1413795F
VA9208-AGx-x Series On/Off and Floating Point Electric
Spring Return Valve Actuators
                                                                                     Part No. 14-1379-5, Rev. F
Installation Instructions                                                                       Issued March 2022
VA9208-AGA-3, VA9208-AGC-3
VA9208-AGC-2, VA9208-AGC-2

Applications
The VA9208-AGx-x Series On/Off and Floating Point
                                                            IMPORTANT: Use this VA9208-AGx-x Series
Electric Spring Return Actuators are direct-mount valve
                                                            On/Off and Floating Point Electric Spring Return
actuators that operate on AC/DC 24 V power. These
                                                            Actuator only to control equipment under normal
bidirectional actuators are used to provide accurate
                                                            operating conditions. Where failure or malfunction of
positioning on Johnson Controls® VG1000 Series
                                                            the electric actuator could lead to personal injury or
1-1/4, 1-1/2, and 2 in. (DN32, DN40, and DN50) ball
                                                            property damage to the controlled equipment or
valves in Heating, Ventilating, and Air Conditioning
                                                            other property, additional precautions must be
(HVAC) applications.
                                                            designed into the control system. Incorporate and
Integral line voltage auxiliary switches, available only    maintain other devices, such as supervisory or
on the VA9208-xxC-3 models, indicate end-stop               alarm systems or safety or limit controls, intended to
position, or perform switching functions within the         warn of or protect against failure or malfunction of
selected rotation range.                                    the electric actuator.
VA9208-AGA-2 actuators include plenum-rated cables          IMPORTANT : Utiliser ce VA9208-AGx-x Series
and are specially configured for installation in spaces     On/Off and Floating Point Electric Spring Return
used for environmental air-handling purposes other          Actuator uniquement pour commander des
than ducts and plenums as specified in National Fire        équipements dans des conditions normales de
Protection Association (NFPA) 70: National Electrical       fonctionnement. Lorsqu'une défaillance ou un
Code section 300.22(C), Other Space Used for                dysfonctionnement du electric actuator risque de
Environmental Air. The space over a hung ceiling used       provoquer des blessures ou d'endommager
for environmental air handling purposes is an example       l'équipement contrôlé ou un autre équipement, la
of the type of space for which these actuators are          conception du système de contrôle doit intégrer des
configured.                                                 dispositifs de protection supplémentaires. Veiller
                                                            dans ce cas à intégrer de façon permanente
                                                            d'autres dispositifs, tels que des systèmes de
                                                            supervision ou d'alarme, ou des dispositifs de
                                                            sécurité ou de limitation, ayant une fonction
                                                            d'avertissement ou de protection en cas de
                                                            défaillance ou de dysfonctionnement du electric
                                                            actuator.

                                                           Installation
                                                           Install the ball valve with the actuator at or above the
                                                           center line of the horizontal piping (see Figure 1).

                                                            IMPORTANT: In steam applications, install the
                                                            valve with the stem horizontal to the piping. Failure
                                                            to follow this precaution may shorten the life of the
                                                            actuator.

                     VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators             1
                                                                                   Installation Instructions
                                                                IMPORTANT: Do not install or use this VA9208
                                                                Series Electric Spring Return Valve Actuator in or
                                                                near environments where corrosive substances or
                                                                vapors could be present. Exposure of the actuator to
                                                                corrosive environments may damage the device’s
                                                                internal components, and will void the warranty.

                                                            Special tools needed
                                                            •     Digital voltmeter
                                                            •     T-20 TORX® driver
                                                            Dimensions
                                                            Valve actuator

                                       FIG:mntpos_H2O_app
                                                            See Figure 2 and Table 1 for valve actuator
                                                            dimensions.

        Figure 1: Mounting positions for chilled
           water and condensing atmosphere

    IMPORTANT: Before specifying VA9208 Series
    Electric Spring Return Valve Actuators for plenum
    applications, verify acceptance of exposed plastic
    materials in plenum areas with the local building
    authority. Building codes for plenum requirements
    vary by location. Some local building authorities
    accept compliance to UL 1995, Heating and Cooling
    Equipment, while others use different acceptance
    criteria.

