1413808E
VA9203-AGx-2Z Series On/Off and Floating Point Electric
Spring Return Valve Actuators
Installation Instructions
VA9203-AGA-2Z, VA9203-AGB-2Z                                                          Part No. 14-1380-8, Rev. E
                                                                                                 Issued March 2022

Applications
The VA9203-AGx-2Z Series On/Off and Floating Point
                                                             IMPORTANT: Use this VA9203 Series Valve
Electric Spring Return Actuators are direct-mount valve
                                                             Actuator only to control equipment under normal
actuators that operate on AC/DC 24 V power. These
                                                             operating conditions. Where failure or malfunction of
bidirectional actuators are used to provide accurate
                                                             the VA9203 Series Valve Actuator could lead to
positioning on Johnson Controls® VG1000 Series
                                                             personal injury or property damage to the controlled
1/2, 3/4, and 1 in. (DN15, DN20, and DN25) ball valves
                                                             equipment or other property, additional precautions
in Heating, Ventilating, and Air Conditioning (HVAC)
                                                             must be designed into the control system.
applications.
                                                             Incorporate and maintain other devices, such as
An integral line voltage auxiliary switch, available only    supervisory or alarm systems or safety or limit
on the VA9203-AGB-2Z models, indicates end-stop              controls, intended to warn of or protect against
position, or performs switching functions within the         failure or malfunction of the VA9203 Series Valve
selected rotation range.                                     Actuator.
VA9203-AGA-2Z actuators includes plenum-rated                IMPORTANT : Utiliser ce VA9203 Series Valve
cables and are specially configured for installation in      Actuator uniquement pour commander des
spaces used for environmental air-handling purposes          équipements dans des conditions normales de
other than ducts and plenums as specified in National        fonctionnement. Lorsqu'une défaillance ou un
Fire Protection Association (NFPA) 70: National              dysfonctionnement du VA9203 Series Valve
Electrical Code section 300.22(C), Other Space Used          Actuatorrisque de provoquer des blessures ou
for Environmental Air. The space over a hung ceiling         d'endommager l'équipement contrôlé ou un autre
used for environmental air handling purposes is an           équipement, la conception du système de contrôle
example of the type of space for which these actuators       doit intégrer des dispositifs de protection
are configured.                                              supplémentaires. Veiller dans ce cas à intégrer de
                                                             façon permanente d'autres dispositifs, tels que des
                                                             systèmes de supervision ou d'alarme, ou des
                                                             dispositifs de sécurité ou de limitation, ayant une
                                                             fonction d'avertissement ou de protection en cas de
                                                             défaillance ou de dysfonctionnement du
                                                             VA9203 Series Valve Actuator.

                                                            Installation
                                                            Install the ball valve with the actuator at or above the
                                                            center line of the horizontal piping (see Figure 1).

                                                             IMPORTANT: In steam applications, install the
                                                             valve with the stem horizontal to the piping. Failure
                                                             to follow this precaution may shorten the life of the
                                                             actuator.

                               VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve             1
                                                                        Actuators Installation Instructions
                                                                                                  IMPORTANT: Do not install or use this VA9203
                                                                                                  Series Electric Spring Return Valve Actuator in or
                                                                                                  near environments where corrosive substances or
                                                                                                  vapors could be present. Exposure of the actuator to
                                                                                                  corrosive environments may damage the device’s
                                                                                                  internal components, and will void the warranty.

                                                                                              Special tool needed
                                                                                              •     Digital voltmeter
                                                                                              •     T-20 TORX® driver
                                                                                              Dimensions
                                                                                              Valve actuator

                                                FIG:mntpos_H2O_app
                                                                                              See Table 1, Table 2, and Figure 2 for the dimensions
                                                                                              of the VA9203 Series Actuated Ball Valves.

