VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
VA9204-Bxx-2 Series On/Off Electric Spring Return Valve
Actuators
Installation Guide LIT-12014315 Rev. —
July 2023
Applications Installation
VA9204-Bxx-2 Series on/off electric spring return actuators Install the ball valve with the actuator at or above the center
are direct-mount valve actuators that operate on 24 VAC line of the horizontal piping (see Figure 1).
power at 50/60 Hz, 24 VDC power, or 85 VAC to 264 VAC
power at 50/60 Hz. These bidirectional actuators are used for IMPORTANT: In steam applications, install the valve with
on/off control on Johnson Controls® VG1000 Series 1/2 in., the stem horizontal to the piping. Failure to follow this
3/4 in., and 1 in. (DN15, DN20, and DN25) ball valves in precaution may shorten the life of the actuator.
HVAC applications. Figure 1: Mounting positions for chilled water and
condensing atmosphere applications
An integral line voltage auxiliary switch, available only on
the VA9204-xxB-2 models, indicates end-stop position, or
performs switching functions within the selected rotation
range.
IMPORTANT: Use this VA9204 Series valve actuator only
to control equipment under normal operating conditions.
Where failure or malfunction of the VA9204 Series
valve actuator could lead to personal injury or property
damage to the controlled equipment or other property,
additional precautions must be designed into the control
system. Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit controls,
intended to warn of or protect against failure or malfunction
of the VA9204 Series valve actuator.
IMPORTANT : Utiliser ce VA9204 Series valve actuator
uniquement pour commander des équipements dans
des conditions normales de fonctionnement. Lorsqu’une
défaillance ou un dysfonctionnement du VA9204 Series
valve actuator risque de provoquer des blessures
ou d’endommager l’équipement contrôlé ou un autre
équipement, la conception du système de contrôle doit
intégrer des dispositifs de protection supplémentaires.
Veiller dans ce cas à intégrer de façon permanente
d’autres dispositifs, tels que des systèmes de supervision IMPORTANT: Do not install or use this VA9204 Series
ou d’alarme, ou des dispositifs de sécurité ou de limitation, valve actuator in or near environments where corrosive
ayant une fonction d’avertissement ou de protection en cas substances or vapors could be present. Exposure of
de défaillance ou de dysfonctionnement du VA9204 Series the actuator to corrosive environments may damage the
valve actuator. device’s internal components, and will void the warranty.
Special tools needed
• Digital voltmeter
• T-20 TORX® driver
1 LIT-12014315 Rev. —
VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
Dimensions
Valve actuator
See Figure 2, Table 1, and Table 2 for dimensions of spring return VA9204 Series-actuated ball valves.
Figure 2: Spring return VA9204-actuated VG1241, VG1245, VG1841, and VG1845 Series ball valve dimensions,
in. (mm)
3 1/2 (89)
Clearance required
3 1/4 (82) 2 7/8 (73)
F
A
Port marking
locations
C
D
E G
B
Table 1: VA9204-actuated VG1241, VG1245, VG1841, and VG1845 Series NPT ball valve dimensions, in. (mm)
Valve size, A B C D E F G
in. (DN)
1/2 (DN15) 6 31/32 (177) 2 33/64 (64) 1 1/4 (32)
4 5/8 (117) 21/32 (17) 1 7/32 (31)
3/4 (DN20) 7 1/8 (181) 2 51/64 (71) 11/32 (9) 1 13/32 (36)
1 (DN25) 4 11/16 (119) 3/4 (19) 1 19/64 (33) 7 31/64 (190) 3 13/32 (87) 1 45/64 (43)
Note: Port A must always be connected to the coil.
Table 2: VA9204-actuated VG1271, VG1275, VG1871, and VG1875 Series sweat ball valve and VA9204-actuated
VG1291, VG1295, VG1891, and VG1895 Series press ball valve dimensions, in. (mm)
Valve size, A B C D E F G
in. (DN)
1/2 (DN15) 7 13/64 (183) 3 25/32 (96) 1 1/4 (32)
4 5/8 (117) 21/32 (17) 1 7/32 (31)
3/4 (DN20) 7 3/4 (197) 4 3/32 (104) 11/32 (9) 1 13/32 (36)
1 (DN25) 4 23/32 (120) 3/4 (19) 1 19/64 (33) 8 3/16 (208) 4 41/64 (118) 1 45/64 (43)
Note: Port A must always be connected to the coil.