2       VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
        Instructions
                                                        3-1/2 (89)
       3-29/32                    2-7/8            Clearance Required
         (99)                     (73)

                                                                                            Port Marking
                                                                                             Locations

                                                                                                                                 FIG:VA9208X_dims

     Figure 2:      Spring return VA9208 actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
                                              dimensions, in. (mm)

Table 1: VA9208 actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve dimensions, in. (mm)
 Valve       Valve            A                B               C             D                E               F          G
 size in.    style1
 (DN)
  1-1/4           All    5-5/32 (131)     1-1/32 (26)    1-23/32 (44)    7-1/4 (184)    3-15/16 (100)      11/32 (9)   1-31/32
 (DN32)                                                                                                                  (50)
  1-1/2           All    5-5/16 (135)     1-9/64 (29)    1-57/64 (48)   7-7/16 (189)    4-21/64 (110)      11/32 (9)   2-11/64
 (DN40)                                                                                                                  (55)
   2             2-way   5-17/32 (140)    1-15/32 (37)    2-1/8 (54)    7-11/16 (195)   4-27/320 (132)     11/32 (9)   2-27/64
 (DN50)                                                                                                                  (62)
                 3-way                                                   7-7/8 (200)

1.   Port A must always be connected to the coil (Figure 2).

VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                                              3
Instructions
Valve actuator with thermal barrier
See Figure 3 and Table 2 for valve actuator dimensions
with optional M9000-561 Thermal Barrier installed.

                                                                3-1/2 (89)
                         3-29/32                           Clearance Required
                           (99)

         A
                                                                                          F

                                                                                                         Port Marking
                                                                                                          Locations
                                                                  C                   C

             B

                                                                                                E                       G         B
                                                           D

     Figure 3:         Spring return VA9208 actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
                         with optional M9000-561 Thermal Barrier installed dimensions, in. (mm)
Table 2: VA9208 actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with optional thermal
         barrier installed dimensions, in. (mm)
 Valve       Valve                 A             B                 C                 D               E                  F             G
 size        style1
 in.
 (DN)
 1-1/4           All        9-17/64 (235)   1-1/32 (26)    1-23/32 (44)          7-1/4 (184)    3-15/16 (100)       11/32 (9)   1-31/32 (50)
 (DN32)
 1-1/2           All        9-15/16 (240)   1-9/64 (29)    1-57/64 (48)         7-7/16 (189)    4-21/64 (110)       11/32 (9)   2-11/64 (55)
 (DN40)
 2           2-way          9-31/32 (244)   1-15/32 (37)       2-1/8 (54)       7-11/16 (195)   4-27/32 (123)       11/32 (9)         N/A
 (DN50)
             3-way                                                               7-7/8 (200)                        11/32 (9)   2-27/64 (62)

1.   Port A must always be connected the coil (Figure 3).

4      VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
       Instructions
Accessories
Table 3: Accessories (order separately)
 Code number         Description
 M9000-560           Ball valve linkage kit for applying M9203 and M9208 Series Actuators to VG1000 Series Valves (quantity
                     1)
 M9000-561           Thermal barrier extends M(VA)9104, M(VA)9203, and M(VA)9208 Series Electric Spring Return Actuator
                     applications to include low pressure steam (quantity 1)
 M9000-342           Weathershield kit for VG1000 Series Ball Valve application of M(VA)9104, M(VA)9203, and M(VA)9208
                     Series Electric Spring Return Actuators (quantity 1)
 M9220-604           Replacement manual override cranks with long crank radius: 2.83 in. (72 mm) (quantity 5)
 M9208-605           Replacement manual override cranks with short crank radius: 1.83 in. (46.5 mm) (quantity 5)

Mounting                                                             3. Remove the linkage from Side A (Figure 5).
Mounting the actuator to spring return Port A
(coil) open
To mount the actuator to spring return Port A (coil)
open:
1. Turn the valve stem to the position outlined in
   Figure 4.

