14138024E
VA9203-GGx-xx Series Proportional Electric Spring Return
Valve Actuators
Installation Instructions
VA9203-GGA-2Z, VA9203-GGB-2Z Part No. 14-1380-24, Rev. E
Issued March 2022
Applications
The VA9203-GGx-2Z Series Proportional Electric Spring Return Actuators are direct-mount valve actuators that
operate on AC/DC 24 V power. These bidirectional actuators are used to provide accurate positioning on Johnson
Controls® VG1000 Series 1/2, 3/4, and 1 in. (DN15, DN20, and DN25) ball valves in Heating, Ventilating, and Air
Conditioning (HVAC) applications.
An integral line voltage auxiliary switch, available only on the VA9203-GGB-2Z model, indicates end-stop position,
or performs switching functions within the selected rotation range.
VA9203-GGA-2Z actuators include plenum-rated cables and are specially configured for installation in spaces used
for environmental air-handling purposes other than ducts and plenums as specified in National Fire Protection
Association (NFPA) 70: National Electrical Code section 300.22(C), Other Space Used for Environmental Air. The
space over a hung ceiling used for environmental air handling purposes is an example of the type of space for
which these actuators are configured.
IMPORTANT: Use this VA9203 Series Valve Actuator only to control equipment under normal operating
conditions. Where failure or malfunction of the VA9203 Series Valve Actuator could lead to personal injury or
property damage to the controlled equipment or other property, additional precautions must be designed into the
control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against failure or malfunction of the VA9203 Series Valve Actuator.
IMPORTANT : Utiliser ceVA9203 Series Valve Actuator uniquement pour commander des équipements dans
des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du VA9203 Series
Valve Actuator risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires.
Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou
d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en
cas de défaillance ou de dysfonctionnement du
VA9203 Series Valve Actuator.
Installation
Install the ball valve with the actuator at or above the center line of the horizontal piping (see Figure 1).
IMPORTANT: In steam applications, install the valve with the stem horizontal to the piping. Failure to follow this
precaution may shorten the life of the actuator.
IMPORTANT: Do not install or use this actuator in or near environments where corrosive substances or vapors
could be present. Exposure of the actuator to corrosive environments may damage the device’s internal
components, and will void the warranty.
Special tools needed
• Digital voltmeter
• T-20 TORX® driver
VA9203-GGx-xx Series Proportional Electric Spring Return Valve
Actuators Installation Instructions
1
FIG:mntpos_H2O_app
Figure 1: Mounting positions for chilled
water and condensing atmosphere
Dimensions
Valve actuator
See Figure 2 and Table 1 and Table 2 for dimensions of spring return VA9203 Series actuated ball valves.
3-1/2 (88.9)
Clearance Required
2-7/8
3-1/4
(82)
(73)
A
Port Marking
Locations
D FIG:VA9203X_dims
Figure 2: Spring return VA9203 actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
dimensions, in. (mm)
Table 1: VA9203 actuated VG1241, VG1245, VG1841, and VG1845 Series NPT Ball Valve dimensions,
in. (mm)
Valve size, A B C D E F G
in. (DN)1
1/2 (DN15) 4-5/8 (117.3) 21/32 (17) 1-7/32 (31) 6-31/32 (177) 2-33/64 (64) 11/32 (9) 1-1/4 (32)
3/4 (DN20) 4-5/8 (117.3) 21/32 (17) 1-7/32 (31) 7-1/8 (181) 2-51/64 (71) 11/32 (9) 1-13/32 (36)
1 (DN25) 4-11/16 (119) 3/4 (19) 1-19/64 (33) 7-31/64 (190) 3-13/32 (87) 11/32 (9) 1-45/64 (43)
1. Port A must always be connected to the coil.
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
2
Table 2: VA9203 actuated VG1271, VG1275, VG1871, and VG1875 Series Sweat Ball Valve and VA9203
actuated VG1291, VG1295, VG1891, and VG1895 Series Press Ball Valve dimensions, in. (mm)
Valve size, A B C D E F G
in. (DN)1
1/2 (DN15) 4-5/8 (117.3) 21/32 (17) 1-7/32 (31) 7-13/64 (183) 3-25/32 (96) 11/32 (9) 1-1/4 (32)
3/4 (DN20) 4-5/8 (117.3) 21/32 (17) 1-7/32 (31) 7-3/4 (197) 4-3/32 (104) 11/32 (9) 1-13/32 (36)
1 (DN25) 4-11/16 (119) 3/4 (19) 1-19/64 (33) 8-3/16 (208) 4-41/64 (118) 11/32 (9) 1-45/64 (43)
1. Port A must always be connected to the coil.
Valve actuator with thermal barrier
See Figure 3 and Table 3 for valve actuator dimensions with optional M9000-561 thermal barrier installed.