      Figure 1: Mounting positions for chilled
         water and condensing atmosphere

                                                                              3-1/2 (89)
                                                                         Clearance Required

                                        2-7/8
              3-1/4
              (82)
                                        (73)

                            A

                                                                                                                        Port Marking
                                                                                                                         Locations

                                                                     D                                                                             FIG:VA9203X_dims

     Figure 2:        Spring return VA9203 actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
                                                dimensions, in. (mm)

Table 1: VA9203 actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve dimensions, in. (mm)
 Valve size,                A               B                                   C                    D              E                  F             G
 in. (DN)1
 1/2 (DN15)           4-5/8 (117)     21/32 (17)                         1-7/32 (31)          6-31/32 (177)    2-33/64 (64)     11/32 (9)    1-1/4 (32)
 3/4 (DN20)           4-5/8 (117)     21/32 (17)                         1-7/32 (31)          7-1/8 (181)      2-51/64 (71)      11/32 (9)   1-13/32 (36)
 1 (DN25)             4-11/16 (119)   3/4 (19)                           1-19/64 (33)         7-31/64 (190)    3-13/32 (87)      11/32 (9)   1-45/64 (43)

1.   Port A must always be connected to the coil.

2      VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
       Instructions
Table 2: VA9203 actuated VG1271, VG1275, VG1871, and VG1875 Series Sweat Ball Valve and VA9203
         actuated VG1291, VG1295, VG1891, and VG1895 Series Press Ball Valve dimensions, in. (mm)
 Valve size,              A              B                  C                 D                 E                    F                               G
 in. (DN)1
 1/2 (DN15)         4-5/8 (117)     21/32 (17)        1-7/32 (31)       7-13/64 (183)    3-25/32 (96)          11/32 (9)     1-1/4 (32)
 3/4 (DN20)         4-5/8 (117)     21/32 (17)        1-7/32 (31)       7-3/4 (197)      4-3/32 (104)          11/32 (9)     1-13/32 (36)
 1 (DN25)           4-11/16 (119)   3/4 (19)          1-19/64 (33)      8-3/16 (208)     4-41/64 (118)         11/32 (9)     1-45/64 (43)

1.    Port A must always be connected to the coil.

Valve actuator with thermal barrier
See Figure 3 and Table 3 for valve actuator dimensions
with optional M9000-561 thermal barrier installed.

                                                             3-1/2 (89)
                                                        Clearance Required
                  3-1/4                   2-7/8
                  (82)                    (73)

                              A

                                                                                              Port Marking
                                                                                               Locations

                                                                                                                              FIG:VA9203X_dimsthbr

                                                  D

     Figure 3:    Spring return VA9203 actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
                    with optional M9000-561 Thermal Barrier installed dimensions, in. (mm)

Table 3: VA9203 actuated VG1241, VG1245, VG1841, and VG1845 Series NPT Ball Valve with optional
         thermal barrier installed dimensions, in. (mm)
 Valve size,              A              B                  C                 D               E                  F                                   G
 in. (DN)1
 1/2 (DN15)         6 (152)         21/32 (17)        1-7/32 (31)        6-31/32 (177)   2-33/64 (64)        11/32 (9)     1-1/4 (32)
 3/4 (DN20)         6 (152)         21/32 (17)        1-7/32 (31)        7-1/8 (181)     2-51/64 (71)        11/32 (9)     1-13/32 (36)
 1 (DN25)           6-1/16 (154)    3/4 (19)          1-19/64 (33)       7-31/64 (190)   3-13/32 (87)        11/32 (9)     1-45/64 (43)

1.    Port A must always be connected to the coil.

          VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                                             3
                                                                                               Instructions
Accessories
Table 4: Accessories (order separately)
 Code number        Description
 M9000-560          Ball valve linkage kit for applying M9203 and M9208 Series Actuators to VG1000 Series Valves (quantity
                    1)
 M9000-561          Thermal barrier extends M(VA)9104, M(VA)9203, M(VA)9208, and M(VA)9308/9310 Series Electric
                    Actuator applications to include low pressure steam (quantity 1)
 M9000-342          Weathershield kit for VG1000 Series Ball Valve application of VA9104, VA9203, VA9208, and VA9308/
                    9310 Series Electric Actuators (quantity 1)
 M9000-607          Position indicator for VG1000 Series Ball Valve applications (quantity 5)
 M9000-700          Universal ball valve linkage kit (quantity 1)

Mounting                                                                 3. Remove the linkage from Side A (Figure 5).
Mounting the actuator to spring return Port A
(Coil) open
To mount the actuator to spring return Port A (coil)
open:
1. Turn the valve stem to the position outlined in
   Figure 4.

                                                            FIG:VG1000

           2 Way                            3 Way

      Figure 4:    Positioning the valve stem                                                                         FIG:RMV_LNK

2. Mount optional M9000-561 Thermal Barrier to the                                 Figure 5:    Removing the linkage
   valve if fluid temperature exceeds 212°F (100°C).
   See the Mounting the thermal barrier section for                      4. Insert the drive shaft into Side B (Figure 6). The
   more information.                                                        drive shaft is keyed for one-way assembly. With
                                                                            gentle pressure applied, rotate the drive shaft until
Note: Proceed to Step 7 if the ball valve linkage is on
                                                                            the key aligns and the drive shaft falls into place.
actuator Side B.