                                                                                                                      FIG:RMV_LNK

                                                        FIG:VG1000

             2 Way                        3 Way

      Figure 4:      Positioning the valve stem
2. Mount optional M9000-561 Thermal Barrier to the
   valve if fluid temperature exceeds 212°F (100°C).
   See the Mounting the thermal barrier section for
   more information.
                                                                               Figure 5:   Removing the linkage
Note: Proceed to Step 7 if the ball valve linkage is on
actuator Side B.

VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                                   5
Instructions
4. Insert the drive shaft into Side B (Figure 6).                     6. Insert fixed pointer and M4x0.7x83 mm long screw
                                                                         into the Side A actuator hub. Direct the arrow on
                                                                         the pointer to 100%.

                                                    FIG: DRV_SHFT_B

                                                                                                                                  FIG:FXPT_A
        Figure 6:     Inserting the drive shaft

5. Install linkage base on Side B using the two
   #10-14 x 2.75 in. long screws (Figure 7). The
   recommended torque is 20 to 24 lb·in.
   (2.3 to 2.7 N·m).                                                         Figure 8:   Installing the fixed pointer

                                                                      7. Install the actuator on the ball valve (Figure 9).
                                                                         Tighten the actuator mounting screw to a torque of
                                                                         10 to 12 lb·in. (1.1 to 1.4 N·m) and snap in the
                                                                         large adjustable pointer into place.

          Figure 7:    Installing the linkage

                                                                                                                  FIG: MNT_ACTA

                                                                                 Figure 9:   Mount the actuator

6     VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
      Instructions
Mounting the actuator to spring return Port A                          4. Insert the drive shaft into Side A (Figure 12).
(Coil) Closed
To mount the actuator to spring return port A (coil)
closed:
1. Turn the valve stem to the position outlined in
   Figure 10.

                                                       FIG:VG1000sdB
            2 Way                   3 Way

       Figure 10: Positioning the valve stem                                    Figure 12: Inserting the drive shaft

2. Mount optional M9000-561 Thermal Barrier to the                     5. Install linkage base on Side A using the two
   valve if fluid temperature exceeds 212°F (100°C).                      #10 14 x 2.75 in. long screws. The recommended
   See the Mounting the thermal barrier section for                       torque is 20 to 24 lb·in. (2.3 to 2.7 N·m).
   more information.
Note: Proceed to Step 7 if the ball valve linkage is on
actuator Side A.
3. Remove the linkage from Side B (Figure 11).

                                                                                                                            FIG:lnkgA

                                                                                 Figure 13: Installing the linkage

          Figure 11: Removing the linkage

VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                                       7
Instructions
6. Insert fixed pointer and M4x0.7x83 mm long screw      Mounting the thermal barrier
   into the Side B actuator hub. Direct the arrow on     Figure 16 shows the optional M9000-561 Thermal
   the pointer to 0% (Figure 14).                        Barrier.
                                                                            Machine Screws

                                                                                              Flange
                                                                                               Nuts
                                                             Barrier

                                                                                                  Drive
                                                                                                  Shaft

                                                           Figure 16: Optional M9000-561 Thermal Barrier

                                                         To mount the optional thermal barrier:
                                                         1. Install the thermal barrier drive shaft into the
                                                            thermal barrier by aligning the tab on the drive
                                                            shaft with the slot on the thermal barrier
                                                            (Figure 17).
      Figure 14: Installing the fixed pointer

7. Install the actuator on the ball valve (Figure 15).
   Tighten the actuator mounting screw to a torque of
   10 to 12 lb·in. (1.1 to 1.4 N·m) and snap the large
   adjustable pointer into place.

