On the display
The display shows AS1668 Fan Start Failure and the amber Fault LED turns ON. The manuals print the message in this one wording. The LED is not lit directly by the panel: the panel controls the AS1668 module, and that module turns the amber Fault LED to ON.
What it means
The manuals summarise it as: Fan has been commanded to start but airflow is not confirmed
— the amber Fault LED turns ON. In full, the 4100ES-S1 panel has sent the Multi-Point I/O the control that closes the relay which controls the fan to start, for example as the result of a manual start or an auto start, and the air flow sensor in the duct has not sent the panel an indication that the air flow is ON. The fault is raised after a programmable delay, to allow the fan to speed up.
Why it appears
- The panel sent the Multi-Point I/O a control to close the relay that controls the fan to start — the manuals give a manual start or an auto start as the examples of such a command.
- The air flow sensor in the duct did not send the panel an indication that the air flow is ON.
- The panel waited through a programmable delay, to allow the fan to speed up, and the air flow confirmation still had not arrived.
What to check
- Establish how the fan was commanded to start — a manual start or an auto start, the two examples the manuals name for this sequence.
- Confirm that the panel's control to close the fan-start relay was sent to the Multi-Point I/O; that relay is what controls the fan to start.
- Check the air flow sensor in the duct: the fault means its indication that the air flow is ON never reached the panel.
- Take the programmable delay into account — the panel allows the fan time to speed up before it declares the fault, so the air flow ON indication must arrive within that delay.
Setpoints and thresholds
- Programmable delay before the fault is declared: it exists to allow the fan to speed up; the fault tables print no value for it.
Questions engineers ask
What does AS1668 Fan Start Failure mean on a Simplex 4100ES?
The fan has been commanded to start but airflow is not confirmed. The panel sent the fan-start control through the Multi-Point I/O, but the air flow sensor in the duct never sent the indication that air flow is ON, so the amber Fault LED turns ON.
Why does my 4100ES show AS1668 Fan Start Failure after a manual or auto start?
Because the air flow sensor in the duct did not report the air flow ON indication back to the panel, and the programmable delay that allows the fan to speed up expired without that confirmation arriving.
Is there a delay before AS1668 Fan Start Failure is announced?
Yes. The panel waits through a programmable delay, to allow the fan to speed up, before it controls the AS1668 module to turn the amber Fault LED ON. The manuals print no value for this delay.
Source
Written from the manufacturer's manuals for the Simplex 4100ES; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:
All Simplex 4100ES messages: fault codes · Simplex 4100ES documentation · Simplex manuals