On the display
The control center shows VSD - High instantaneous current. The manuals print this wording only — there are no variants. The message comes from the medium voltage variable speed drive (MVVSD): it first appears in the drive's cycling fault list, and once it has occurred three times in 90 min it is also listed among the drive's safety faults.
What it means
The drive continuously monitors the instantaneous current it delivers to the motor. Two of the three output lines, T1 and T3, are measured by two DC current transformers within the drive; the third phase, T2, is derived. The three phases of instantaneous output current are continuously compared to an instantaneous limit of 233% of the drive's 100% FLA rating. If the peak instantaneous current trip limit is exceeded, the drive initiates a cycling shutdown. When the cycling fault has occurred three times in 90 min, the same message becomes a safety fault.
Why it appears
- The peak instantaneous current trip limit was exceeded: one or more phases of instantaneous output current rose above the instantaneous limit of 233% of the drive's 100% FLA rating.
- Repetition: the message escalates from a cycling fault to a safety fault once the cycling fault has occurred three times in 90 min.
Setpoints and thresholds
- Instantaneous trip limit: 233% of the drive's 100% FLA rating.
- Safety fault escalation: the cycling fault occurring three times in 90 min.
- MVVSD instantaneous current limits — peak instantaneous motor over current trip, 2,300 V 60 Hz models (Horsepower rating — trip): 500 — 250; 600 — 301; 700 — 366; 800 — 401; 900 — 471; 1,000 — 523; 1,250 — 653; 1,500 — 784; 1,750 — 915; 2,000 — 1,022; 2,250 — 1,153.
- Peak instantaneous motor over current trip, 3,300 V 50/60 Hz models: 500 — 182; 600 — 219; 700 — 257; 800 — 292; 900 — 329; 1,000 — 364; 1,250 — 455; 1,500 — 548; 1,750 — 639; 2,000 — 728; 2,250 — 805.
- Peak instantaneous motor over current trip, 4,160 V 60 Hz and 6,600 V 50/60 Hz models: 500 — 145; 600 — 173; 700 — 203; 800 — 231; 900 — 261; 1,000 — 289; 1,250 — 362; 1,500 — 434; 1,750 — 506; 2,000 — 579; 2,250 — 639.
Reset and restart
As a cycling fault, the message needs no manual reset: it clears automatically when the fault condition no longer exists, and if the chiller was running when the fault occurred, it automatically restarts. Once the fault has become a safety fault, the manual's instruction is: The chiller can be started after the fault is cleared on the starter, and the Clear button is pressed next to the listed event on the Systems Details screen.
The companion manual describes the same recovery as pressing the CLEAR FAULT key on the OptiView display.
Questions engineers ask
What does VSD - High instantaneous current mean on a YORK YK chiller?
The drive's peak instantaneous output current to the motor exceeded the trip limit, which is set at 233% of the drive's 100% FLA rating, so the drive initiated a cycling shutdown. Lines T1 and T3 are measured by two DC current transformers and the third phase, T2, is derived.
How do I reset VSD - High instantaneous current on a YORK YK?
As a cycling fault it clears by itself once the condition is gone, and a chiller that was running restarts automatically. As a safety fault, the chiller can be started after the fault is cleared on the starter and the Clear button is pressed next to the listed event on the Systems Details screen.
What is the trip limit for VSD - High instantaneous current?
The instantaneous limit is 233% of the drive's 100% FLA rating. The manual's MVVSD instantaneous current limits table lists the peak instantaneous motor over current trip per Horsepower rating and voltage — for example, 250 for a 500 Horsepower rating on 2,300 V 60 Hz models.
Why does VSD - High instantaneous current keep coming back on my YORK YK?
The message escalates with repetition: once the cycling fault has occurred three times in 90 min it becomes a safety fault, which no longer clears automatically and requires the fault to be cleared on the starter and the Clear button pressed next to the listed event on the Systems Details screen.
Messages next to this one
Source
Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:
All YORK YK messages: fault codes · YORK YK documentation · YORK manuals