3-1/2 (88.9)
Clearance Required
3-1/4 2-7/8
(82) (73)
A
Port Marking
Locations
FIG:VA9203X_dims
D
Figure 3: Spring return VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
with optional M9000-561 Thermal Barrier Installed dimensions, in. (mm)
Table 3: VA9203 actuated VG1241, VG1245, VG1841, and VG1845 Series NPT Ball Valve with optional
thermal barrier installed dimensions, in. (mm)
Valve size in. A B C D E F G
(DN)1
1/2 (DN15) 6 (152) 21/32 (17) 1-7/32 (31) 6-31/32 (177) 2-33/64 (64) 11/32 (9) 1-1/4 (32)
3/4 (DN20) 6 (152) 21/32 (17) 1-7/32 (31) 7-1/8 (181) 2-51/64 (71) 11/32 (9) 1-13/32 (36)
1 (DN25) 6-1/16 (154) 3/4 (19) 1-19/64 (33) 7-31/64 (190) 3-13/32 (87) 11/32 (9) 1-45/64 (43)
1. Port A must always be connected to the coil.
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
3
Accessories
Table 4: Accessories (order separately)
Code number Description
M9000-560 Ball valve linkage kit for applying M9203 and M9208 Series Actuators to VG1000 Series Valves (quantity
1)
M9000-561 Thermal barrier extends M(VA)9104, M(VA)9203, and M(VA)9208 Series Electric Spring Return Actuator
applications to include low pressure steam (quantity 1)
M9000-342 Weathershield kit for VG1000 Series Ball Valve application of VA9104, VA9203, and VA9208 Series
Electric Spring Return Actuators (quantity 1)
M9000-607 Position indicator for VG1000 Series Ball Valve applications (quantity 5)
M9000-700 Universal ball valve linkage kit (quantity1)
Mounting
Mounting the actuator to spring return Port A (coil) open
To mount the actuator to spring return Port A (coil) open:
1. Turn the valve stem to the position outlined in Figure 4.
FIG:VG1000
2 Way 3 Way
Figure 4: Positioning the valve stem
2. Mount optional M9000-561 Thermal Barrier to the valve if fluid temperature exceeds 212°F (100°C). See the
Mounting the thermal barrier section for more information.
Note: Proceed to Step 7 if the ball valve linkage is on actuator Side B.
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
4
3. Remove the linkage from Side A (Figure 5).
FIG:RMV_LNK
Figure 5: Removing the linkage
4. Insert the drive shaft into Side B (Figure 6). The drive shaft is keyed for one-way assembly. With gentle
pressure applied, rotate the drive shaft until the key aligns and the drive shaft falls into place.
FIG:DRV_SHFT
Figure 6: Inserting the drive shaft
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
5
5. Install linkage base on Side B using the two #8-32 x 0.625 in. long screws (Figure 7). The recommended
torque is 29 to 33 lb·in. (3.3 to 3.7 N·m).
FIG: INST_LNK
Figure 7: Installing the linkage
6. Insert fixed pointer and M4x0.7x83 mm long screw into the Side A actuator hub (Figure 8). Direct the arrow on
the pointer to 100%.
FIG:FXPT
Figure 8: Installing the fixed
pointer
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
6
7. Install the actuator on the ball valve (Figure 9). Tighten the actuator mounting screw to a torque of 10 to 12
lb·in. (1.1 to 1.4 N·m) and snap the large adjustable pointer into place.
FIG:MNT_ACT
Figure 9: Mount the actuator
Mounting the actuator to spring return Port A (coil) closed
To mount the actuator to spring return port A (coil) closed:
1. Turn the valve stem to the position outlined in Figure 10.
FIG:VG1000sdB
2 Way 3 Way
Figure 10: Positioning the valve stem
2. Mount optional M9000-561 Thermal Barrier to the valve if fluid temperature exceeds 212°F (100°C). See the
Mounting the thermal barrier section for more information.
Note: Proceed to Step 7 if the ball valve linkage is on actuator Side A.
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
7
3. Remove the linkage from Side B (Figure 13).
FIG:RMV_LNK_B
Figure 11: Removing the linkage
4. Insert the drive shaft into Side A (Figure 12). The drive shaft is keyed for one-way assembly. With gentle
pressure applied, rotate the drive shaft until the key aligns and the drive shaft falls into place.
Figure 12: Inserting the drive shaft
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
8
5. Install linkage base on Side A using the two #8-32 x 0.625 in. long screws (Figure 13). The recommended
torque is 29 to 33 lb·in. (3.3 to 3.7 N·m).
FIG: INST_LNK
Figure 13: Installing the linkage
6. Insert fixed pointer and M4x0.7x83 mm long screw into the Side B actuator hub (Figure 14). Direct the arrow on
the pointer to 0%.
FIG:INST_FXPT_B
Figure 14: Installing the fixed pointer
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
9
7. Install the actuator on the ball valve (Figure 15). Tighten the actuator mounting screw to a torque of
10 to 12 lb·in. (1.1 to 1.4 N·m) and snap the large adjustable pointer into place.
FIG:MNT_ACT_B
Figure 15: Mount the actuator
Mounting the thermal barrier
Figure 16 shows the optional M9000-561 Thermal Barrier.
Machine Screws
Flange
Nuts
Barrier
Drive
Shaft
Figure 16: Optional M9000-561 Thermal Barrier
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
10
To mount the optional thermal barrier:
1. Install the thermal barrier drive shaft into the thermal barrier by aligning the tab on the drive shaft with the slot
on the thermal barrier (Figure 17).
Figure 17: Installing the drive
shaft into the thermal barrier
2. Rotate the drive shaft to align marks on the top of the thermal drive shaft with matching marks on the valve
stem.
3. Mount the thermal barrier onto the valve using the four included M5x16 mm machine screws and four M5
flange nuts. Tighten the screws to a recommended torque of 21 to 25 lb·in.
(2.4 to 2.8 N·m).(Figure 18).
FIG:in_act
Figure 18: Installing the barrier
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
11
4. Proceed to actuator mounting instructions. Follow the same steps as mounting directly to the valve when
mounting the actuator to the thermal barrier.
Wiring
See Figure 19, Figure 20, and Figure 21 to wire the applicable VA9203-GGx-xx Series model.
DC 0(2)...10 V Control
BLK RED GRY ORN
1 2 3 4
+
AC/DC
24 V ~(+)
DC 0(2)...10 V Y
DC 0(2)...10 V +
U
COM
0(4)...20 mA Control with
External Resistor
BLK RED GRY ORN
1 2 3 4
+
AC/DC
24 V ~(+)
0(4)...20 mA
Y
500Ω / 0.25 W
DC 0(2)...10 V +
U
COM
Master-Slave Application
Master-Subordinate Application
BLK RED GRY ORN BLK RED GRY ORN
1 2 3 4 1 2 3 4
+ +
AC/DC
24 v
~(+)
FIG:VA9208-GGx_cntrlwir
DC 0(2)...10 V Y
DC 0(2)...10 V +
U
COM
Figure 19: Control Wiring Diagrams
Figure 19: Control wiring diagrams
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
12
Override to MIN position Override to MAX position
BLK RED GRY ORN BLK RED GRY ORN
1 2 3 4 1 2 3 4
+ +
AC
24 V ~
B
A
AC C
24 V ~
DC 0(2)...10 V Y
DC 0(2)...10 V Y
DC 0(2)...10 V +
DC 0(2)...10 V +
U
U
COM
COM
A Open = MIN Position
B Closed = MAX Position
A Closed = Normal Operation
C Closed = Normal Operation
Override to
MIN, MID, MAX positions Override to
0(4)...20 mA Control with MIN, MID, MAX positions
External Resistor 0(2)...10 V Control
BLK RED GRY ORN BLK RED GRY ORN
1 2 3 4 1 2 3 4
+ +
A A
B B
AC AC
24 V ~ 24 V ~
0(4)...20 mA
C DC
C
Y Y
0(2)...10 V
500 Ω / 0.25 W + +
U U
COM NCOM
N
C A B C
O
A B
I
T
C
O
I )
N
U
F
T
C
N
U
F
0% ( MIN 0% ( MIN )
FIG:M9203GGx2(Z)_wir
50% ( MID ) 50% ( MID )
100% ( MAX ) 100% ( MAX )
NORMAL NORMAL
Figure 20: Control wiring diagrams (overrides)
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
13
5.0 (2.9) A 240 V ~
21 S1
23
22
21
BLK/ BLK/ BLK/
RED BLU GRY
21 22 23
COM NC NO
Figure 21: Auxiliary
switch wiring diagram
WARNING: Risk of Electric Shock.
! Disconnect or isolate all power supplies before making electrical connections. More than one
disconnection or isolation may be required to completely de-energize equipment. Contact with
components carrying hazardous voltage can cause electric shock and may result in severe personal
injury or death.
AVERTISSEMENT : Risque de décharge électrique.
Débrancher ou isoler toute alimentation avant de réaliser un raccordement électrique. Plusieurs
isolations et débranchements sont peut-être nécessaires pour -couper entièrement l'alimentation de
l'équipement. Tout contact avec des composants porteurs de tensions dangereuses risque d'entraîner
une décharge électrique et de provoquer des blessures graves, voire mortelles.
CAUTION: Risk of Property Damage.
! Do not apply power to the system before checking all wiring connections. Short circuited or improperly
connected wires may result in permanent damage to the equipment.
MISE EN GARDE : Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils
formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement
l'équipement.
CAUTION: Risk of Property Damage.
! Insulate and secure each unused wire lead before applying power to the actuator. Failure to insulate
and secure each unused wire lead may result in property damage.
MISE EN GARDE : Risque de dégâts matériels.
Isoler et protéger chaque fil non utilisé avant de mettre l'actuator sous tension. Le non-respect de cette
obligation d'isolation et de protection de chaque fil non utilisé risque d'entraîner des dégâts matériels.
IMPORTANT: Make all wiring connections in accordance with the National Electrical Code and local
regulations. Use proper Electrostatic Discharge (ESD) precautions during installation and servicing to avoid
damaging the electronic circuits of the actuator.
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
14
Using conduit
All VA9203 Series Actuators accept 1/2 in. (13 mm) threaded electrician’s fittings.(Figure 22).
Figure 22: Adding flexible metal conduit
1. Feed the actuator cables through the field supplied electrician’s fitting and conduit.
2. Thread the electrician’s fitting into the actuator and secure the conduit to the fitting in accordance with local
building code requirements.
Setup and adjustments
Mode selection switch
Actuators have an external mode selection switch to calibrate, select the input signal range, and to reverse the
control logic. The switch is accessible from both the A and B sides of the actuator (Figure 23). Actuators are
delivered in Direct Acting (DA), DC 0 to 10 V input signal mode. To change to Reverse Acting (RA) mode, move the
mode selection switch from DA to RA. The input signal range is selectable between DC 0 to 10 V or DC 2 to 10 V.
If the CAL function is not used, both input signal ranges are proportioned across the full rotation range of 0 to 95°
rotation.
For example, if a DC 0 to 10 V input signal is selected an the rotation range is limited to 75, the rotation range lit will
be reached at DC 8.3 V.
CAL CAL
2-10 2-10 2-10 2-10
+ + + +
DA RA RA DA
0-10 0-10 0-10 0-10
FIG:modesel
Side A of Actuator Side B of Actuator
Figure 23: Mode selection
Control response
The installation side of the actuator and the position of the mode selection switch combine to determine control
response from the actuator (Figure 24).
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
15
Installation Side
Mode Selection Switch
CAL CAL
Input Signal 2-10 2-10 2-10 2-10
+ + + +
DA RA RA DA
0-10 0-10 0-10 0-10
Increasing
Decreasing
Rotation Position
Direction Feedback
Direct 0-10 V 0.0 V 1.7 V 3.3 V 5.0 V 6.7 V 8.3 V 10.0 V
Acting 2-10 V
FIG:VA92xxCtrlRspns
Reverse 0-10 V
Acting 2-10 V 10.0 V 8.7 V 7.3 V 6.0 V 4.7 V 3.3 V 2.0 V
* 0° is the spring return position.
Figure 24: Control response
Calibration (CAL) function
The CAL function enables the actuator to redefine the selected input signal range proportionally across a reduced
rotation range. The actuator maintains calibration when power is lost or removed.
Follow these steps to calibrate the input signal range:
1. With power applied to the actuator, move the mode selection switch to the CAL position and leave it in this
position for approximately 5 seconds. The actuator begins rotating until the end-stops are found.
2. Move the mode selection switch to the desired input signal range. Selection can me made while the calibration
process is in progress, or after it is complete. The selected input signal is proportionally reconfigured to the
reduced rotation range.
Note: During normal operation, if the actuator stroke increases due to seal or seat wear, input signals are
automatically reconfigured to the increased rotation range in approximately 0.5° increments.
3. If the actuator mounting position is changed or if the linkage is adjusted, repeat Step 1 and Step 2 to repeat the
CAL function.
Note: The mode selection switch must remain out of the CAL position for at least 2 seconds before re-
initiating the CAL function.
Note: If the mode selection switch is left in the CAL position, the actuator defaults to 0-10 V input signal range,
DA.
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
16
Auxiliary switch (VA9203-xxB-xx models)
The VA9203-xxB-xx models include one integral auxiliary switch with a switch adjuster accessible on either face of
the actuator (Figure 25). The factory setting for auxiliary switch is 10% closing (relative to the 0 to 100% rotation
range as printed on the product label). See the Technical specifications table for the auxiliary switch ratings.
WARNING: Risk of Electric Shock and Property Damage.
! Insulate and secure each unused wire lead before applying power to the actuator. Failure to insulate
and secure each unused wire lead may result in property damage, electric shock, and severe personal
injury or death.
AVERTISSEMENT : Risque de décharge électrique et dégâts matériels.
Isoler et protéger chaque fil non utilisé avant de mettre l'actuator sous tension. Le non-respect de cette
obligation d'isolation et de protection de chaque fil non utilisé risque d'entraîner des dégâts matériels,
des décharges électriques et des blessures graves, voire mortelles.
The switch point is continuously adjustable throughout the actuator’s rotation range. For the most accurate switch
positioning, see Figure 25 and use the method in the following example. To change the switch point of auxiliary
switch, proceed as follows:
1. Position the actuator in the full spring return position.
Note: The switch is factory set to trip when the actuator reaches the 10% position.
2. Rotate the switch adjuster until it points to the desired switch point.
3. Connect the auxiliary switch to a power source or an ohmmeter and apply power to the actuator. The actuator
moves to the fully open position and holds while power is applied.
4. Observe the switch point. If required, repeat Step 1 through Step 3.
Figure 25: Switch trip point settings
Repair information
A number of replacement parts are available; see Table 4 for more details. If an VA9203 Series Electric Spring
Return Actuator fails to operate within its specifications, replace the unit. For a replacement electric actuator,
contact the nearest Johnson Controls representative.
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
17
Technical specifications
VA9203-GGx-2Z Series Proportional Electric Spring Return Actuator (Part 1 of 2 )
Power requirements AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety
Extra-Low Voltage (SELV) (Europe), 4.7 VA running, 2.7 VA holding position
DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe) 1.8
W running, 1 W holding position
Minimum transformer size: 6 VA per actuator
Input signal/adjustments Factory set at DC 0 to 10 V, CW rotation with signal increase
selectable DC 0 (2) to 10 V or 0 (4) to 20 mA with field-furnished 500 ohm 0.25
W minimum resistor
Switch selectable direct or reverse action with signal increase
Control input impedance Voltage input: 100,000 ohm
Current input: 500 ohm with field-furnished 500 ohm resistor
Feedback signal DC 0 (2) to 10 V for desired rotation range up to 95°
Corresponds to rotation limits, 0.5 mA at 10 V maximum
Auxiliary switch -xxB models One Single-Pole, Double-Throw (SPDT), double-insulated switch with silver
rating contacts:
AC 24 V, 50 VA pilot duty
AC 120 V, 5.8 A resistive, 1/4 hp, 275 VA pilot duty
AC 240 V, 5.0 A resistive, 1/4 hp, 275 VA pilot duty
Spring return Direction is selectable with mounting position of actuator:
Actuator face labeled A is away from valve: CCW spring return
Actuator face labeled B is away from valve: CW spring return
Rated torque Power on 27 lb·in (3 N·m) all operating temperatures
(running)
Power off 27 lb·in (3 N·m) all operating temperatures
(spring returning)
Rotation range Maximum full stroke: 95°
Adjustable stop: 35° to 95° maximum position
Rotation time for Power on 90 seconds constant for 0 to 27 lb·in. (3 N·m) load, at all operating conditions
90 degrees of (running)
travel
Power off 12 to 17 seconds for 0 to 27 lb·in. (3 N·m) load, at room temperature
(spring returning) 16 seconds nominal at full rated load
22 seconds maximum with 27 lb·in. (3 N·m) load, at -22°F (-30°C)
Life cycles 60,000 full stroke cycles with 27 lb·in. (3 N·m) load
1,500,000 repositions with 27 lb·in. (3 N·m) load
Audible noise Power on <37 dBA at 27 lb·in. (3 N·m) load, at a distance of 39-13/32 in. (1 m)
rating (running)
Power on <20 dBA at a distance of 39-13/32 in. (1 m)
(holding)
Power off <56 dBA at 27 lb·in. (3 N·m) load, at a distance of 39-13/32 in. (1 m)
(spring returning)
Electrical GGA-2Z models 36 in. (0.9 m) UL 444 Type CMP plenum rated cable with 19 AWG (0.75 mm2)
connections conductors and 1/4 in. (6 mm) ferrule ends
GGB-2Z models 48 in. (1.2 m) UL 758 Type AWM halogen free cable with 18 AWG (0.85 mm2)
conductors and 1/4 in. (6 mm) ferrule ends
Conduit connections Integral 1/2 in. (13 mm) threaded conduit connector(s)
VA9203-GGx-xx Series Proportional Electric Spring Return Valve Actuators Installation Instructions
18
VA9203-GGx-2Z Series Proportional Electric Spring Return Actuator (Part 2 of 2 )
Fluid VG12x1 and VG18x1 23 to 203°F (-5 to 95°C), not rated for steam service
temperature Series
limits
VG12x5 and VG18x5 -22 to 212°F (-30 to 100°C), not rated for steam service
Series
VG12x5 and VG18x5 -22 to 284°F (-30 to 140°C) water; 15 psig (103 kPa) at 250°F (121°C)
Series with saturated steam
M9000-561 Thermal
Barrier installed
Ambient Standard operating -22 to 140°F (-30 to 60°C); 90% RH maximum, noncondensing
conditions
Storage -40 to 185°F (-40 to 85°C); 95% RH maximum, noncondensing
Enclosure rating NEMA 2 (IP54) for all mounting directions
Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1,
Automatic Electrical Controls for Household and Similar Use; and
UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for Electric
Actuators
Plenum Rated (UL 2043). Suitable for use in other environmental air space
(plenums) in accordance with Section 300.22 (C) of the National Electric Code
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002,
3rd Ed., Automatic Electrical Controls for Household and Similar Use; and
CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment
Europe CE Mark – Johnson Controls declares that this product is in compliance with
the essential requirements and other relevant provisions of the EMC Directive
2004/108/EC and Low Voltage Directive 2006/95/EC
Australia and New C-Tick Mark, Australia/NZ Emissions Compliant
Zealand
Shipping weight -GGA models 2.0 lb (0.9 kg)
-GGB models 2.4 lb (1.1 kg)
UK Single Point of Contact: European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
TYCO PARK GRIMSHAW LANE VOLTAWEG 20 5757 N GREEN BAY AVE C/O CONTROLS PRODUCT MANAGEMENT
MANCHESTER M40 2WL 6101 XK ECHT GLENDALE WI 53209 NO. 32 CHANGJIANG NEW DISTRICT
UNITED KINGDOM THE NETHERLANDS USA WUXI JIANGSU PROVINCE 214028
CHINA
Building Technologies & Solutions
5757 N Green Bay Ave Glendale, WI 53209
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners. © 2022 Johnson Controls.