Fault · YORK YK · Water-cooled centrifugal chiller

YORK YKVSD - High phase A, B, C instantaneous current

On the display

The panel reads VSD - High phase A, B, C instantaneous current. The manual prints this single wording with no variants. It is listed among the Variable speed compressor drive cycling fault messages and applies to TM, VSD, and LVSD model drives.

What it means

This shutdown is generated by the VSD if the motor current on that phase exceeds a given limit. The motor current is sensed by current transformers on the VSD output pole assemblies, and the signals are sent to the VSD logic board for processing. The limit that applies depends on the drive model (see the thresholds below).

Why it appears

  • A voltage sag on the utility power feeding the VSD, in excess of the specified voltage range for this product. This is the cause when the chiller trips but then restarts and runs without an issue, and it is especially true if the chiller was running at or near full load. When the line voltage dips suddenly, the current to the motor increases.
  • An output pole problem — the most likely cause if the chiller keeps tripping on this shutdown.

What to check

  1. Note whether the chiller was running at or near full load when the trip occurred.
  2. Restart the chiller and observe whether it runs without an issue.
  3. If the restart succeeds and the chiller runs fine, the cause was a voltage sag on the utility power feeding the VSD; the manual indicates no further action.
  4. If the chiller does not restart and keeps tripping, an output pole problem is the most likely cause and the VSD requires service.

Setpoints and thresholds

Table 178 of the manual gives the maximum instantaneous permissible currents per TM/VSD/LVSD drive model:

  • 351/292 — 771 A
  • 503/419 — 1,200 A
  • 790/658 — 1,890 A
  • 1055/914 — 2,749 A
  • 1300/1100 — 3,265 A

Reset and restart

The manual gives no separate reset procedure for this message. It is a cycling fault, so the chiller can be restarted after the trip; if it then runs without an issue, no further action is indicated. If this cycling shutdown occurs three times in 90 min, the third shutdown becomes a safety shutdown. A chiller that does not restart and keeps tripping needs the VSD serviced.

Questions engineers ask

Why does my York YK trip on VSD high phase A, B, C instantaneous current?

If the chiller restarts and runs without an issue, the cause is a voltage sag on the utility power feeding the VSD beyond the specified voltage range — especially at or near full load. If it keeps tripping, an output pole problem is the most likely cause.

What is the instantaneous current limit for the VSD on a YK chiller?

It depends on the drive model: 351/292 — 771 A, 503/419 — 1,200 A, 790/658 — 1,890 A, 1055/914 — 2,749 A, and 1300/1100 — 3,265 A.

What happens if the VSD high phase current shutdown repeats?

If this cycling shutdown occurs three times in 90 min, the third shutdown becomes a safety shutdown. A chiller that keeps tripping on this message needs the VSD serviced.

How do I clear the VSD high phase instantaneous current fault?

The manual describes no separate reset. The chiller is restarted after the trip; a successful restart that runs without an issue needs no further action, while repeated tripping means the VSD requires service.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: