T600MSx-3 Multi-Stage Thermostat
Installation Instructions
T600MSN-3, T600MSP-3                                                               Part No. 24-9890-617, Rev. A
                                                                                              Issued June 30, 2014

Applications                                              North American Emissions Compliance
The T600MSN-3 non-programmable and T600MSP-3              United States
programmable thermostats are specifically designed
for control of multi-stage commercial heating and             This equipment has been tested and found to
cooling equipment.                                            comply with the limits for a Class A digital device
                                                              pursuant to Part 15 of the FCC Rules. These limits
 IMPORTANT: The T600MSx-3 Thermostat is                       are designed to provide reasonable protection
 intended to provide an input to equipment under              against harmful interference when this equipment is
 normal operating conditions. Where failure or                operated in a commercial environment. This
 malfunction of the thermostat could lead to personal         equipment generates, uses, and can radiate radio
 injury or property damage to the controlled                  frequency energy and, if not installed and used in
 equipment or other property, additional precautions          accordance with the instruction manual, may cause
 must be designed into the control system.                    harmful interference to radio communications.
 Incorporate and maintain other devices, such as              Operation of this equipment in a residential area is
 supervisory or alarm systems or safety or limit              likely to cause harmful interference, in which case
 controls, intended to warn of or protect against             the user will be required to correct the interference
 failure or malfunction of the thermostat.                    at his/her own expense.
 IMPORTANT: Le T600MSx-3 Thermostat est
 destiné à transmettre des données entrantes à un         Canada
 équipement dans des conditions normales de
                                                              This Class (A) digital apparatus meets all the
 fonctionnement. Lorsqu'une défaillance ou un
                                                              requirements of the Canadian Interference-Causing
 dysfonctionnement du thermostat risque de
                                                              Equipment Regulations.
 provoquer des blessures ou d'endommager
 l'équipement contrôlé ou un autre équipement, la             Cet appareil numérique de la Classe (A) respecte
 conception du système de contrôle doit intégrer des          toutes les exigences du Règlement sur le matériel
 dispositifs de protection supplémentaires. Veiller           brouilleur du Canada.
 dans ce cas à intégrer de façon permanente
 d'autres dispositifs, tels que des systèmes de           Installation
 supervision ou d'alarme, ou des dispositifs de
                                                          Location Considerations
 sécurité ou de limitation, ayant une fonction
 d'avertissement ou de protection en cas de               Locate the T600MSx-3 thermostat:
 défaillance ou de dysfonctionnement du thermostat.       •     on a partitioning wall, approximately 5 ft (1.5 m)
                                                                above the floor in a location of average
                                                                temperature
                                                          •     away from direct sunlight, radiant heat, outside
                                                                walls, behind doors, air discharge grills, stairwells,
                                                                or outside doors
                                                          •     away from steam or water pipes, warm air stacks,
                                                                unconditioned areas (not heated or cooled), or
                                                                sources of electrical interference
                                                          Note: Allow for vertical air circulation to the
                                                          T600MSx-3 thermostat.

                                                T600MSx-3 Multi-Stage Thermostat Installation Instructions            1
To install the thermostat:                                                     Note: Be sure to position the thermostat mounting
                                                                               base so that the arrow on the base points upward to
1. Use a Phillips-head screwdriver to remove the
                                                                               indicate the top of the thermostat.
   security screw on the bottom of the thermostat
   cover.                                                                      6. Drill a 3/16 in. (5 mm) hole at each of the two
                                                                                  marked locations and tap nylon anchors (included
2. Pull the bottom edge of the thermostat cover and
                                                                                  with the thermostat) flush to the wall surface.
   open the thermostat as illustrated in Figure 1.
                                                                               7. Position the thermostat mounting base on the wall
                                                                                  and use the two mounting screws (included with
                                                                                  the thermostat) to secure the base to the surface
                                                                                  as illustrated in Figure 3.
                                                                               Note: Be careful not to overtighten the mounting
                                                                               screws.

                                           FIG:cvr_rmvl

                                                                                                                                        FIG:mntng_bs
     Figure 1: Removing the Thermostat Cover

3. Carefully pull the locking tabs on the right side of
   the thermostat mounting base and unlock the                                          Figure 3: Securing the Thermostat
   Printed Circuit Board (PCB). Open the PCB to the                                         Mounting Base to the Wall
   left as illustrated in Figure 2.
                                                                               8. Swing the PCB back to the right and carefully snap
                                                                                  it into the locking tabs on the thermostat mounting
                                                                                  base.
                                                                               9. Pull the pull-tabs on each of the connectors and
                                                                                  remove the screw terminal blocks as illustrated in
                                          PCB
                                          Locking                                 Figure 4.
                                          Tabs