2 LIT-12014315 Rev. —
VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
Valve actuator with thermal barrier
See Figure 3 and Table 3 for valve actuator dimensions with the optional M9000-561 Thermal Barrier installed.
Figure 3: Spring return VA9204-actuated VG1241, VG1245, VG1841, and VG1845 Series ball valve with the optional
M9000-561 Thermal Barrier installed dimensions, in. (mm)
3 1/2 (89)
Clearance required
3 1/4 (82) 2 7/8 (73)
A F
Port marking
locations
C
D G
E
B
Table 3: VA9204-actuated VG1241, VG1245, VG1841, and VG1845 Series NPT ball valve with the optional thermal
barrier installed dimensions, in. (mm)
Valve size, A B C D E F G
in. (DN)
1/2 (DN15) 6 31/32 (177) 2 33/64 (64) 1 1/4 (32)
6 (152) 21/32 (17) 1 7/32 (31)
3/4 (DN20) 7 1/8 (181) 2 51/64 (71) 11/32 (9) 1 13/32 (36)
1 (DN25) 6 1/16 (154) 3/4 (19) 1 19/64 (33) 7 31/64 (190) 3 13/32 (87) 1 45/64 (43)
Note: Port A must always be connected to the coil.
Repair information
A number of replacement parts are available; see Table 4 for more details. If a VA9204 Series electric actuator fails to
operate within its specifications, replace the unit. For a replacement electric actuator, contact the nearest Johnson Controls
representative.
Accessories
Table 4: Accessories (order separately)
Code number Description
M9000-560 Ball valve linkage kit for applying M9203, M9204 and M9208 Series actuators to VG1000 Series valves (quantity: 1)
M9000-561 Thermal barrier extends M(VA)9104, M(VA)9203, M(VA)9204, and M(VA)9208 Series electric spring return actuator applications to
include low pressure steam (quantity: 1)
M9000-342 Weathershield kit for VG1000 Series ball valve application of VA9104, VA9203, VA9204, and VA9208 Series electric actuators
(quantity: 1)
M9000-607 Position indicator for VG1000 Series ball valve applications (quantity: 5)
M9000-700 Universal ball valve linkage kit (quantity: 1)
3 LIT-12014315 Rev. —
VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
Mounting 4. Insert the drive shaft into Side B (Figure 6). The drive shaft
Mounting the actuator to spring return Port A (coil) open is keyed for one-way assembly. With gentle pressure
To mount the actuator to spring return Port A (coil) open: applied, rotate the drive shaft until the key aligns and the
drive shaft falls into place.
1. Turn the valve stem to the position outlined in Figure 4. Figure 6: Inserting the drive shaft
Figure 4: Positioning the valve stem
2-way 3-way
2. Mount the optional M9000-561 Thermal Barrier to the valve
if fluid temperature exceeds 212°F (100°C). See the
Mounting the thermal barrier section for more information.
Note: Proceed to Step 7 if the ball valve linkage is on actuator 5. Install the linkage base on Side B using the two
Side B. #8‑32 x 0.625 in. long screws (Figure 7). Tighten the
linkage screws to a torque of 29 lb·in. to 33 lb·in.
3. Remove the linkage from Side A (Figure 5). (3.3 N•m to 3.7 N•m).
Figure 5: Removing the linkage Figure 7: Installing the linkage
4 LIT-12014315 Rev. —
VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
6. Insert the fixed pointer and M4x0.7x83 mm long screw into Mounting the actuator to spring return Port A (coil)
the Side A actuator hub (Figure 8). Direct the arrow on the closed
pointer to 100%. To mount the actuator to spring return Port A (coil) closed:
Figure 8: Installing the fixed pointer
1. Turn the valve stem to the position outlined in Figure 10.
Figure 10: Positioning the valve stem
2-way 3-way
2. Mount the optional M9000-561 Thermal Barrier to the valve
if fluid temperature exceeds 212°F (100°C). See the
Mounting the thermal barrier section for more information.