                                                                       Figure 17: Installing the drive
                                                                        shaft into the thermal barrier

                                                         2. Rotate the drive shaft to align marks on the top of
                                                            the thermal drive shaft with matching marks on the
                                                            valve stem.

         Figure 15: Mount the actuator

8     VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
      Instructions
3. Mount the thermal barrier onto the valve using the     4. The actuator requires 8-1/2 manual override crank
   four included M5x16 mm machine screws and four            rotations from the full spring return position to fully
   M5 flange nuts. Tighten the screws to a                   reposition the actuator hub. At the end of travel, the
   recommended torque of 21 to 25 lb·in.                     rotation resistance increases. Do not force the
   (2.4 to 2.8 N·m) (Figure 18)                              manual crank past this point.
                                                          5. While holding the manual crank in the wound
                                                             position, rotate and hold the red lock shaft
                                                             approximately 10° then release the manual crank
                                                             to lock the actuator hub in place.
                                                              Note: Insert and slightly rotate the manual crank
                                                              in the direction indicated by the arrow on the label
                                                              to unlock the actuator hub. Alternately, the actuator
                                                              hub automatically unlocks when power is applied
                                                              to the actuator, and returns the actuator to normal
                                                              drive and spring return operation.
                                                          Wiring
                                                                       WARNING: Risk of Electric Shock.

                                                               !       Disconnect or isolate all power supplies
                                                                       before making electrical connections.
                                           FIG:in_act                  More than one disconnection or isolation
                                                                       may be required to completely
                                                                       de-energize equipment. Contact with
                                                                       components carrying hazardous voltage
                                                                       can cause electric shock and may result
          Figure 18: Installing the Barrier                            in severe personal injury or death.

4. Proceed to the actuator mounting instructions.                      AVERTISSEMENT : Risque de
   Follow the same steps as mounting directly to the                   décharge électrique.
   valve when mounting actuator to the thermal                         Débrancher ou isoler toute alimentation
   barrier.                                                            avant de réaliser un raccordement
                                                                       électrique. Plusieurs isolations et
Note: Depending on your application, you may                           débranchements sont peut-être
position the assembly in any of the four 90° increments                nécessaires pour -couper entièrement
on the valve.                                                          l'alimentation de l'équipement. Tout
Manual override                                                        contact avec des composants porteurs
                                                                       de tensions dangereuses risque
Use only the supplied manual override crank to
                                                                       d'entraîner une décharge électrique et de
reposition the actuator hub when using the manual
                                                                       provoquer des blessures graves, voire
override feature.
                                                                       mortelles.
 IMPORTANT: Applying excessive torque to the
 manual override or operating the manual override
 with a power tool may damage the internal
 components of the actuator and cause premature
 failure.

To reposition the actuator hub, proceed as follows:
1. De-energize the actuator.
2. Insert the hex end of the manual override crank
   into the manual override adjustment point on the
   face of the actuator.
3. Rotate the manual override crank in the direction
   indicated by the arrow on the label.

VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                  9
Instructions
            CAUTION: Risk of Property Damage.

     !
                                                                             Floating Control, Four Wire
            Do not apply power to the system before
                                                                                        RA RA
            checking all wiring connections. Short                                     DA   DA
            circuited or improperly connected wires                            BLK RED GRY ORN
                                                                                    2   3   4
            may result in permanent damage to the                               1

            equipment.
            MISE EN GARDE : Risque de dégâts
            matériels.
            Ne pas mettre le système sous tension
                                                                                         ~
            avant d'avoir vérifié tous les raccords de                                            24 VAC
                                                                                 -       +        24 VDC
            câblage. Des fils formant un court-circuit
            ou connectés de façon incorrecte
            risquent d'endommager                                           Open/Close, Single Wire Control

            irrémédiablement l'équipement.                                                   RA    RA
                                                                                        DA   DA
                                                                                BLK RED GRY ORN
            CAUTION: Risk of Property Damage.                                    1   2   3   4

