*14138016E*
                                                                                       14-1380-16, Rev. F

VA9203-Bxx-2 Series On/Off Electric Spring Return
Valve Actuators
                                                                                       Part No. 14-1380-16, Rev. F
Installation Instructions                                                                           Issued June 2018
VA9203-BGA-2, VA9203-BGB-2,VA9203-BUA-2, VA9203-BUB-2

Applications                                                Installation
The VA9203-Bxx-2 Series On/Off Electric Spring              Install the ball valve with the actuator at or above the
Return Actuators are direct-mount valve actuators that      center line of the horizontal piping (see Figure 1).
operate on AC 24 V power at 50/60 Hz, DC 24 V
power, or AC 85 to 264 V power at 50/60 Hz. These               IMPORTANT: In steam applications, install the
bidirectional actuators are used for on/off control on          valve with the stem horizontal to the piping. Failure
Johnson Controls® VG1000 Series 1/2, 3/4, and 1 in.             to follow this precaution may shorten the life of the
(DN15, DN20, and DN25) ball valves in Heating,                  actuator.
Ventilating, and Air Conditioning (HVAC) applications.
An integral line voltage auxiliary switch, available only
on the VA9203-xxB-2 models, indicates end-stop
position, or performs switching functions within the
selected rotation range.

 IMPORTANT: Use this VA9203 Series Valve
 Actuator only to control equipment under normal
 operating conditions. Where failure or malfunction of
 the VA9203 Series Valve Actuator could lead to
 personal injury or property damage to the controlled
 equipment or other property, additional precautions
 must be designed into the control system.
 Incorporate and maintain other devices, such as
 supervisory or alarm systems or safety or limit

                                                                                                      FIG:mntpos_H2O_app
 controls, intended to warn of or protect against
 failure or malfunction of the VA9203 Series Valve
 Actuator.
 IMPORTANT : Utiliser ce VA9203 Series Valve                        Figure 1: Mounting Positions for Chilled
 Actuator uniquement pour commander des                                Water and Condensing Atmosphere
 équipements dans des conditions normales de
 fonctionnement. Lorsqu'une défaillance ou un                   IMPORTANT: Do not install or use this VA9203
 dysfonctionnement duVA9203 Series Valve                        Series Valve Actuator in or near environments where
 Actuatorrisque de provoquer des blessures ou                   corrosive substances or vapors could be present.
 d'endommager l'équipement contrôlé ou un autre                 Exposure of the actuator to corrosive environments
 équipement, la conception du système de contrôle               may damage the device’s internal components, and
 doit intégrer des dispositifs de protection                    will void the warranty.
 supplémentaires. Veiller dans ce cas à intégrer de
 façon permanente d'autres dispositifs, tels que des        Special Tool Needed
 systèmes de supervision ou d'alarme, ou des                •     Digital voltmeter
 dispositifs de sécurité ou de limitation, ayant une
 fonction d'avertissement ou de protection en cas de        •     T-20 TORX® driver
 défaillance ou de dysfonctionnement du
 VA9203 Series Valve Actuator.

                              VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation               1
                                                                                               Instructions
Dimensions
Valve Actuator
See Figure 2, Table 1, and Table 2 for dimensions of
Spring Return VA9203 Series Actuated Ball Valves.

                                                                     3-1/2 (89)
                                                                Clearance Required
                                                  2-7/8
                   3-1/4                          (73)
                   (82)

                                 A

                                                                                                          Port Marking
                                                                                                           Locations

                                                            D                                                                         FIG:VA9203X_dims

     Figure 2:    Spring Return VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
                                           Dimensions, in. (mm)

Table 1: VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series NPT Ball Valve Dimensions, in.
         (mm)
 Valve Size,               A              B                     C                    D              E                F              G
 in. (DN)1
 1/2 (DN15)       4-5/8 (117)        21/32 (17)           1-7/32 (31)          6-31/32 (177)   2-33/64 (64)    11/32 (9)      1-1/4 (32)
 3/4 (DN20)       4-5/8 (117)        21/32 (17)           1-7/32 (31)          7-1/8 (181)     2-51/64 (71)    11/32 (9)      1-13/32 (36)
 1 (DN25)         4-11/16 (119)      3/4 (19)             1-19/64 (33)         7-31/64 (190)   3-13/32 (87)    11/32 (9)      1-45/64 (43)