Note: Proceed to Step 7 if the ball valve linkage is on actuator
Side A.
3. Remove the linkage from Side B (Figure 11).
Figure 11: Removing the linkage
7. Install the actuator on the ball valve (Figure 9). Tighten the
actuator mounting screw to a torque of 10 lb·in. to 12 lb·in.
(1.1 N•m to 1.4 N•m) and snap the large adjustable pointer
into place.
Figure 9: Mounting the actuator
5 LIT-12014315 Rev. —
VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
4. Insert the drive shaft into Side A (Figure 12). The drive shaft 6. Insert the fixed pointer and M4x0.7x83 mm long screw into
is keyed for one-way assembly. With gentle pressure the Side B actuator hub (Figure 14). Direct the arrow on the
applied, rotate the drive shaft until the key aligns and the pointer to 0%.
drive shaft falls into place. Figure 14: Installing the fixed pointer
Figure 12: Inserting the drive shaft
5. Install the linkage base on Side A using the two
#8-32 x 0.625 in. long screws (Figure 13). Tighten the
linkage screws to a torque of 29 lb·in. to 33 lb·in.
(3.3 N•m to 3.7 N•m).
Figure 13: Installing the linkage
7. Install the actuator on the ball valve (Figure 15). Tighten the
actuator mounting screw to a torque of 10 lb·in. to 12 lb·in.
(1.1 N•m to 1.4 N•m) and snap the large adjustable pointer
into place.
Figure 15: Mounting the actuator
6 LIT-12014315 Rev. —
VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
Mounting the thermal barrier 2. Rotate the drive shaft to align marks on the top of the
Figure 16 shows the optional M9000-561 Thermal Barrier. thermal drive shaft with matching marks on the valve stem.
Figure 16: Optional M9000-561 Thermal Barrier 3. Mount the thermal barrier onto the valve using the four
included M5x16 mm machine screws and four M5 flange
Machine screws nuts. Tighten the screws to a torque of 21 lb·in. to 25 lb·in.
(2.4 N•m to 2.8 N•m) (Figure 18).
Figure 18: Installing the barrier
Flange
nuts
Barrier
Drive
shaft
To mount the optional thermal barrier:
1. Install the thermal barrier drive shaft into the thermal barrier
by aligning the tab on the drive shaft with the slot on the
thermal barrier (Figure 17).
Figure 17: Installing the drive shaft into the thermal
barrier
4. Proceed to actuator mounting instructions. Follow the same
steps as mounting directly to the valve when mounting the
actuator to the thermal barrier.
7 LIT-12014315 Rev. —
VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
Wiring WARNING: Risk of electric shock.
See Figure 19 and Figure 20 to wire the applicable Disconnect or isolate all power supplies before
VA9204‑Bxx-2 Series model. making electrical connections. More than one
Figure 19: Control wiring diagrams disconnection or isolation may be required to
completely de-energize equipment. Contact with
components carrying hazardous voltage can cause
M M electric shock and may result in severe personal
injury or death.
BLK RED WHT BLK AVERTISSEMENT : Risque de décharge
électrique.
1 2 1 2 Débrancher ou isoler toute alimentation
avant de réaliser un raccordement électrique.
Plusieurs isolations et débranchements sont
peut-être nécessaires pour couper entièrement
l’alimentation de l’équipement. Tout contact avec
des composants porteurs de tensions dangereuses
risque d’entraîner une décharge électrique et de
provoquer des blessures graves, voire mortelles.
CAUTION: Risk of property damage.
T ~ 24 VAC 50/60 Hz N L1 Do not apply power to the system before checking
- + 24 VDC 85...264 VAC 50/60 Hz all wiring connections. Short circuited or improperly
connected wires may result in permanent damage
Figure 20: Optional auxiliary switch wiring diagram to the equipment.
5.0 (2.9) A 240 V
S1 MISE EN GARDE : Risque de dégâts matériels.
