Simplex 4100ES-S1 Fire Indicator Panel Australian User Guide

Document typeUser Guide
Document numberLT0400
Equipment4100ES-S1 Fire Alarm Control Unit
BrandSimplex
Revised2024-03-11
File size2.9 MB

Fault codes in this document

Upgrading an Existing Configuration

Code / displayMeaningCauseActionPage
Panel reports the existing configuration is an incompatible versionNon-matching configuration – panel repeatedly restartsConfiguration does not match the Panel Exec firmware installed (e.g., panel Exec firmware was updated and the configuration was not upgraded with the compatible programmer version)The upgraded version of the configuration must be downloaded before normal operation will resume17

AS1668 Fan Faults

Code / displayMeaningCauseActionPage
Amber "FLT" LED ONMechanical Services Board faultThe Mechanical Services Board sends a fault (e.g., mains failure) to the Multi-Point I/O; the Multi-Point I/O sends the fault condition to the panel74
Amber Fault LED ONAS1668 Fan Start FailurePanel sent a control to close the relay that controls the fan to start (e.g., as result of Manual start or auto start) but the air flow sensor in the duct did not send the panel an indication that the air flow is ON; indicated after a programmable delay to allow the fan to speed up74
Amber Fault LED ONAS1668 Fan Stop FailurePanel sent a control to open the relay that controls the fan to stop but the air flow sensor in the duct did not send the panel an indication via the Multi-Point I/O that the air flow is OFF; indicated after a programmable delay to allow the fan to slow down74
FAN #1 FAULTFan fault trouble point (P1265, point type TROUBLE) that drives the amber fault LEDSets when the fan control relay is set to operate the fan but the airflow indicator does not report that air is flowing; when the fan control relay is set to stop the fan but the airflow indicator reports that air is flowing; or when a fault signal is received from the Mechanical Services Board (after the FAN FAULT DELAY timer/setpoint)82

System Digital Pseudo Points

Code / displayMeaningCauseActionPage
P132
ANALOG SENSOR ALMOST DIRTY LOG ENABLE
Trouble point. When activated, lowers the dirty threshold by 10 analog units so any analog sensors approaching the dirty threshold report as dirty to the historical trouble log (for Field Service use)Must be logged in at Level 3 to force system pseudo points on or off118
P214
Clear Alarm Verification Tallies (Trouble)
When activated, clears all alarm verification tallies in the local panel; the Alarm Verification Tally Limit Exceeded trouble point is cleared by this pointActivate P214 (must be logged in at Level 3 to force system pseudo points on or off)118
P248
EARTH FAULT LATCH ENABLE
Trouble point that is turned on when earth fault latching is enabledUser enables earth fault latching from the diagnostic menuThis pseudo point should not be directly controlled by Custom Control equations118
P447
IDNET DUPLICATE SEARCH ACTIVE
Trouble pseudo that is ON when IDNet Duplicate Search is activatedIDNet Duplicate Search activated118
P448
IDNET WEAK SEARCH ACTIVE
Trouble pseudo that is ON when IDNet Weak Search is activatedIDNet Weak Search activated118
P478
Inhibit Device Troubles while Disabled (V12.06)
If this point is on, device level troubles (e.g., head missing, no answer, wrong type) are inhibited when the point is disabled; if the pseudo is off, those troubles will report even if a point is disabledTurned ON after reboot by CC Equation 3-7118
P482
RECURRING TROUBLE FILTERING ACTIVE
Trouble point the master activates whenever the algorithm to filter recurring runaway device troubles has been activatedRecurring trouble filtering set on the Systems Option Page in the ES Programmer (default is 0)118
P484
INSTALL MODE ACTIVE
Trouble point the master activates whenever a point is in Install ModeA point is in Install ModeThis trouble will clear when there are no points in Install Mode119
P480
COMPACT FLASH MISSING/ FAILED
Trouble point the master activates when the Compact Flash is missing or failedCompact flash removed, or is full or cannot be readFitting a new compact flash in the CPU will clear this trouble119
P499
FIRMWARE NEEDS UPDATE
Trouble point the master activates when the firmware needs updateIncompatible Firmware version or corrupted .BIN fileReload the firmware with the IP File Transfer utility using the Download config and all execs option, or use the History/Undo tab to restore to factory default119

System Analog Pseudo Points

Code / displayMeaningCauseActionPage
A98
BATTERY TROUBLE COUNTER
Stores the number of times a Battery Fault has been detected since last reboot119
A99
AC POWER FAIL COUNTER
Stores the number of times a Mains Fail Fault has been detected since last reboot119
A112
GROUND TROUBLE COUNTER
Stores the number of times an Earth Fault has been detected since last reboot120
A115
EXCESSIVELY DIRTY (OUT OF RANGE)
Stores the number of Excessively Dirty detectors120
A116
DIRTY SENSOR COUNTER
Stores the number of Dirty detectors120
A117
ALMOST DIRTY COUNTER
Stores the number of Almost Dirty detectors120