SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

YK Mod G and Later, YK Mod H and YZ/YZD Mod A, 3630 Optiview Software Version V10

Document typeService Information Letter
Document numberSI0564
EquipmentYK Centrifugal Chiller
BrandYORK
File size1.7 MB

Fault codes in this document

YZ Purge Control

Code / displayMeaningCauseActionPage
Purge Equalization Low Suction Temp WarningLow Purge Suction Temperature during the equalization period.Purge Suction Temperature is less than the Purge Suction Temperature Threshold during the entire equalization period.No longer initiates a Purge System Inhibit. Resets automatically when the Purge Suction Temperature is greater than the Purge Suction Temperature Threshold.2

Access code entry attempts

Code / displayMeaningCauseActionPage
Access Code not processed - Wait 5 seconds between attempts.Message displayed when an access code entry is attempted too soon after the previous attempt.Access code entry attempt made within the 5 second delay between access code entry attempts.Wait 5 seconds between access code entry attempts.8
Access Code not processed - 1 Minute lockout active.Message displayed when the system prevents additional logon attempts for 1 minute.An invalid access code was entered consecutively within 5 minutes for the number of times as defined by the maximum logon attempts.Lockout is active for 1 minute; no additional logon attempts are possible during that time.8
Invalid Access CodeThe code entered does not match the encrypted structure for the chiller.An invalid Access Code was entered; displays in the dialog error box if no lockout is in effect.Constitutes a failed login attempt and is logged in the Access Log.8
Expired Access CodeThe code entered is valid, but the access code duration has expired.Access code duration has expired; displays in the dialog error box if no lockout is in effect.Constitutes a failed login attempt and is logged in the Access Log.8
Inactive Access CodeThe code entered is valid, but the access time is in the future.Access time of the code is in the future; displays in the dialog error box if no lockout is in effect.Constitutes a failed login attempt and is logged in the Access Log.8

New Warnings

Code / displayMeaningCauseActionPage
WARNING - SALES ORDER - INVALID SERIAL NUMBERNew warning added with this software version; indicates the Unit Serial Number is blank.The Unit Serial Number is blank.Resets automatically when the Unit Serial Number is populated.13

Miscellaneous changes

Code / displayMeaningCauseActionPage
Chilled Liquid Flow Switch OpenFault. In software version V09 this fault did not trip during the end Prelube for YK.Corrected in this version so that only the first 44 seconds of Prelube are bypassed.13

Every row above cites the page of this document it came from, and each one is re-read against that page by an automatic check before publication.

Manufacturer document, published here as reference material for equipment we supply. The original lives at docs.johnsoncontrols.com. The rights holder may ask us to take it down — we will.