21 Ne pas mettre le système sous tension avant
23 d’avoir vérifié tous les raccords de câblage.
22
Des fils formant un court-circuit ou connectés
21 de façon incorrecte risquent d’endommager
irrémédiablement l’équipement.
BLK / BLK / BLK /
RED BLU GRY
21 22 23
COM NC NO
8 LIT-12014315 Rev. —
VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
WARNING: Risk of property damage. Setup and adjustments
Insulate and secure each unused wire lead before Auxiliary switch (VA9204-xxB-xx models)
applying power to the actuator. Failure to insulate WARNING: Risk of electric shock and property
and secure each unused wire lead may result in damage.
property damage. Insulate and secure each unused wire lead before
applying power to the actuator. Failure to insulate
AVERTISSEMENT : Risque de dégâts matériels. and secure each unused wire lead may result
Isoler et protéger chaque fil non utilisé avant de in property damage, electric shock, and severe
mettre l’actuator sous tension. Le non-respect personal injury or death.
de cette obligation d’isolation et de protection de
chaque fil non utilisé risque d’entraîner des dégâts AVERTISSEMENT : Risque de décharge
matériels. électrique et dégâts matériels.
Isoler et protéger chaque fil non utilisé avant de
IMPORTANT: Make all wiring connections in accordance mettre l’actuator sous tension. Le non-respect
with the National Electrical Code and local regulations. Use de cette obligation d’isolation et de protection
proper Electrostatic Discharge (ESD) precautions during de chaque fil non utilisé risque d’entraîner des
installation and servicing to avoid damaging the electronic dégâts matériels, des décharges électriques et des
circuits of the actuator. blessures graves, voire mortelles.
Using conduit The VA9204-xxB-xx models include one integral auxiliary
All VA9204 Series actuators accept 1/2 in. threaded switch with a switch adjuster accessible on either face
electrician’s fittings (Figure 21). of the actuator (Figure 22). The factory setting for the
Figure 21: Adding flexible metal conduit auxiliary switch is 10% closing (relative to the 0% to 100%
rotation range as printed on the product label). See the
Technical specifications section for the auxiliary switch
ratings.
The switch point is continuously adjustable throughout the
actuator’s rotation range. For the most accurate switch
positioning, see Figure 22 and use the method in the following
example. To change the switch point of the auxiliary switch:
1. Position the actuator in the full spring return position.
1. Feed the actuator cables through the field-supplied
Note: The switch is factory set to trip when the actuator
electrician’s fitting and conduit.
reaches the 10% position.
2. Thread the electrician’s fitting into the actuator and secure
the conduit to the fitting in accordance with local building
2. Rotate the switch adjuster until it points to the desired
code requirements.
switch point.
3. Connect the auxiliary switch to a power source or an
ohmmeter and apply power to the actuator. The actuator
moves to the fully open position and holds while power is
applied.
4. Observe the switch point. If required, repeat Step 1 through
Step 3.
Figure 22: Switch trip point settings
9 LIT-12014315 Rev. —
VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
Technical specifications
VA9204-Bxx-2 Series On/Off Electric Spring Return Actuator
Specification Description
-BGx-2 models 24 VAC (19.2 VAC to 28.8 VAC) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV) (Europe), 5 VA running,
Power 1.6 VA holding position, 24 VDC (21.6 VDC to 28.8 VDC): Class 2 (North America) or SELV (Europe) 2.8 W running, 0.8 W holding
requirements position. Minimum transformer size: 6 VA for each actuator
-BUx-2 models 100 VAC to 240 VAC (85 VAC to 264 VAC) at 50/60 Hz: 0.06 A running, 0.02 A holding position
Auxiliary switch -xxB-2 models One single-pole, double-throw (SPDT), double-insulated switch with silver contacts:
rating 24 VAC, 50 VA pilot duty
120 VAC, 5.8 A resistive, 1/4 hp, 275 VA pilot duty
240 VAC, 5.0 A resistive, 1/4 hp, 275 VA pilot duty
Spring return Direction is selectable with mounting position of actuator:
Actuator face labeled A is away from valve: CCW spring return
Actuator face labeled B is away from valve: CW spring return
Power on 35 lb·in. (4 N•m) all operating temperatures
(running)
Rated torque
Power off 35 lb·in. (4 N•m) all operating temperatures
(spring returning)
Rotation range Maximum full stroke: 95°
Power on 53 s to 71 s constant for 0 lb·in. to 35 lb·in. (4 N•m) load, at room temperature
(running) 60 s nominal at full rated load (0.25 rpm)
Rotation time
-Bxx-2 models
for 90 degrees
Power off 37 s to 46 s for 0 lb·in. to 35 lb·in. (4 N•m) load, at room temperature
of travel
(spring returning) 44 s nominal at full rated load
75 s maximum with 35 lb·in. (4 N•m) load at -22°F (-30°C)
Life cycles 60,000 full stroke cycles with 35 lb·in. (4 N·m) load
Power on <36 dBA at 35 lb·in. (4 N•m) load, at a distance of 39 13/32 in. (1 m)
(running)
Audible noise Power on <20 dBA at a distance of 39 13/32 in. (1 m)
rating (holding)
Power off <35 dBA at 35 lb·in. (4 N•m) load, at a distance of 39 13/32 in. (1 m)
(spring returning)
Actuator 48 in. (1.2 m) UL 758 Type AWM halogen-free cable with 18 AWG (0.85 mm2) conductors and 0.25 in. (6 mm) ferrule ends
Electrical (all models)
connections Auxiliary switches 48 in. (1.2 m) UL 758 Type AWM halogen-free cable with 18 AWG (0.85 mm2) conductors and 0.25 in. (6 mm) ferrule ends
(-xxB-2 models)
Conduit connections Integral 1/2 in. (13 mm) threaded conduit connectors
VG12x1 and 23°F to 203°F (-5°C to 95°C), not rated for steam service
VG18x1 Series
VG12x5 and -22°F to 212°F (-30°C to 100°C), not rated for steam service
Fluid VG18x5 Series
temperature VG12x5 and -22°F to 284°F (-30°C to 140°C) water; 15 psig (103 kPa) at 250°F (121°C) saturated steam
limits VG18x5 Series
with M9000-561
Thermal Barrier
installed
Standard -22°F to 140°F (-30°C to 60°C); 90% RH maximum, non-condensing
Ambient
operating
conditions
Storage -40°F to 185°F (-40°C to 85°C); 95% RH maximum, non-condensing
Enclosure rating NEMA 2 (IP54) for all mounting directions
Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for Household and Similar Use;
and UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for Electric Actuators. Plenum Rated (UL 2043). Suitable for use
in other environmental air space (plenums) in accordance with Section 300.22 (C) of the National Electric Code.
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic Electrical Controls for Household
and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment.
Europe Johnson Controls declares that this products is in compliance with the essential requirements and other relevant provisions of the
EMC Directive and Low Voltage Directive and equivalent UK regulations.
Australia and RCM Mark, Australia/NZ Emissions Compliant
New Zealand
-xxA Models 2.0 lb (0.9 kg)
Shipping weight
-xxB Models 2.4 lb (1.1 kg)
10 LIT-12014315 Rev. —
VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
Product warranty
This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/buildingswarranty.
Patents
Patents: https://jcipat.com
Single point of contact
APAC EU UK NA/SA
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT VOLTAWEG 20 TYCO PARK 5757 N GREEN BAY AVE.
NO. 32 CHANGJIANG RD. NEW DISTRICT 6101 XK ECHT GRIMSHAW LANE GLENDALE WI 53209
WUXI JIANGSU PROVINCE 214028 THE NETHERLANDS MANCHESTER USA
CHINA M40 2WL
UNITED KINGDOM
For more contact information, refer to www.johnsoncontrols.com/locations.
Building Technologies & Solutions
Headquarters: Milwaukee, Wisconsin, USA
Branch offices: Principal cities worldwide
Johnson Controls® is a registered trademark of Johnson Controls.
All other marks herein are the marks of their respective owners.
© Copyright 2023 Johnson Controls. All rights reserved. Any unauthorized use or copying is strictly prohibited.