                                                          FIG:prntd_crct_brd

       Figure 2: Opening the Thermostat PCB

4. Pull approximately 6 in. (152 mm) of wire from the
   wall and insert the wire through the hole in the
   thermostat mounting base.
                                                                                                                      FIG:trmnl_blcks
5. Align the thermostat mounting base on the wall and
   use the base as a template to mark the two
   mounting hole locations.
                                                                                 Figure 4: Removing the Screw Terminal Blocks

2     T600MSx-3 Multi-Stage Thermostat Installation Instructions
Wiring                                                            IMPORTANT: Make all wiring connections in
When an existing thermostat is replaced, remove and               accordance with local, national, and regional
label the wires to identify the terminal functions. When          regulations. Do not exceed the electrical ratings of
a T600MSx-3 thermostat is replaced, simply remove                 the T600MSx-3 thermostat.
the old screw terminal blocks and reinsert them onto
the PCB of the replacement thermostat.                           To wire the thermostat:
                                                                 1. Strip the ends of each wire a 1/4 in. (6 mm) and
            CAUTION: Risk of Electric Shock.                        connect them to the appropriate screw terminals as
            Disconnect the power supply before
     !      making electrical connections to avoid
                                                                    indicated in Figure 5.
                                                                 2. Carefully push any excess wire back into the wall.
            electric shock.
                                                                    Seal the hole in the wall with fireproof material to
            MISE EN GARDE : Risque de décharge                      prevent drafts from affecting the ambient
            électrique.                                             temperature readings.
            Débrancher l'alimentation avant de
            réaliser tout raccordement électrique afin           3. Reinsert the screw terminal blocks onto the PCB.
            d'éviter tout risque de décharge                     4. Reattach the thermostat cover to the mounting
            électrique.                                             base (top side first).
                                                                 Note: Use a Phillips-head screwdriver to reinstall the
            CAUTION: Risk of Property Damage.
                                                                 security screw on the bottom of the thermostat cover.
            Do not apply power to the system before
     !      checking all wiring connections. Short
                                                                                                            3 pole right top
            circuited or improperly connected wires                        5 pole left top connector        connector
            may result in permanent damage to the
                                                                               Y2    Y1     G     RC    C      RH    W1 W2
            equipment.
            MISE EN GARDE : Risque de dégâts                                    1     2     3     4     5      6      7       8
            matériels.
            Ne pas mettre le système sous tension
            avant d'avoir vérifié tous les raccords de                     7 pole bottom connector

                                                                                                                                                    FIG:T600MSx_trmblk
            câblage. Des fils formant un court-circuit                               AUX D1       D2   RS   Scom    OS MS
            ou connectés de façon incorrecte
            risquent d'endommager                                                    10     11    12 13      14     15     16
            irrémédiablement l'équipement.                                           Figure 5: Terminal Blocks

                                                                                          Isolated Contact
                                                                                          - Lighting
                                                                                          - On/Off Actuation
                                                                                          - Exhaust Fan

             Y2       Y1      G     RC    C     RH     W1      W2         AUX         D1     D2        RS   Scom      OS

                                                      Heat 1 Heat 2
                                                                               Aux
            Cool 2   Cool 1   Fan

                                                                                                  Remote            Remote
                                              If using the same power source                       Room             Outdoor
                         24 VAC

                                                                                                                                  FIG:T600MSx_wir
                                              for the thermostat and heating                      Sensor            Sensor
                     Thermostat Power
                                              loads, install a jumper
                                              across RC and RH.

                                    Figure 6: Wiring the T600MSx-3 Thermostats

                                                     T600MSx-3 Multi-Stage Thermostat Installation Instructions                                                          3
                                                                         •   Use the YES/SCROLL key to:
Table 1: Terminal Identification (See Figure 5.)                             -   confirm menu selections and to advance to the
 Number       Label     Function                                                 next menu item
 1            Y2        Energizes on a call for second-stage                 -   stop the Status Display Menu from scrolling
                        cooling.                                                 and to manually scroll to the next parameter on
 2            Y1        Energizes on a call for first-stage                      the menu
                        cooling.
                                                                         Note: When the thermostat is left unattended for
 3            G         Energizes fan in accordance with
                                                                         45 seconds, the thermostat display resumes scrolling.
                        selected fan mode.
 4            RC        24 VAC from equipment transformer                •   Use the NO key to decline a parameter change and
                                                                             to advance to the next menu item.
 5            C         24 VAC (Common) from equipment
                        transformer                                      •   Use the MENU key to:
 6            RH        24 VAC for heating stage
                                                                             -   access the Main User Menu or exit the menu
 7            W1        Energizes on a call for first-stage
                        heating.                                             -   access the Installer Configuration Menu or to
 8            W2        Energizes on a call for second-stage                     exit the menu (See the Configuring the
                        heating.                                                 T600MSx-3 Thermostat Thermostat section.)
 10           Aux       Auxiliary output                                 •   Use the UP/DOWN arrow keys to change the
 11           DI1       Configurable Digital Input 1                         configuration parameters and to activate a setpoint
                                                                             adjustment.
 12           DI2       Configurable Digital Input 2
 13           RS        Remote Room Temperature Sensor                   Backlit Liquid Crystal Display (LCD)
 14           Scom      Sensor Common                                    The T600MSx-3 thermostat includes a 2-line,
                                                                         8-character backlit display. Low-level backlighting is
 15           OS        Outdoor Air Sensor
                                                                         present during normal operation, and it brightens when
 16           MS        Not Used                                         any user interface key is pressed. The backlight returns
                                                                         to low level when the thermostat is left unattended for
Setup and Adjustments                                                    45 seconds.
Thermostat Operation Overview                                            Light-Emitting Diodes (LEDs)
                                                                         Three LEDs are included to indicate the fan status, call
                                                                         for heat, or call for cooling:
                                                                         •   The FAN LED is on when the fan is on.
                                                                         •   The HEAT LED is on when heating is on.
                                                                         •   The COOL LED is on when cooling is on.