                                                                                                                                    FIG:DRV_SHFT

                                                                                  Figure 6:    Inserting the drive shaft

4     VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
      Instructions
5. Install linkage base on Side B using the two                            7. Install the actuator on the ball valve (Figure 9).
   #8-32 x 0.625 in. long screws (Figure 7). The                              Tighten the actuator mounting screw to a torque of
   recommended torque is 29 to 33 lb·in.                                      10 to 12 lb·in. (1.1 to 1.4 N·m) and snap the large
   (3.3 to 3.7 N·m).                                                          adjustable pointer into place.

                                                           FIG: INST_LNK                                                FIG:MNT_ACT

         Figure 7:     Installing the linkage
                                                                                      Figure 9:    Mount the actuator
6. Insert fixed pointer and M4x0.7x83 mm long screw
   into the Side A actuator hub (Figure 8). Direct the                     Mounting the actuator to spring return Port A
   arrow on the pointer to 100%.                                           (coil) closed
                                                                           To mount the actuator to spring return port A (coil)
                                                                           closed:
                                                                           1. Turn the valve stem to the position outlined in
                                                                              Figure 10.

                                                                                                                                      FIG:VG1000sdB
                                                                                       2 Way                  3 Way

                                                FIG:FXPT
                                                                                  Figure 10: Positioning the valve stem
                                                                           2. Mount optional M9000-561 Thermal Barrier to the
           Figure 8:    Installing the fixed                                  valve if fluid temperature exceeds 212°F (100°C).
                        pointer                                               See the Mounting the thermal barrier section for
                                                                              more information.
                                                                           Note: Proceed to Step 7 if the ball valve linkage is on
                                                                           actuator Side A.

       VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                                             5
                                                                                            Instructions
3. Remove the linkage from Side B (Figure 13).                                 5. Install linkage base on Side A using the two
                                                                                  #8-32 x 0.625 in. long screws (Figure 13). The
                                                                                  recommended torque is 29 to 33 lb·in.
                                                                                  (3.3 to 3.7 N·m).

                                               FIG:RMV_LNK_B

                                                                                                                                               FIG: INST_LNK
         Figure 11: Removing the linkage
                                                                                         Figure 13: Installing the linkage
4. Insert the drive shaft into Side A (Figure 12). The
   drive shaft is keyed for one-way assembly. With                             6. Insert fixed pointer and M4x0.7x83 mm long screw
   gentle pressure applied, rotate the drive shaft until                          into the Side B actuator hub (Figure 14). Direct the
   the key aligns and the drive shaft falls into place.                           arrow on the pointer to 0%.

                                                               FIG:DRV_SHFTA

        Figure 12: Inserting the drive shaft

                                                                                                                             FIG:INST_FXPT_B

                                                                                     Figure 14: Installing the fixed pointer

6     VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
      Instructions
7. Install the actuator on the ball valve (Figure 15).
   Tighten the actuator mounting screw to a torque of
   10 to 12 lb·in. (1.1 to 1.4 N·m) and snap the large
   adjustable pointer into place.

                                               FIG:MNT_ACT_B

           Figure 15: Mount the actuator

       VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation   7
                                                                                            Instructions
Mounting the thermal barrier                               2. Rotate the drive shaft to align marks on the top of
Figure 16 shows the optional M9000-561 Thermal                the thermal drive shaft with matching marks on the
Barrier.                                                      valve stem.
                       Machine Screws                      3. Mount the thermal barrier onto the valve using the
                                                              four included M5x16 mm machine screws and four
                                                              M5 flange nuts. Tighten the screws to a
                                                              recommended torque of 21 to 25 lb·in.
                                                              (2.4 to 2.8 N·m) (Figure 18).

                                     Flange
                                      Nuts
     Barrier

                                        Drive
                                        Shaft

    Figure 16: Optional M9000-561 Thermal Barrier

To mount the optional thermal barrier:
1. Install the thermal barrier drive shaft into the
   thermal barrier by aligning the tab on the drive
                                                                                                    FIG:in_act
   shaft with the slot on the thermal barrier
   (Figure 17).

