050 IP00

Дополнительно

Description Type Manufacturer Manufacturer Type No. Siemens Type No.
Replacement fuse for power module F5AH250V Littelfuse 216005.MA000 200021116
230 V fan unit with 3 fans On request Rittal On request On request
8-pole, terminal strip with screw terminals SLT 5.08/8B SN OR Weidmüller 1611770000 On request

Please contact:

Siemens AG

A&D SE EWF EMS 3 schmidt.bernhard@siemens.com

A&D MC PM1 wolfgang.zapf@siemens.com