        Backlit, plain text
                                                                         Programming Overview
      LCD is easy to read                                                There are three menus used to view, program, and
        in any condition.                  Room Temp
                                           70.0ºF                        configure the T600MSx-3 thermostat:
           LEDs indicate
           system activity.
                                                                         The Status Display Menu is displayed during normal
                                     YES   NO
                                                                         thermostat operation. This menu continuously scrolls
                                                                         through the following parameters:
                                                                         •   Room Temperature
                                                         FIG:T600_frnt
          Five keys on the thermostat
          make operation easy and intuitive.                             •   Day and Time (T600MSP-3)
         Figure 7: Front Cover of Thermostat                             •   System Mode
                                                                         •   Occupancy Status – Occupied/Unoccupied/
Thermostat User Interface Keys                                               Override (T600MSP-3)
The T600MSx-3 thermostat user interface consists of
                                                                         •   Outdoor Temperature – An outdoor air temperature
five keys on the front cover (as illustrated in Figure 7).
                                                                             sensor must be connected.
The function of each key is as follows:

4     T600MSx-3 Multi-Stage Thermostat Installation Instructions
•     Applicable Alarms – The backlight lights up as an           2. Once the Installer Configuration Menu begins,
      alarm condition is displayed.                                  press the NO key to scroll through the parameters
                                                                     listed in Table 2.
Note: Press the YES/SCROLL key to temporarily stop
this menu from scrolling.                                         3. When the desired parameter is displayed, use the
                                                                     YES key to choose the desired selection option.
The Main User Menu is used to access and change
the basic operating parameters of the thermostat.                 4. Press the YES key and then the NO key to
Access this menu by pressing the MENU key during                     continue scrolling through the parameters.
normal thermostat operation.                                      To exit the Installer Configuration Menu any time, press
The Installer Configuration Menu is used to set up                the MENU key, and at the exit prompt, press the YES
the thermostat for application-specific operation. To             key. To pass over a parameter without changing it,
access this menu, press and hold the MENU key for                 press the NO key.
approximately 8 seconds.                                          When the thermostat is in the Installer Configuration
Configuring the T600MSx-3 Thermostat                              Menu and left unattended for approximately 8 seconds,
                                                                  the thermostat reverts to the Status Display Menu.
The T600MSx-3 thermostat comes from the factory
with default settings for all configurable parameters.            Configuring Inputs DI1 and DI2
The default settings are shown in Table 2. To                     When DI1 and DI2 are configured for an alarm
reconfigure the parameters via the thermostat, follow             condition, an alarm condition is displayed locally when
the steps in this section.                                        the input is closed. An alarm message is included on
1. To access the Installer Configuration Menu, press              the scrolling Status Display Menu and when the
   and hold the MENU key for approximately                        message is displayed, the backlight momentarily
   8 seconds.                                                     lights up.
                                                                  Each input can be configured to the Selection Options
                                                                  included in Table 2.
Table 2: Installer Configuration Menu (Part 1 of 4)
    Parameter      Description and Default                Selection Options
    Appearing
    on Display
    DI11           Configuration of Digital Input 1.      (None): No function is associated with an input.
                   Default: None                          (Service): A Service alarm is displayed on the thermostat when the
                                                          input is energized. This input can be tied into the air conditioning unit
                                                          control card, which provides an alarm should there be a malfunction.
                                                          (Filter): A Filter alarm is displayed. This alarm can be connected to
                                                          a differential pressure switch that monitors a filter.
                                                          (RemOVR): Temporary occupancy request via a remote input. This
                                                          override function is controlled by a manual remote occupancy
                                                          override. When enabled, this condition disables the override
                                                          capability of the thermostat.
                                                          (RemNSB): Remote Night Setback (NSB) via a time clock input, an
                                                          occupancy sensor, or from a voltage-free contact.
                                                          Contact open = Occupied; contact closed = Unoccupied.
    DI21           Configuration of Digital Input 2.      (None): No function is associated with an input.
                   Default: None                          (Service): A Service alarm is displayed on the thermostat when the
                                                          input is energized. This input can be tied into the air conditioning unit
                                                          control card, which provides an alarm should there be a malfunction.
                                                          (Filter): A Filter alarm is displayed. This alarm can be connected to
                                                          a differential pressure switch that monitors a filter.
                                                          (RemOVR): Temporary occupancy request via a remote input. This
                                                          override function is controlled by a manual remote occupancy
                                                          override. When enabled, this condition disables the override
                                                          capability of the thermostat.
                                                          (RemNSB): Remote Night Setback (NSB) via a time clock input, an
                                                          occupancy sensor, or from a voltage-free contact.
                                                          Contact open = Occupied; contact closed = Unoccupied.