                                                                     Figure 18: Installing the barrier

                                                           4. Proceed to actuator mounting instructions. Follow
                                                              the same steps as mounting directly to the valve
                                                              when mounting the actuator to the thermal barrier.

               Figure 17: Installing the Drive
               Shaft into the Thermal Barrier

8       VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
        Instructions
Wiring                                                                                            5.0 (2.9) A 240 V ~

See Figure 19 and Figure 20 to wire the applicable                                                        21 S1
                                                                                                   23
VA9203-AGx-2Z Series model.
                                                                                                   22
                  Floating Control, Four Wire                                                             21
                                 RA RA                                                             BLK/ BLK/ BLK/
                                DA   DA                                                            RED BLU GRY
                    BLK     RED GRY ORN
                                                                                                    21   22   23
                     1       2   3   4

                                                                                                 COM NC NO

                             ~          24 VAC
                      -      +          24 VDC

                Open/Close, Single Wire Control                                                  Figure 20: Auxiliary
                                 RA RA                                                          switch wiring diagram
                                DA   DA
                    BLK     RED GRY ORN
                     1       2   3   4
                                                                                            WARNING: Risk of Electric Shock.

                                                                                        !   Disconnect or isolate all power supplies
                                                                                            before making electrical connections.
                                                                                            More than one disconnection or isolation
                                                                                            may be required to completely
                             ~          24 VAC                                              de-energize equipment. Contact with
                     -       +         24 VDC
                                                                                            components carrying hazardous voltage
                   On/Off Control, Two Wire
                                                                                            can cause electric shock and may result
                                 RA RA
                                                                                            in severe personal injury or death.
                                DA   DA
                    BLK     RED GRY ORN                                                     AVERTISSEMENT : Risque de
                     1       2   3   4                                                      décharge électrique.
                                                                                            Débrancher ou isoler toute alimentation
                                                                                            avant de réaliser un raccordement
                                                                                            électrique. Plusieurs isolations et
                                                                                            débranchements sont peut-être
                                                                                            nécessaires pour -couper entièrement
                                   ~         24 VAC                                         l'alimentation de l'équipement. Tout
                      -            +         24 VDC
                                                                                            contact avec des composants porteurs
                                                                                            de tensions dangereuses risque
   Floating Control, Multiple Actuators with One Transformer                                d'entraîner une décharge électrique et de
                RA RA                              RA RA                                    provoquer des blessures graves, voire
               DA   DA                            DA   DA                                   mortelles.
    BLK    RED GRY ORN                 BLK    RED GRY ORN
     1      2   3   4                   1      2   3   4

                                                               FIG:M92xx-AGx_cntrlwir

            ~             24 VAC
      -     +             24 VDC

          Figure 19: Control wiring diagrams

          VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                            9
                                                                                               Instructions
            CAUTION: Risk of Property Damage.
                                                         Using conduit

     !      Do not apply power to the system before      All VA9203 Series Actuators accept 1/2 in. threaded
            checking all wiring connections. Short       electrician’s fittings.(Figure 21).
            circuited or improperly connected wires
            may result in permanent damage to the
            equipment.
            MISE EN GARDE : Risque de dégâts
            matériels.
            Ne pas mettre le système sous tension
            avant d'avoir vérifié tous les raccords de
            câblage. Des fils formant un court-circuit
            ou connectés de façon incorrecte
            risquent d'endommager
            irrémédiablement l'équipement.
                                                               Figure 21: Adding flexible metal conduit
            CAUTION: Risk of Property Damage.

     !      Insulate and secure each unused wire
            lead before applying power to the
                                                         1. Feed the actuator cables through the field supplied
                                                            electrician’s fitting and conduit.
            actuator. Failure to insulate and secure     2. Thread the electrician’s fitting into the actuator and
            each unused wire lead may result in             secure the conduit to the fitting in accordance with
            property damage.                                local building code requirements.
            MISE EN GARDE : Risque de dégâts
            matériels.
                                                         Setup and adjustments
            Isoler et protéger chaque fil non utilisé    Mode selection switch
            avant de mettre l'actuator sous tension.     Actuators have an external mode selection switch to
            Le non-respect de cette obligation           reverse control logic. The switch is accessible from
            d'isolation et de protection de chaque fil   both A and B sides of the actuator as illustrated in
            non utilisé risque d'entraîner des dégâts    Figure 22. Actuators are delivered in Direct Acting (DA)
            matériels.                                   mode and can be switched by the user to Reverse
                                                         Acting (RA) mode.
 IMPORTANT: Make all wiring connections in
 accordance with the National Electrical Code and
 local regulations. Use proper Electrostatic Discharge              DA          RA       RA          DA
                                                                                                             FIG:modsel
 (ESD) precautions during installation and servicing
                                                                   Side A of Actuator   Side B of Actuator
 to avoid damaging the electronic circuits of the
 actuator.                                                               Figure 22: Mode selection