     !      Insulate and secure each unused wire
            lead before applying power to the
            actuator. Failure to insulate and secure
            each unused wire lead may result in
            property damage.                                                             ~         24 VAC

            MISE EN GARDE : Risque de dégâts                                     -       +        24 VDC

            matériels.
            Isoler et protéger chaque fil non utilisé
            avant de mettre l'actuator sous tension.                            On/Off Control, Two Wire

            Le non-respect de cette obligation                                                RA    RA
                                                                                         DA   DA
            d'isolation et de protection de chaque fil                           BLK RED GRY ORN
            non utilisé risque d'entraîner des dégâts                             1   2   3   4

            matériels.

 IMPORTANT: Make all wiring connections in
 accordance with the National Electrical Code and
 local regulations. Use proper Electrostatic Discharge                                        ~         24 VAC
 (ESD) precautions during installation and servicing                                 -        +         24 VDC

 to avoid damaging the electronic circuits of the
 actuator.                                                  Floating Control, Multiple Actuators with One Transformer
                                                                          RA RA                       RA RA
See Figure 19 to wire the applicable VA9208-AGx-x                        DA   DA                     DA   DA
Series model.                                                    BLK RED GRY ORN             BLK RED GRY ORN
                                                                  1   2   3   4               1   2   3   4

                                                                                                                  FIG:VA9208-AGx_cntrlwir
                                                                       ~        24 VAC
                                                                  -    +        24 VDC

                                                                 Figure 19: Control wiring diagrams

                                                           IMPORTANT: Multiple VA9208-AGx-x Actuators
                                                           must be on independent loads.

10    VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
      Instructions
Figure 20 shows the optional Auxiliary Switch Wiring.       Setup and adjustments
                                                            Mode selection switch
                                                            Actuators have an external mode selection switch to
                                                            reverse control logic. The switch is accessible from
                                                            both A and B sides of the actuator as illustrated in
                                                            Figure 22. Actuators are delivered in Direct Acting (DA)
                                                            mode and can be switched by the user to Reverse
                                                            Acting (RA) mode.

                                                                                                               FIG:AGx_modsel
                                                                   DA             RA     RA            DA

                                                                  Side A of Actuator    Side B of Actuator

                                            FIG: AX_SWCTH
          COM NC      NO   COM   NC    NO
                                                                         Figure 22: Mode selection

                                                            Control response
    Figure 20: Optional auxiliary switch wiring
                                                            The installation side of the actuator and the position of
Using conduit                                               the mode selection switch combine to determine
                                                            control response from the actuator. See Figure 23.
All VA9208 Series Actuators accept 3/8 in. (10 mm)
trade size flexible metal conduit.                                                         Installation Side

                                                                 Control Inputs          Mode Selection Switch
                                                                GRY       ORN
                                                                 3         4

                                                                                                                                FIG:VA92xxAGx_CtrlRspns
    Figure 21: Adding flexible metal conduit

1. Feed the actuator cables through the field-supplied
   conduit.
2. Push the conduit into the holes in the actuator and                  Figure 23: Control response
   secure it with the supplied 10-32 x 9/16 in. screws,
   as illustrated in Figure 21. The product label marks     Auxiliary switch (VA9208-xxC-3 models)
   the position of holes for the screws. Drive the          The VA9208-xxC-3 models include two integral
   screws through the product label in the marked           auxiliary switches with a switch adjuster accessible on
   positions. Drive the screwhead flush with the plate      either face of the actuator (Figure 5). The factory
   to secure the conduit.                                   setting for Auxiliary Switch No. 1 is 83% closing, and
                                                            the nominal setting for Auxiliary Switch No. 2 is 10%
 IMPORTANT: Careful workmanship is required to
                                                            opening (relative to the 0 to 100% rotation range as
 secure flexible metal conduit. Cut the conduit end
                                                            printed on the product label). See the Technical
 perpendicular to its axis. Insert the cut end into the
                                                            specifications table for the auxiliary switch ratings.
 bottom of the holes in the actuator and hold the
 conduit in place while securing it with the screws
 provided. Check a completed installation by pulling
 on the conduit to ensure its retention.

VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                               11
Instructions
                                                           2. Rotate the switch adjuster until it points to the
                                                              desired switch point.
             CAUTION: Risk of Property Damage.

     !       Insulate and secure each unused wire
             lead before applying power to the
             actuator. Failure to insulate and secure
             each unused wire lead may result in
             property damage.
             MISE EN GARDE : Risque de dégâts
             matériels.
             Isoler et protéger chaque fil non utilisé
             avant de mettre l'actuator sous tension.
             Le non-respect de cette obligation                                                            FIG:SW _TRP

             d'isolation et de protection de chaque fil
             non utilisé risque d'entraîner des dégâts            Figure 24: Switch trip point settings
             matériels.
                                                           3. Connect Auxiliary Switch No. 2 to a power source
The switch point of Auxiliary Switch No. 1 is fixed. The      or an ohmmeter and apply power to the actuator.
switch point of Auxiliary Switch No. 2 is independently       The actuator moves to the fully open position and
and continuously adjustable from 74 to 5% position.           holds while power is applied.
For the most accurate switch positioning, see Figure 24
and use the method in the following example. To            4. Observe the switch point. If required, repeat Step 1
change the switch point of Auxiliary Switch No. 2,            through Step 3.
proceed as follows:                                        Repair information
1. Position the actuator in the full spring return         A number of replacement parts are available; see
   position.                                               Table 3 for more details. If a VA9208 Series Electric
                                                           Spring Return Actuator fails to operate within its
     Note: The switch is factory set to trip when the
                                                           specifications, replace the unit. For a replacement
     actuator reaches the 10% position.
                                                           electric actuator, contact the nearest Johnson Controls
                                                           representative.

12     VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
       Instructions
Technical specifications
VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Actuators (Part 1 of 2 )
 Power               -AGx models          AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety
 Requirements                             Extra-Low Voltage (SELV) (Europe), 7.9 VA Running, 5.5 VA Holding Position
                                          DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe)
                                          3.5 W running, 1.9 W holding position
                                          Minimum transformer size: 8 VA per actuator
 Input signal/       -AGx models          AC 19.2 to 28.8 V at 50/60 Hz or DC 24 V +20%/-10% Class 2 (North America)
 adjustments                              or SELV (Europe) minimum pulse width: 500 ms
 Control input       -AGx models          3,000 ohm control inputs
 impedance
 Auxiliary switch    -xxC models          Two Single-Pole, Double-Throw (SPDT), double-insulated switches with gold
 rating                                   over silver contacts:
                                          AC 24 V, 50 VA pilot duty
                                          AC 120 V, 5.8 A resistive, 1/4 hp, 275 VA pilot duty
                                          AC 240 V, 5.0 A resistive, 1/4 hp, 275 VA pilot duty
 Spring return                            Direction is selectable with mounting position of actuator:
                                          Actuator face labeled A is away from valve: CCW spring return
                                          Actuator face labeled B is away from valve: CW spring return
 Rated torque        Power on             70 lb·in. (8 N·m) all operating temperatures
                     (running)
                     Power off            70 lb·in. (8 N·m) all operating temperatures
                     (spring returning)
 Rotation range                           Maximum full stroke: 95°
 Rotation time for   Power on             150 seconds for 0 to 70 lb·in. (8 N·m) load, at all operating conditions
 90 degrees of       (running)
 travel
                     Power off            17 to 25 seconds for 0 to 70 lb·in. (8 N·m) load, at room temperature
                     (spring returning)   22 seconds nominal at full rated load
                                          94 seconds maximum with 70 lb·in. (8 N·m) load, at -40°F (-40°C)
 Life cycles                              60,000 full stroke cycles with 70 lb·in. (8 N·m) load
                                          1,500,000 repositions with 70 lb·in. (8 N·m) load
 Audible noise       Power on             <35 dBA at 70 lb·in. (8 N·m) load, at a distance of 39-13/32 in. (1 m)
 rating              (running)
                     Power on             <20 dBA at a distance of 39-13/32 in. (1 m)
                     (holding)
                     Power off            <52 dBA at 70 lb·in. (8 N·m) load, at a distance of 39-13/32 in. (1 m)
                     (spring returning)
 Electrical          AGx-3 models         48 in. (1.2 m) UL 758 Type AWM halogen free cable with 18 AWG (0.85 mm2)
 connections                              conductors and 1/4 in. (6 mm) ferrule ends
                     AGx-2 models         36 in. (0.9 m) UL 444 Type CMP plenum rated cable with 19 AWG (0.75 mm2)
                                          conductors and 1/4 in. (6 mm) ferrule ends
                     Auxiliary switches   48 in. (1.2 m) UL 758 Type AWM halogen free cable with 18 AWG (0.85 mm2)
                     (-xxC models)        conductors and 1/4 in. (6 mm) ferrule ends
 Conduit connections                      Integral connectors for 3/8 in. (10 mm) flexible metal conduit
 Fluid               VG12x1 and VG18x1    23 to 203°F (-5 to 95°C), not rated for steam service
 temperature         Series
 limits
                     VG12x5 and VG18x5    -22 to 212°F (-30 to 100°C), not rated for steam service
                     Series
                     VG12x5 and VG18x5    -22 to 284°F (-30 to 140°C) water; 15 psig (103 kPa) at 250°F (121°C)
                     Series with          saturated steam
                     M9000-561 Thermal
                     Barrier installed

VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                    13
Instructions
VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Actuators (Part 2 of 2 )
 Ambient                  Standard operating          -40 to 140°F (-40 to 60°C); 90% RH maximum, noncondensing
 conditions
                          Storage                     -40 to 185°F (-40 to 85°C); 95% RH maximum, noncondensing
 Enclosure rating                                     NEMA 2 (IP54) for all mounting directions
 Compliance               United States               UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1,
                                                      Automatic Electrical Controls for Household and Similar Use; and
                                                      UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for Electric
                                                      Actuators
                          Canada                      UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002,
                                                      3rd Ed., Automatic Electrical Controls for Household and Similar Use; and
                                                      CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment
                          Europe                      CE Mark – Johnson Controls declares that this product is in compliance with
                                                      the essential requirements and other relevant provisions of the EMC Directive
                                                      and the Low Voltage Directive.
                          Australia and New           RCM Mark, Australia/NZ Emissions Compliant
                          Zealand
 Shipping weight          -AGA models                 3.5 lb (1.6 kg)
                          -AGC models                 3.9 lb (1.8 kg)
UK Single Point of Contact:   European Single Point of Contact: NA/SA Single Point of Contact:      APAC Single Point of Contact:
JOHNSON CONTROLS        JOHNSON CONTROLS                        JOHNSON CONTROLS                    JOHNSON CONTROLS
TYCO PARK GRIMSHAW LANE VOLTAWEG 20                             5757 N GREEN BAY AVE                C/O CONTROLS PRODUCT MANAGEMENT
MANCHESTER M40 2WL      6101 XK ECHT                            GLENDALE WI 53209                   NO. 32 CHANGJIANG NEW DISTRICT
UNITED KINGDOM          THE NETHERLANDS                         USA                                 WUXI JIANGSU PROVINCE 214028
                                                                                                    CHINA

                                                                                                       Building Technologies & Solutions
                                                                                                 5757 N Green Bay Ave, Glendale, WI 53209
                                                   Metasys® and Johnson Controls® are registered trademarks of Johnson Controls
                                          All other marks herein are the marks of their respective owners. © 2022 Johnson Controls

14      VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
        Instructions
Published in U.S.A.                                                                                                 www.johnsoncontrols.com