                                                       T600MSx-3 Multi-Stage Thermostat Installation Instructions                 5
Table 2: Installer Configuration Menu (Part 2 of 4)
 Parameter      Description and Default                 Selection Options
 Appearing
 on Display
 Lockout        Selectable Lockout Levels for           Function                              Lockout Level
                limiting end-user keypad interaction.
                                                                                 (0)            (1)                (2)
                Default: 0
                                                        Occupancy            Access         Access         No Access
                                                        Override
                                                        Permanent            Access         No Access      No Access
                                                        Temperature
                                                        Setpoints
                                                        Temporary            Access         Access         No Access
                                                        Temperature
                                                        Setpoints
                                                        System Mode          Access         No Access      No Access
                                                        Setting
                                                        Fan Mode Setting     Access         No Access      No Access
                                                        Schedule             Access         No Access      No Access
                                                        Setting4
                                                        Clock Setting4       Access         Access         Access

                                                        Permanent Hold4      Access         No Access      No Access

 Pwr del2       Sets the delay time period at           Range: 10.0 to 120.0 sec
                thermostat power up, or at each
                time power is removed and
                reapplied, before any operation
                (fan, heating, or cooling) is
                authorized. Also can be used to
                sequence the startup of multiple
                units in one location.
                Default: 10.0 sec
 Frost pr       Provides a minimum heating              (on): Enabled
                setpoint of 42.0°F/5.5°C to prevent     (off): Disabled
                freezing in the zone controlled by
                the thermostat.
                Default: off
 Heat max3      Sets the Occupied and Unoccupied        Range: 40.0°F/4.5°C to 90.0°F/32.0°C
                maximum Heating setpoint values.
                Default: 90.0°F/32.0°C
 Cool min3      Sets the Occupied and Unoccupied        Range: 54.0°F/12.0°C to 100.0°F/37.5°C
                minimum Cooling setpoint values.
                Default: 54.0°F/12.0°C
 Anticycl       Anti-Short Cycle timer sets the         Range: 0.0 to 5.0 min adjustable in 1-minute increments
                minimum on/off times for heating        Set the anti-short cycle timer to 0.0 min for equipment that already
                and cooling stages.                     has its own anti-short cycle timer.
                Default: 2.0 min
 Heat cph       Sets the maximum number of              Range: 3.0 to 8.0 cycles per hour
                Heating cycles per hour.
                Default: 4.0
 Cool cph       Sets the maximum number of              Range: 3.0 or 4.0 cycles per hour
                Cooling cycles per hour.
                Default: 4.0

6     T600MSx-3 Multi-Stage Thermostat Installation Instructions
Table 2: Installer Configuration Menu (Part 3 of 4)
 Parameter     Description and Default                Selection Options
 Appearing
 on Display
 Deadband      Sets the minimum deadband              Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C°
               between the heating and cooling        increments
               setpoints.
               Default: 2.0F°/1.0C°
 Fan cont      Determines how the fan is activated    (off): The thermostat will not activate the fan in response to a call for
               in response to a call for heating.     heating. The fan is activated by the equipment fan and limit control.
               Fan cont applies to W1 & W2 and        (on): Enables the thermostat to activate the fan in response to a call
               Fan Mode auto only. Fan cont           for heating or cooling.
               does not affect fan operation on a
               call for cooling (Y1 & Y2).
               Default: on
 Fan del       Fan delay extends fan operation        (on): Extends fan operation by 60 seconds after a heating or cooling
               after a heating or cooling cycle has   cycle has ended.
               ended.                                 (off): No extension of fan operation after a heating or cooling cycle
               Default off                            has ended.
                                                      The fan delay is only active when the fan is in the Auto mode.
 TOccTime      Sets the duration of the Temporary     Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
               Occupancy Time (when the
               thermostat is in the Unoccupied
               mode) when a Schedule Override
               Function is enabled using either the
               Main User Menu or DI1 or DI2
               configured as a temporary override
               remote contact (RemOVR).
               Sets the effective duration of the
               Temporary heating or cooling
               setpoints set using the up/down
               arrow keys.
               Default: 3.0 hrs
 Cal RS        Sets the desired room air              Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
               temperature sensor calibration         increments
               (offset). The offset can be added to
               or subtracted from the actual
               displayed room temperature.
               Default: 0.0F°/0.0C°C
 Cal OS        Sets the desired outdoor air           Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
               temperature sensor calibration         increments
               (offset). The offset can be added to
               or subtracted from the actual
               displayed room temperature.
               Default: 0.0F°/0.0C°
 H stage       Reverts the operation of a two-stage   (1.0): One Stage
               thermostat to a single-stage           (2.0): Two Stages
               thermostat when the second heating
               stage is not needed.
               Default: 2.0
 C stage       Reverts the operation of a two-stage   (1.0): One Stage
               thermostat to a single-stage           (2.0): Two Stages
               thermostat when the second cooling
               stage is not needed.
               Default: 2.0