10    VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
      Instructions
Control response                                                                      The switch point is continuously adjustable throughout
The installation side of the actuator and the position of                             the actuator’s rotation range. For the most accurate
the mode selection switch combine to determine                                        switch positioning, see Figure 24 and use the method
control response from the actuator. See Figure 23.                                    in the following example. To change the switch point of
                                                                                      auxiliary switch, proceed as follows:
                                Installation Side
                                                                                      1. Position the actuator in the full spring return
                                                                                         position.
                                                                                          Note: The switch is factory set to trip when the
                                                                                          actuator reaches the 10% position.
                                                                                      2. Rotate the switch adjuster until it points to the
      Control Inputs          Mode Selection Switch                                      desired switch point.
    GRY        ORN
                                                                                      3. Connect the auxiliary switch to a power source or
     3          4
                                                                                         an ohmmeter and apply power to the actuator. The
                                                                                         actuator moves to the fully open position and holds
                                                                                         while power is applied.

                                                            FIG:VA92xxAGx_CtrlRspns
                                                                                      4. Observe the switch point. If required, repeat Step 1
                                                                                         through Step 3.

             Figure 23: Control response

Auxiliary switch (VA9203-xxB-xx models)
The VA9203-xxB-xx models include one integral
auxiliary switch with a switch adjuster accessible on
either face of the actuator (Figure 24). The factory
setting for the auxiliary switch is 10% closing (relative
to the 0 to 100% rotation range as printed on the
product label). See the Technical specifications table                                       Figure 24: Switch trip point settings
for the auxiliary switch ratings.
                                                                                      Repair information
              WARNING: Risk of Electric Shock and

     !        Property Damage.                                                        A number of replacement parts are available; see
              Insulate and secure each unused wire                                    Table 4 for more details. If an VA9203 Series Electric
              lead before applying power to the                                       Spring Return Actuator fails to operate within its
              actuator. Failure to insulate and secure                                specifications, replace the unit. For a replacement
              each unused wire lead may result in                                     electric actuator, contact the nearest
              property damage, electric shock, and                                    Johnson Controls® representative.
              severe personal injury or death.
              AVERTISSEMENT : Risque de
              décharge électrique et dégâts
              matériels.
              Isoler et protéger chaque fil non utilisé
              avant de mettre l'actuator sous tension.
              Le non-respect de cette obligation
              d'isolation et de protection de chaque fil
              non utilisé risque d'entraîner des dégâts
              matériels, des décharges électriques et
              des blessures graves, voire mortelles.

          VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                                 11
                                                                                               Instructions
Technical specifications
VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Actuators (Part 1 of 2 )
Power requirements                       AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety
                                         Extra-Low Voltage (SELV) (Europe), 5.1 VA running, 2.8 VA holding position
                                         DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe)
                                         1.9 W running, 1.1 W holding
                                         Holding position minimum transformer size: 6 VA per actuator
Input signal/adjustments                 AC 19.2 to 28.8 V at 50/60 Hz or DC 24 V +20%/-10%
                                         Class 2 (North America) or SELV (Europe)
                                         Minimum pulse width: 500 msec
Control input impedance                  4,700 ohm control inputs
Auxiliary switch    -xxB models          One Single-Pole, Double-Throw (SPDT), double-insulated switch with silver
rating                                   contacts:
                                         AC 24 V, 50 VA pilot duty
                                         AC 120 V, 5.8 A resistive, 1/4 hp, 275 VA pilot duty
                                         AC 240 V, 5.0 A resistive, 1/4 hp, 275 VA pilot duty
Spring return                            Direction is selectable with mounting position of actuator:
                                         Actuator face labeled A is away from valve: CCW spring return
                                         Actuator face labeled B is away from valve: CW spring return
Rated torque        Power on             27 lb·in. (3 N·m) all operating temperatures
                    (running)
                    Power off            27 lb·in. (3 N·m) all operating temperatures
                    (spring returning)
Rotation range                           Maximum full stroke: 95°
Rotation time for   Power on             90 seconds constant for 0 to 27 lb·in. (3 N·m) load, at all operating conditions
90 degrees of       (running)
travel
                    Power off            12 to 17 seconds for 0 to 27 lb·in. (3 N·m) load, at room temperature
                    (spring returning)   16 seconds nominal at full rated load
                                         22 seconds maximum with 27 lb·in. (3 N·m) load, at -22°F (-30°C)
Life cycles                              60,000 full stroke cycles with 27 lb·in. (3 N·m) load
                                         1,500,000 repositions with 27 lb·in. (3 N·m) load
Audible noise       Power on             <37 dBA at 27 lb·in. (3 N·m) load, at a distance of 39-13/32 in. (1 m)
rating              (running)
                    Power on             <20 dBA at a distance of 39-13/32 in. (1 m)
                    (holding)
                    Power off            <56 dBA at 27 lb·in. (3 N·m) load, at a distance of 39-13/32 in. (1 m)
                    (spring returning)
Electrical          AGA-2Z models        36 in. (0.9 m) UL 444 Type CMP plenum rated cable with 19 AWG (0.75 mm2)
connections                              conductors and 1/4 in. (6 mm) ferrule ends
                    AGB-2Z models        48 in. (1.2 m) UL 758 Type AWM halogen free cable with 18 AWG (0.85 mm2)
                                         conductors and 1/4 in. (6 mm) ferrule ends
Conduit connections                      Integral 1/2 in. (13 mm) threaded conduit connectors
Fluid               VG12x1 and VG18x1    23 to 203°F (-5 to 95°C), not rated for steam service
temperature         Series
limits
                    VG12x5 and VG18x5    -22 to 212°F (-30 to 100°C), not rated for steam service
                    Series
                    VG12x5 and VG18x5    -22 to 284°F (-30 to 140°C) water; 15 psig (103 kPa) at 250°F (121°C)
                    Series with          saturated steam
                    M9000-561 Thermal
                    Barrier Installed

12   VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation
     Instructions
VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Actuators (Part 2 of 2 )
 Ambient                  Standard operating          -22 to 140°F (-30 to 60°C); 90% RH maximum, noncondensing
 conditions
                          Storage                     -40 to 185°F (-40 to 85°C); 95% RH maximum, noncondensing
 Enclosure rating                                     NEMA 2 (IP54) for all mounting directions
 Compliance               United States               UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1,
                                                      Automatic Electrical Controls for Household and Similar Use; and
                                                      UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for Electric
                                                      Actuators
                                                      Plenum Rated (UL 2043). Suitable for use in other environmental air space
                                                      (plenums) in accordance with Section 300.22 (C) of the National Electric Code
                          Canada                      UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002,
                                                      3rd Ed., Automatic Electrical Controls for Household and Similar Use; and
                                                      CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment
                          Europe                      CE Mark – Johnson Controls declares that this product is in compliance with
                                                      the essential requirements and other relevant provisions of the EMC Directive
                                                      and the Low Voltage Directive.
                          Australia and New           RCM Mark, Australia/NZ Emissions Compliant
                          Zealand
 Shipping weight          -AGA models                 2.0 lb (0.9 kg)
                          -AGB models                 2.4 lb (1.1 kg)
UK Single Point of Contact:   European Single Point of Contact: NA/SA Single Point of Contact:      APAC Single Point of Contact:
JOHNSON CONTROLS        JOHNSON CONTROLS                        JOHNSON CONTROLS                    JOHNSON CONTROLS
TYCO PARK GRIMSHAW LANE VOLTAWEG 20                             5757 N GREEN BAY AVE                C/O CONTROLS PRODUCT MANAGEMENT
MANCHESTER M40 2WL      6101 XK ECHT                            GLENDALE WI 53209                   NO. 32 CHANGJIANG NEW DISTRICT
UNITED KINGDOM          THE NETHERLANDS                         USA                                 WUXI JIANGSU PROVINCE 214028
                                                                                                    CHINA

                                                                                                       Building Technologies & Solutions
                                                                                                 5757 N Green Bay Ave, Glendale, WI 53209
                                                   Metasys® and Johnson Controls® are registered trademarks of Johnson Controls
                                          All other marks herein are the marks of their respective owners. © 2022 Johnson Controls

          VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation                             13
                                                                                               Instructions
Published in U.S.A.                                                                                            www.johnsoncontrols.com