On the display
The panel shows Low Discharge Superheat. In the manual's fault table for this model the message is listed as a safety fault, and the documentation prints it under exactly this wording for the YK; no shortened or alternative display text is given for it.
What it means
This message is a safety fault. The chiller control sets it when the compressor discharge superheat stays below 1.0°F for 5 minutes. The evaluation is not running from the first moment the machine starts: it is bypassed for the first 30 minutes of run time, so superheat readings taken during that start-up window cannot set the fault. The message can only be set once those 30 minutes have elapsed and the discharge superheat has then remained below 1.0°F for 5 minutes. The release notes for this software version describe this behaviour — the 30-minute run-time bypass together with the 1.0°F / 5-minute set condition — as a change made to the Low Discharge Superheat safety fault. No other thresholds or times are given for this message in the documentation for this model.
Why it appears
- The fault is set when the discharge superheat is less than 1.0°F for 5 minutes, after the 30-minute start-up bypass; the fault table lists no other cause for this message.
Setpoints and thresholds
- Set condition: discharge superheat less than 1.0°F, sustained for 5 minutes.
- Start-up bypass: no evaluation during the first 30 minutes of run time.
Questions engineers ask
What does Low Discharge Superheat mean on a YORK YK chiller?
It is a safety fault. The control sets it when the compressor discharge superheat stays below 1.0°F for 5 minutes.
Why does the Low Discharge Superheat fault not appear right after the chiller starts?
The check is bypassed for the first 30 minutes of run time, so low superheat readings during that start-up window cannot set the fault.
At what superheat does the Low Discharge Superheat fault set on a YK?
Below 1.0°F, held for 5 minutes, once the first 30 minutes of run time have passed.
Has the Low Discharge Superheat fault behaviour changed on the YK?
Yes. The release notes for this software version list the 30-minute run-time bypass and the 1.0°F / 5-minute set condition as a change made to this safety fault.