                                                  T600MSx-3 Multi-Stage Thermostat Installation Instructions                      7
Table 2: Installer Configuration Menu (Part 4 of 4)
 Parameter        Description and Default                  Selection Options
 Appearing
 on Display
 H lock           Discontinues heating operation in        Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
                  response to the outdoor air
                  temperature. Requires that an
                  outdoor air temperature sensor be
                  installed and connected.
                  Default: 120°F/49°C
 C lock           Discontinues cooling operation in        Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
                  response to the outdoor air
                  temperature. Requires that an
                  outdoor air temperature sensor be
                  installed and connected.
                  Default: -40°F/-40°C
 2/4event4        Sets the number of events within a       (2.0): Two events (one occupied and one unoccupied) within a
                  24-hour period.                          24-hour period
                  Default: 2.0                             (4.0): Four events (two occupied and two unoccupied) within a
                                                           24-hour period
 Aux cont         Energizes peripheral devices             (n.c.): Contact open = Occupied; contact closed = Unoccupied
                  (lighting equipment, exhaust fans,       (n.o.): Contact closed = Occupied; contact open = Unoccupied
                  and economizers).                        The contact toggles with the internal Occupied/Unoccupied
                  Default: n.o.                            schedule (or the NSB contact on one of the digital inputs, if used).
 Prog rec4        Provides the desired occupied            (on): Enabled (provides the desired occupied temperature at the
                  temperature either at the start of the   start of the occupied schedule)
                  occupied schedule or after the           (off): Disabled (provides the desired occupied temperature after the
                  occupied schedule begins.                occupied schedule begins)
                  Note: Progressive recovery is
                  disabled if either DI1 or DI2 is
                  configured as remote NSB.
                  Default: off

1.   Setting DI1 or DI2 to RemNSB disables schedules and stops the Schedule menu display. Any other setting enables
     schedules and the Schedule menu. (T600MSP-3 only)
2.   When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
     hold the UP or DOWN arrow key to change the numeric value in increments of ten.
3.   When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F°/0.5C° increments; press
     and hold the UP or DOWN arrow key to change the value in 5.0F°/5.0C° increments.
4.   T600MSP-3 only

8      T600MSx-3 Multi-Stage Thermostat Installation Instructions
Operation                                                  Table 3: Programming the T600MSx-3 Thermostat
                                                                    (Part 2 of 2)
Programming/Operating the T600MSx-3
Thermostat                                                  Thermostat         Description
                                                            Display
Once the thermostat is configured via the Installer
Configuration Menu, its operating parameters can be                            Sets the Occupied and Unoccupied
                                                               Schedule        Time Periods
programmed via the Main User Menu. Access this
                                                               set? Y/N        See the Programming the Daily
menu by pressing the MENU key during normal                                    Schedule – Two-Event and
thermostat operation. The Main User Menu contains                              Programming the Daily Schedule –
the basic operating features of the thermostat.                                Four-Event sections.
The Main User Menu also uses Auto Help, which is                               Sets the Day and Time
displayed automatically in the menu when there is a            Clock           See the Setting the Day and Time
                                                               set? Y/N        section.
pause in programming activity. To exit Auto Help,
continue with the programming selection. When the
thermostat is in the Main User Menu and is left
unattended for 45 seconds, the menu reverts to the                             Sets a Permanent Hold on the
                                                               Schedule        Schedule or Resumes the Schedule
Status Display Menu.
                                                               hold? Y/N       See the Setting Schedule Hold
Follow the steps in Table 3 to program the thermostat.                         section.
Table 3: Programming the T600MSx-3 Thermostat
         (Part 1 of 2)
                                                           Note: Schedule Set and Clock Set are available on
 Thermostat         Description                            T600MSP-3 models only.
 Display
                    Press the MENU key while in the        Enabling Temporary Override Schedule
   RoomTemp         Status Display Menu to enter the       Note: The Override Schedule function is available in
   75.0 F          Main User Menu.                        T600MSN-3 models only when DI1 or DI2 is configured
                                                           as remote NSB.
                                                           Note: The Override Schedule prompt only appears
                    Overrides Unoccupied Setpoints
                                                           when in the Unoccupied (Unoccup) or Unoccupied
   Override         Only Appears if Thermostat is in
                                                           Hold (Unoccup hold) Mode.
   schd Y/N         Unoccupied State
                    See the Enabling Override Schedule     The override schedule prompt only appears when the
                    section.                               thermostat is in the unoccupied state. This menu
                    Cancels Override mode.                 selection gives the user the option of overriding the
   Cancel                                                  unoccupied setpoints with the occupied setpoints for
   ovrd Y/N                                                the amount of time specified under the TOccTime
                                                           parameter. See the Configuring the T600MSx-3
                                                           Thermostat section.
                    Sets the Temperature Setpoints
                                                           Note: If DI1 or DI2 is configured to operate as a
   Temperat         See the Entering Permanent
                                                           remote override contact, this menu is disabled.
   set? Y/N         Temperature Setpoints section.
                                                           To override the unoccupied state while in the Main User
                                                           Menu:
                    Selects the System Mode Default:
                                                           1. Press the NO key to all prompts until the Override
   Sys mode         Automatic (auto)
                                                              Schedule prompt appears. If the thermostat is in
   set? Y/N         See the Selecting the System Mode
                    section.                                  the unoccupied state, this is the first prompt.
                                                           2. Press the YES key to enable the temporary
                    Selects the Fan Mode Default:             override. The thermostat returns to the Status
   Fan mode         Automatic (auto) for T600MSN-3            Display Menu.
   set? Y/N         Smart (smart) for T600MSP-3
                                                           When scrolling through the Status Display Menu,
                    See the Selecting the Fan Mode
                    section.                               Override now appears for the schedule status
                                                           parameter.

                                                 T600MSx-3 Multi-Stage Thermostat Installation Instructions        9
Canceling the Temporary Override                            Table 4: Entering Permanent Temperature
The Cancel Override (Cancel ovrd) prompt only                        Setpoints
appears when the thermostat is in the unoccupied             Thermostat          Description
override mode.                                               Display
To resume the schedule while in the Main User Menu:                              Press the UP/DOWN arrow keys to
                                                               Heating           set the temperature. Press the YES
1. Press the NO key to all prompts until the Cancel            68.0F            key to store the value and advance to
   ovrd prompt appears. If the thermostat is in the                              the next menu.
   override state, this is the first prompt.
2. Press the YES key to resume the programmed                                    Press the YES key to change the
   schedule.                                                   Unocc CL          unoccupied cooling setpoint. Press
                                                               set? Y/N          the NO key to advance to the
The thermostat returns to the Status Display Menu.                               unoccupied heating setpoint.

Entering Permanent Temperature Setpoints
The first prompt appearing in the Main User Menu of                              Press the UP/DOWN arrow keys to
                                                               Unocc CL          set the temperature. Press the YES
the thermostat when in the occupied state is to set the                          key to store the value and advance to
permanent temperature setpoint.                                80.0F
                                                                                 the next menu.
To enter the permanent heating and cooling setpoints
for the Occupied and Unoccupied Modes, follow the                                Press the YES key to change the
steps in Table 4. When changing the temperatures,              Unocc HT          unoccupied heating setpoint. Press
press the keys once to change the temperature in               set? Y/N          the NO key to advance to the
0.5F°/0.5C° increments; press and hold down the keys                             temperature display units.
to change the temperature in 5.0F°/5.0C° increments.
Table 4: Entering Permanent Temperature                                          Press the UP/DOWN arrow keys to
         Setpoints                                             Unocc HT          set the temperature. Press the YES
                                                               62.0F            key to store the value and advance to
 Thermostat         Description                                                  the next menu.
 Display
                    Press the MENU key while in the                              Press the YES key to set the display
     RoomTemp       Status Display Menu to enter the                             units to °F or °C. Press the NO key to
                    Main User Menu.                            F/C
     75.0F                                                    set? Y/N
                                                                                 advance to the temperature setpoint
                                                                                 type menu.

                    Press the NO key to all prompts until                        Press the YES key to return to the
     Temperat       the temperature setpoint prompt                              Status Display Menu or press the NO
                    appears on the display (it may be the      Exit?
     set? Y/N                                                          Y/N       key to re-enter the temperature
                    first prompt). Press the YES key to                          setting menu.
                    enter the temperature setting menu.

                    Press the YES key to change the
     Cooling        occupied cooling setpoint. Press the    Entering Temporary Temperature Setpoints
     set? Y/N       NO key to advance to the occupied
                    heating setpoint menu.                  The temperature setpoints can be changed temporarily
                                                            for the occupied and unoccupied heating and cooling
                                                            modes. To temporarily change the setpoint, press the
                    Press the UP/DOWN arrow keys to         UP/DOWN arrow keys to change the temporary
     Cooling        set the temperature. Press the YES
                    key to store the value and advance to   setpoint for the current mode of operation.
     75.0F
                    the next menu.                          Note: Whether the thermostat is heating or cooling,
                                                            the respective setpoint will be temporarily adjusted. To
                    Press the YES key to change the         toggle between the temporary heating and cooling
     Heating        occupied heating setpoint. Press the    setpoints, press the NO key while changing the
     set? Y/N       NO key to advance to the unoccupied     temporary setpoints.
                    cooling setpoint menu.

10     T600MSx-3 Multi-Stage Thermostat Installation Instructions
Ending Temporary Temperature Setpoints                        Selecting the Fan Mode
The temporary setpoints remain in effect for the              The thermostat has three fan mode settings:
duration set in the TOccTime parameter or until
                                                              •   On Fan Mode (on): Energizes the fan all the time
manually released.
                                                                  for both occupied and unoccupied states, even if
Note: Setting TOccTime to 0.0 hrs prevents the                    the system mode is set to off.
temporary setpoints from taking effect.
                                                              •   Automatic Fan Mode (auto): Energizes the fan
To manually release the temporary setpoint, while in              only on a call for heating or cooling, for both
the Main User Menu:                                               occupied and unoccupied states. This is the default
                                                                  setting for T600MSN-3 thermostats.
1. Press the NO key to all prompts until the Temperat
   set prompt appears. If the thermostat is in the            •   Smart Fan Mode (smart): Energizes the fan all
   occupied state, this is the first prompt.                      the time for occupied states, and only on a call for
                                                                  heating or cooling in unoccupied states. This is the
2. Press the YES key to cancel all temporary                      default setting for T600MSP-3 thermostats.
   setpoints.
                                                              To select the fan mode while in the Main User Menu:
3. Press the MENU key again and press the YES key
   to exit the Main User Menu.                                1. Press the NO key to all prompts until the fan mode
                                                                 prompt appears on the display. Press the YES key
The setpoint reverts to the Permanent Temperature
                                                                 to set the fan mode.
Setpoint.
                                                              2. Press the UP/DOWN arrow keys to locate the
Selecting the System Mode                                        desired fan mode. Press the YES key to select the
The thermostat has four system modes:                            desired fan mode.
•   Automatic Mode (auto): Automatic changeover               3. Press the YES key to return to the Status Display
    between heating and cooling. This is the default             Menu or press the NO key to return to the fan
    setting.                                                     mode selection menu.
•   Cooling Mode (cool): Cooling operation only               Programming the Daily Schedule – Two-Event
•   Heating Mode (heat): Heating operation only               The schedule-setting menu is used to enter the
                                                              occupied or unoccupied states for each day of the
•   Off Mode (off): The thermostat is off; however,           week. The schedule-setting menu reflects either a
    when frost protection (Frost pr parameter) is             two- or a four-event schedule per day, based on what
    enabled, the thermostat still calls for heat if the       was selected in the 2/4event parameter during the
    temperature falls below 42°F/5.5°C.                       configuration process. If the schedule-setting menu
To set the system mode while in the Main User Menu:           does not reflect a two-event schedule, select two
                                                              events in the 2/4event parameter of the Installer
1. Press the NO key to all prompts until the system           Configuration Menu.
   mode prompt appears on the display. Press the
   YES key to select the desired system mode.                 When changing the time, press the UP/DOWN arrow
                                                              keys once to change the time in 1-minute increments;
2. Press the UP/DOWN arrow keys to locate the                 press and hold down the keys to change the time in
   desired system mode. Press the YES key to select           30-minute increments.
   the desired system mode.
                                                              Note: Programming one of the digital inputs to remote
3. Press the YES key to return to the Status Display
                                                              NSB disables the menu.
   Menu or press the NO key to return to the system
   mode selection menu.

