Safety shutdown · YORK YK · Water-cooled centrifugal chiller

YORK YKVSD - High phase A, B, or C inverter baseplate temperature

On the display

The display reads VSD - High phase A, B, or C inverter baseplate temperature. The manual places this message in the medium voltage variable speed drive safety fault messages group, so it is a safety shutdown of the drive, not an ordinary status notice. A single wording covers all three phases: the phase named in the message (A, B, or C) is the one whose inverter baseplate is involved.

What it means

The inverter baseplate (heatsink) of the stated phase has overheated and the drive has shut down to protect itself. For the medium voltage drive the manual gives the trip point directly: This shutdown occurs if the stated phase heatsink temperature exceeds 175°F (79.4°C). For VSD and LVSD model drives the same message is described as a shutdown that occurs when the baseplate temperature exceeds the trip temperature for that drive size. While the drive cools, the fans and water pump remain energized until all the inverter heatsink temperatures fall below the reset temperatures.

Why it appears

  • The stated phase heatsink temperature has exceeded 175°F (79.4°C).
  • On VSD and LVSD model drives: the inverter baseplate temperature has exceeded the trip temperature listed for that drive size in Table 235.

What to check

  1. Note which phase — A, B, or C — the message names: that stated phase's heatsink is the one that overheated.
  2. Expect cooling to continue on its own: the fans and water pump remain energized until all the inverter heatsink temperatures fall below the reset temperatures.
  3. Wait for the release point — on the medium voltage drive the fault is released when all the heatsink temperatures fall below 145°F (62.8°C).
  4. Start the chiller only after the fault condition has cleared, then clear the event as described under Reset.

Setpoints and thresholds

  • Trip point, medium voltage drive: stated phase heatsink above 175°F (79.4°C).
  • Fault release: all heatsink temperatures below 145°F (62.8°C).
  • Table 235 — inverter baseplate temperature thresholds (°F), trip temperature / fan and pump shutoff:
    • VSD 424/351/292/270Hp — 175 / 165
    • VSD 608/503/419/385Hp — 175 / 165
    • VSD 790/658/608/704Hp — 196 / 165
    • VSD 1055/914/917/948Hp — 196 / 165
    • LVSD 1100Hp — 232 / 222
    • LVSD 1300/1100Hp — 210 / 175

Reset and restart

The drive releases the fault itself once every heatsink has cooled below the release temperature — no key press clears it while the drive is still hot. After that, the manuals give two clearing paths depending on the control at the panel. For the medium voltage drive: The chiller can be started after the fault is cleared on the starter, and the Clear button is pressed next to the listed event on the Systems Details screen. For VSD and LVSD model drives: The chiller can be started after the fault condition clears, and the CLEAR FAULT key is pressed on the display.

Questions engineers ask

What causes the YORK YK VSD - High phase A, B, or C inverter baseplate temperature shutdown?

The stated phase heatsink temperature has exceeded 175°F (79.4°C). For VSD and LVSD model drives the trip is reached when the baseplate temperature passes the trip temperature listed for that drive size in Table 235.

How do I reset the fault and restart the chiller?

Wait until all heatsink temperatures fall below 145°F (62.8°C) so the drive releases the fault. Then clear it on the starter and press the Clear button next to the event on the Systems Details screen, or press the CLEAR FAULT key on the display.

Can I restart the chiller while the inverter is still hot?

No. The fans and water pump stay energized until all the inverter heatsink temperatures fall below the reset temperatures, and the chiller can be started only after the fault condition clears.

What are the trip temperatures for the different VSD and LVSD drive sizes?

Per Table 235: 175°F for the 424/351/292/270Hp and 608/503/419/385Hp VSD models, 196°F for the 790/658/608/704Hp and 1055/914/917/948Hp models, 232°F for the 1100Hp LVSD and 210°F for the 1300/1100Hp LVSD.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:

All YORK YK messages: fault codes · YORK YK documentation · YORK manuals