1.   Port A must always be connected to the coil.

Table 2: VA9203 Actuated VG1271, VG1275, VG1871, and VG1875 Series Sweat Ball Valve and VA9203
         Actuated VG1291, VG1295, VG1891, and VG1895 Series Press Ball Valve Dimensions, in. (mm)
 Valve Size,               A              B                     C                    D                E                  F            G
 in. (DN)1
 1/2 (DN15)        4-5/8 (117)       21/32 (17)           1-7/32 (31)          7-13/64 (183)   3-25/32 (96)       11/32 (9)     1-1/4 (32)
 3/4 (DN20)        4-5/8 (117)       21/32 (17)           1-7/32 (31)          7-3/4 (197)     4-3/32 (104)       11/32 (9)     1-13/32 (36)
 1 (DN25)          4-23/32 (120)     3/4 (19)             1-19/64 (33)         8-3/16 (208)    4-41/64 (118)      11/32 (9)     1-45/64 (43)

1.   Port A must always be connected to the coil.

2      VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions
Valve Actuator with Thermal Spacer
See Figure 3 and Table 3 for valve actuator dimensions
with optional M9000-561 Thermal Barrier installed.

                                                                   3-1/2 (89)
                                                              Clearance Required
                       3-1/4                      2-7/8
                       (82)                       (73)

                                   A

                                                                                                  Port Marking
                                                                                                   Locations

                                                                                                                               FIG:VA9203X_dimsthbr

                                                          D

     Figure 3:    Spring Return VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
                    with Optional M9000-561 Thermal Barrier Installed Dimensions, in. (mm)

Table 3: VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series NPT Ball Valve with Optional
         Thermal Barrier Installed Dimensions, in. (mm)
 Valve Size,               A                B                  C                   D              E                  F                                G
 in. (DN)1
 1/2 (DN15)         6 (152)            21/32 (17)         1-7/32 (31)        6-31/32 (177)   2-33/64 (64)        11/32 (9)   1-1/4 (32)
 3/4 (DN20)         6 (152)            21/32 (17)         1-7/32 (31)        7-1/8 (181)     2-51/64 (71)        11/32 (9)   1-13/32 (36)
 1 (DN25)           6-1/16 (154)       3/4 (19)           1-19/64 (33)       7-31/64 (190)   3-13/32 (87)        11/32 (9)   1-45/64 (43)

1.    Port A must always be connected to the coil.

Accessories
Table 4: Accessories (Order Separately)
 Code Number          Description
 M9000-560            Ball Valve Linkage Kit for Applying M9203 and M9208 Series Actuators to VG1000 Series Valves
                      (Quantity 1)
 M9000-561            Thermal Barrier Extends M(VA)9104, M(VA)9203, and M(VA)9208 Series Electric Spring Return Actuator
                      Applications to Include Low Pressure Steam (Quantity 1)
 M9000-342            Weathershield Kit for VG1000 Series Ball Valve application of VA9104, VA9203, and VA9208 Series
                      Electric Spring Return Actuators (quantity 1)
 M9000-607            Position Indicator for VG1000 Series Ball Valve Applications (Quantity 5)
 M9000-700            Universal Ball Valve Linkage Kit (Quantity 1)

                   VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions                                            3
Mounting                                                                4. Insert the drive shaft into Side B (Figure 6). The
                                                                           drive shaft is keyed for one-way assembly. With
Mounting the Actuator to Spring Return Port A                              gentle pressure applied, rotate the drive shaft until
(Coil) Open                                                                the key aligns and the drive shaft falls into place.
To mount the actuator to spring return Port A (coil)
open:
1. Turn the valve stem to the position outlined in
   Figure 4.

                                                                                                                                         FIG:DRV_SHFT

                                                           FIG:VG1000

           2 Way                         3 Way                                   Figure 6:   Inserting the Drive Shaft
      Figure 4:    Positioning the Valve Stem
                                                                        5. Install linkage base on Side B using the two
2. Mount optional M9000-561 Thermal Barrier to the                         #8-32 x 0.625 in. long screws (Figure 7). The
   valve if fluid temperature exceeds 212°F (100°C).                       recommended torque is 29 to 33 lb·in.
   See the Mounting the Thermal Barrier section for                        (3.3 to 3.7 N·m).
   more information.
Note: Proceed to Step 7 if the ball valve linkage is on
actuator Side B.
3. Remove the linkage from Side A (Figure 5).

                                                                                                                         FIG: INST_LNK

                                                                                 Figure 7:    Installing the Linkage

                                             FIG:RMV_LNK

          Figure 5:   Removing the Linkage

4     VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions
6. Insert fixed pointer and M4x0.7x83 mm long screw               Mounting the Actuator to Spring Return Port A
   into the Side A actuator hub (Figure 8). Direct the            (Coil) Closed
   arrow on the pointer to 100%.                                  To mount the actuator to spring return Port A (coil)
                                                                  closed:
                                                                  1. Turn the valve stem to the position outlined in
                                                                     Figure 10.

                                                                                                                                 FIG:VG1000sdB
                                                                              2 Way                  3 Way

                                                                         Figure 10: Positioning the Valve Stem
                                                       FIG:FXPT
                                                                  2. Mount optional M9000-561 Thermal Barrier to the
                                                                     valve if fluid temperature exceeds 212°F (100°C).
           Figure 8:   Installing the Fixed
                                                                     See the Mounting the Thermal Barrier section for
                       Pointer
                                                                     more information.
7. Install the actuator on the ball valve (Figure 9).             Note: Proceed to Step 7 if the ball valve linkage is on
   Tighten the actuator mounting screw to a torque of             actuator Side A.
   10 to 12 lb·in. (1.1 to 1.4 N·m) and snap the large
   adjustable pointer into place.                                 3. Remove the linkage from Side B (Figure 13).

                                              FIG:MNT_ACT

                                                                                                                 FIG:RMV_LNK_B
          Figure 9:    Mount the Actuator

                                                                           Figure 11: Removing the Linkage

                VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions                                      5
4. Insert the drive shaft into Side A (Figure 12). The            6. Insert fixed pointer and M4x0.7x83 mm long screw
   drive shaft is keyed for one-way assembly. With                   into the Side B actuator hub (Figure 14). Direct the
   gentle pressure applied, rotate the drive shaft until             arrow on the pointer to 0%.
   the key aligns and the drive shaft falls into place.

                                                                                                               FIG:INST_FXPT_B
        Figure 12: Inserting the Drive Shaft

5. Install linkage base on Side A using the two                         Figure 14: Installing the Fixed Pointer
   #8-32 x 0.625 in. long screws (Figure 13). The
   recommended torque is 29 to 33 lb·in.                          7. Install the actuator on the ball valve (Figure 15).
   (3.3 to 3.7 N·m).                                                 Tighten the actuator mounting screw to a torque of
                                                                     10 to 12 lb·in. (1.1 to 1.4 N·m) and snap the large
                                                                     adjustable pointer into place.

                                                                                                                                 FIG:MNT_ACT_B
                                                  FIG: INST_LNK

          Figure 13: Installing the Linkage
                                                                             Figure 15: Mount the Actuator

6     VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions
Mounting the Thermal Barrier                                2. Rotate the drive shaft to align marks on the top of
Figure 16 shows the optional M9000-561 Thermal                 the thermal drive shaft with matching marks on the
Barrier.                                                       valve stem.
                     Machine Screws                         3. Mount the thermal barrier onto the valve using the
                                                               four included M5x16 mm machine screws and four
                                                               M5 flange nuts. Tighten the screws to a
                                                               recommended torque of 21 to 25 lb·in.
                                                               (2.4 to 2.8 N·m) (Figure 18).

                                    Flange
                                     Nuts
   Barrier

                                      Drive
                                      Shaft

 Figure 16: Optional M9000-561 Thermal Barrier

To mount the optional thermal barrier:
1. Install the thermal barrier drive shaft into the
   thermal barrier by aligning the tab on the drive
                                                                                                      FIG:in_act
   shaft with the slot on the thermal barrier
   (Figure 17).

                                                                      Figure 18: Installing the Barrier

                                                            4. Proceed to actuator mounting instructions. Follow
                                                               the same steps as mounting directly to the valve
                                                               when mounting the actuator to the thermal barrier.

             Figure 17: Installing the Drive
             Shaft into the Thermal Barrier

                  VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions      7
Wiring
See Figure 19 and Figure 20 to wire the applicable
                                                                      WARNING: Risk of Electric Shock.
VA9203-Bxx-2 Series model.
                                                                      Disconnect or isolate all power supplies
                                                                  !   before making electrical connections.
                                                                      More than one disconnection or isolation
                                                                      may be required to completely
                    BLK RED                                           de-energize equipment. Contact with
                     1   2                                            components carrying hazardous voltage
                                                                      can cause electric shock and may result
                                                                      in severe personal injury or death.
                                                                      AVERTISSEMENT : Risque de
                                                                      décharge électrique.
                                                                      Débrancher ou isoler toute alimentation
                            ~ AC 24 V 50/60                           avant de réaliser un raccordement
                        -   + DC 24 V
                                                                      électrique. Plusieurs isolations et
                                                                      débranchements sont peut-être
                                                                      nécessaires pour -couper entièrement
                                                                      l'alimentation de l'équipement. Tout
                     WHT BLK                                          contact avec des composants porteurs
                      1   2                                           de tensions dangereuses risque
                                                                      d'entraîner une décharge électrique et de
                                                                      provoquer des blessures graves, voire
                                                                      mortelles.

                                          FIG:VA9203Bxx2_wiring
                                                                      CAUTION: Risk of Property Damage.
                                                                      Do not apply power to the system before
                       N     L1
               AC 85...264 V 50/60 Hz                             !   checking all wiring connections. Short
              Figure 19: Control Wiring                               circuited or improperly connected wires
                      Diagrams                                        may result in permanent damage to the
                                                                      equipment.
                   5.0 (2.9) A 240 V ~                                MISE EN GARDE : Risque de dégâts
                            21 S1
                                                                      matériels.
                   23                                                 Ne pas mettre le système sous tension
                   22                                                 avant d'avoir vérifié tous les raccords de
                            21                                        câblage. Des fils formant un court-circuit
                   BLK/ BLK/ BLK/                                     ou connectés de façon incorrecte
                   RED BLU GRY                                        risquent d'endommager
                    21   22   23
                                                                      irrémédiablement l'équipement.

                 COM NC NO

    Figure 20: Optional Auxiliary Switch Wiring

8     VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions
            CAUTION: Risk of Property Damage.
                                                            Auxiliary Switch (VA9203-xxB-xx Models)
            Insulate and secure each unused wire
     !      lead before applying power to the
                                                                        WARNING: Risk of Electric Shock and
                                                                        Property Damage.
            actuator. Failure to insulate and secure
            each unused wire lead may result in
                                                                 !      Insulate and secure each unused wire
                                                                        lead before applying power to the
            property damage.                                            actuator. Failure to insulate and secure
            MISE EN GARDE : Risque de dégâts                            each unused wire lead may result in
            matériels.                                                  property damage, electric shock, and
            Isoler et protéger chaque fil non utilisé                   severe personal injury or death.
            avant de mettre l'actuator sous tension.                    AVERTISSEMENT : Risque de
            Le non-respect de cette obligation                          décharge électrique et dégâts
            d'isolation et de protection de chaque fil                  matériels.
            non utilisé risque d'entraîner des dégâts                   Isoler et protéger chaque fil non utilisé
            matériels.                                                  avant de mettre l'actuator sous tension.
                                                                        Le non-respect de cette obligation
 IMPORTANT: Make all wiring connections in                              d'isolation et de protection de chaque fil
 accordance with the National Electrical Code and                       non utilisé risque d'entraîner des dégâts
 local regulations. Use proper Electrostatic Discharge                  matériels, des décharges électriques et
 (ESD) precautions during installation and servicing                    des blessures graves, voire mortelles.
 to avoid damaging the electronic circuits of the
 actuator.                                                  The VA9203-xxB-xx models include one integral
                                                            auxiliary switch with a switch adjuster accessible on
Using Conduit                                               either face of the actuator (Figure 22). The factory
All VA9203 Series Actuators accept 1/2 in. threaded         setting for Auxiliary Switch is 10% closing (relative to
electrician’s fittings (Figure 21).                         the 0 to 100% rotation range as printed on the product
                                                            label). See the Technical Specifications section for the
                                                            auxiliary switch ratings.
                                                            The switch point is continuously adjustable throughout
                                                            the actuators’s rotation range. For the most accurate
                                                            switch positioning, see Figure 22 and use the method
                                                            in the following example. To change the switch point of
                                                            auxiliary switch, proceed as follows:
                                                            1. Position the actuator in the full spring return
                                                               position.

     Figure 21: Adding Flexible Metal Conduit                   Note: The switch is factory set to trip when the
                                                                actuator reaches the 10% position.
1. Feed the actuator cables through the field-supplied
   electrician’s fitting and conduit.                       2. Rotate the switch adjuster until it points to the
                                                               desired switch point.
2. Thread the electrician’s fitting into the actuator and
                                                            3. Connect the auxiliary switch to a power source or
   secure the conduit to the fitting in accordance with
                                                               an ohmmeter and apply power to the actuator. The
   local building code requirements.
                                                               actuator moves to the fully open position and holds
Setup and Adjustments                                          while power is applied.
                                                            4. Observe the switch point. If required, repeat Step 1
                                                               through Step 3.
                                                            Repair Information
                                                            A number of replacement parts are available; see
                                                            Table 4 for more details. If an VA9203 Series Electric
                                                            Actuator fails to operate within its specifications,
                                                            replace the unit. For a replacement electric actuator,
                                                            contact the nearest Johnson Controls representative.

                 VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions         9
     Figure 22: Switch Trip Point Settings

10   VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions
Technical Specifications
VA9203-Bxx-x Series On/Off Electric Spring Return Actuator (Part 1 of 2 )
 Power                -BGx-2 Models         AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety
 Requirements                               Extra-Low Voltage (SELV) (Europe), 5 VA Running, 1.6 VA Holding Position DC
                                            24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe) 2.8 W
                                            Running, 0.8 W Holding Position
                                            Minimum Transformer Size: 6 VA per Actuator
                      -BUx-2 Models         AC 100 V to 240 V (AC 85 V to 264 V) at 50/60 Hz: 0.06 A Running,
                                            0.02 A Holding Position
 Auxiliary Switch     -xxB-2 Models         One Single-Pole, Double-Throw (SPDT), Double-Insulated Switch with Silver
 Rating                                     Contacts:
                                            AC 24 V, 50 VA Pilot Duty
                                            AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty
                                            AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
 Spring Return                              Direction is Selectable with Mounting Position of Actuator:
                                            Actuator Face Labeled A is Away from Valve: CCW Spring Return
                                            Actuator Face Labeled B is Away from Valve: CW Spring Return
 Rated Torque         Power On              27 lb·in. (3 N·m) All Operating Temperatures
                      (Running)
                      Power Off             27 lb·in. (3 N·m) All Operating Temperatures
                      (Spring Returning)
 Rotation Range                             Maximum Full Stroke: 95°
 Rotation Time        Power On              53 to 71 Seconds Constant for 0 to 27 lb·in. (3 N·m) Load, at Room Temperature
 for 90 Degrees       (Running)             60 Seconds Nominal at Full Rated Load (0.25 rpm)
 of Travel            Bxx-2 Models
                      Power Off             37 to 46 Seconds for 0 to 27 lb·in. (3 N·m) Load, at Room Temperature
                      (Spring Returning)    44 Seconds Nominal at Full Rated Load
                                            75 Seconds Maximum with 27 lb·in. (3 N·m) Load at -22°F (-30°C)
 Life Cycles                                60,000 Full Stroke Cycles with 27 lb·in. (3 N·m) Load
 Audible Noise        Power On              <36 dBA at 27 lb·in. (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
 Rating               (Running)
                      Power On              <20 dBA at a Distance of 39-13/32 in. (1 m)
                      (Holding)
                      Power Off             <35 dBA at 27 lb·in. (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
                      (Spring Returning)
 Electrical           Actuator              48 in. (1.2 m) UL 758 Type AWM Halogen Free Cable with 18 AWG (0.85 mm2)
 Connections          (All Models)          Conductors and 0.25 in. (6 mm) Ferrule Ends
                      Auxiliary Switches    48 in. (1.2 m) UL 758 Type AWM Halogen Free Cable with 18 AWG (0.85 mm2)
                      (-xxB-2 Models)       Conductors and 0.25 in. (6 mm) Ferrule Ends
 Conduit Connections                        Integral 1/2 in. (13 mm) Threaded Conduit Connectors

                                                                                        Building Technologies & Solutions
                                                                                507 E. Michigan Street, Milwaukee, WI 53202
                                             Metasys® and Johnson Controls® are registered trademarks of Johnson Controls,
                                     All other marks herein are the marks of their respective owners. © 2018 Johnson Controls

11    VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions

Published in U.S.A.                                                                                 www.johnsoncontrols.com
VA9203-Bxx-x Series On/Off Electric Spring Return Actuator (Part 2 of 2 )
 Fluid              VG12x1 and           23 to 203°F (-5 to 95°C), Not Rated for Steam Service
 Temperature        VG18x1 Series
 Limits
                    VG12x5 and           -22 to 212°F (-30 to 100°C), Not Rated for Steam Service
                    VG18x5 Series
                    VG12x5 and           -22 to 284°F (-30 to 140°C) water; 15 psig (103 kPa) at 250°F (121°C) Saturated
                    VG18x5 Series        Steam
                    with
                    M9000-561
                    Thermal Barrier
                    Installed
 Ambient            Standard             -22 to 140°F (-30 to 60°C); 90% RH Maximum, Noncondensing
 Conditions         Operating
                    Storage              -40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
 Enclosure Rating                        NEMA 2 (IP54) for all Mounting Directions
 Compliance         United States        UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1,
                                         Automatic Electrical Controls for Household and Similar Use; and UL 60730-2-14:
                                         2002-02, Ed. 1, Part 2 Particular Requirements for Electric Actuators
                                         Plenum Rated (UL 2043). Suitable for use in other environmental air space
                                         (plenums) in accordance with Section 300.22 (C) of the National Electric Code
                    Canada               UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002,
                                         3rd Ed., Automatic Electrical Controls for Household and Similar Use; and CSA
                                         C22.2 No. 24-93 Temperature Indicating and Regulating Equipment
                    Europe               CE Mark – Johnson Controls declares that this product is in compliance with the
                                         essential requirements and other relevant provisions of the
                                         EMC Directive and the Low Voltage Directive.
                    Australia and New    RCM Mark, Australia/NZ Emissions Compliant
                    Zealand
 Shipping Weight    -xxA Models          2.0 lb (0.9 kg)
                    -xxB Models          2.4 lb (1.1 kg)

European Single Point of Contact:       NA/SA Single Point of Contact:          APAC Single Point of Contact:
JOHNSON CONTROLS                        JOHNSON CONTROLS                        JOHNSON CONTROLS
WESTENDHOF 3                            507 E MICHIGAN ST                       C/O CONTROLS PRODUCT
45143 ESSEN                             MILWAUKEE WI 53202                      MANAGEMENT
GERMANY                                 USA                                     NO. 22 BLOCK D NEW DISTRICT
                                                                                WUXI JIANGSU PROVINCE 214142
                                                                                CHINA

12    VA9203-Bxx-2 Series On/Off Electric Spring Return Valve Actuators Installation Instructions