                                                    T600MSx-3 Multi-Stage Thermostat Installation Instructions      11
To set the time schedule for a two-event schedule,           Table 5: Programming the Daily Schedule –
follow the steps in Table 5. See Table 7, Events 1                    Two-Event (Part 2 of 2)
and 2, for an example of a two-event office schedule.         Thermostat         Description
Table 5: Programming the Daily Schedule –                     Display
         Two-Event (Part 1 of 2)                                                 If the YES key was pressed, the next
 Thermostat         Description                                 Wednesda         prompt is for Wednesday. Repeat the
                                                                set? Y/N         procedure for the rest of the days of
 Display
                                                                                 the week.
                    Press the MENU key while in the
     RoomTemp       Status Display Menu to enter the
     75.0F         Main User Menu.                                              After setting the schedule for all the
                                                                Exit?            days of the week, following the last
                                                                        Y/N      entry for Sunday, press the YES key
                                                                                 to return to the Status Display Menu
                    Press the NO key to all prompts until                        or press the NO key to start again at
     Schedule       the schedule set prompt appears on                           Monday.
     set? Y/N       the display. Press the YES key to
                    enter the scheduling menu.
                                                             Programming the Daily Schedule – Four-Event
                                                             The schedule-setting menu is used to enter the
                    Press the YES key to set the             occupied and unoccupied states for each day of the
     Monday         schedule for Monday or press the NO      week. The schedule-setting menu reflects either a
     set? Y/N       key to advance to Tuesday.
                                                             two- or four-event schedule per day, based on what
                                                             was selected in the 2/4event parameter during the
                                                             configuration process. If the schedule-setting menu
                    Press the YES key to set the             does not reflect a four-event schedule, select four
     Occupied       occupied start time for Monday or        events in the 2/4event parameter of the Installer
     day? Y/N       press the NO key to advance to
                    Tuesday. Selecting NO will leave the     Configuration Menu.
                    thermostat in the unoccupied state       When changing the time, press the UP/DOWN arrow
                    for the entire day.
                                                             keys once to change the time in 1-minute increments;
                    Press the UP/DOWN arrow keys to          press and hold down the keys to change the time in
     Occupied       set the occupied start time. Press the
                                                             30-minute increments.
     12:00 AM       YES key to enter the time.
                                                             Note: Programming one of the digital inputs to remote
                                                             NSB disables the menu.
                    Press the UP/DOWN arrow keys to          To set the time schedule for a four-event schedule,
     Unoccup        set the unoccupied start time. Press
                                                             follow the steps in Table 6. See Table 7 for an example
     12:00 AM       the YES key to enter the time.
                                                             of a four-event office schedule.
                                                             Table 6: Programming the Daily Schedule –
                                                                      Four-Event (Part 1 of 2)
                    Press the YES key to set the
     Tuesday        schedule for Tuesday or press the         Thermostat         Description
     set? Y/N       NO key to advance to Wednesday.           Display
                                                                                 Press the MENU key from the Status
                                                                RoomTemp         Display Menu to enter the Main User
                    Press the YES key to copy the               75.0F           Menu.
     Copy Y/N       schedule from the previous day.
     previous       Press the NO key to set a different
                    schedule.
                                                                                 Press the NO key to all prompts until
                                                                Schedule         the schedule set prompt appears on
                                                                set? Y/N         the display. Press the YES key to
                                                                                 enter the scheduling menu.

12     T600MSx-3 Multi-Stage Thermostat Installation Instructions
Table 6: Programming the Daily Schedule –
         Four-Event (Part 2 of 2)
Thermostat       Description
Display
                 Press the YES key to set the
   Monday        schedule for Monday or press the NO
   set? Y/N      key to advance to Tuesday.

                 Press the YES key to set the
   Occupied      occupied start time for Monday or
   day? Y/N      press the NO key to advance to
                 Tuesday. Selecting NO will leave the
                 thermostat in the unoccupied state
                 for the entire day.
                 Press the UP/DOWN arrow keys to
   Occupied      set the first occupied start time. Press
   12:00 AM      the YES key to enter the time.

                 Press the UP/DOWN arrow keys to
   Unoccup       set the first unoccupied start time.
   12:00 AM      Press the YES key to enter the time.

                 Press the UP/DOWN arrow keys to
   Occupie2      set the second occupied start time.
   12:00 AM      Press the YES key to enter the time.

                 Press the UP/DOWN arrow keys to
   Unoccup2      set the second unoccupied start time.
   12:00 AM      Press the YES key to enter the time.

                 Press the YES key to set the
   Tuesday       schedule for Tuesday or press the
   set? Y/N      NO key to advance to Wednesday.

                 Press the YES key to copy the
   Copy Y/N      schedule from the previous day.
   previous      Press the NO key to set a different
                 schedule.

                 If the YES key was pressed, the next
   Wednesda      prompt is for Wednesday. Repeat the
   set? Y/N      procedure for all days of the week.

                 After setting the schedule for all the
   Exit?         days of the week, following the last
           Y/N   entry for Sunday, press the YES key
                 to return to the Status Display Menu
                 or press the NO key to start again at
                 Monday.

                                                  T600MSx-3 Multi-Stage Thermostat Installation Instructions   13
Table 7: Four-Event Office Schedule
                                 Event 1                  Event 2                  Event 3                  Event 4
                                Occupied                Unoccupied               Occupied 2              Unoccupied 2
 Event                       Cool        Heat         Cool           Heat      Cool        Heat         Cool        Heat
                             72°F        70°F         80°F        62°F         72°F        70°F         80°F        62°F
                            (22°C)      (21°C)       (27°C)      (17°C)       (22°C)      (21°C)       (27°C)      (17°C)
 Monday                          7:00 A.M.                5:00 P.M.               12:00 P.M.1              12:00 P.M.1
 Tuesday                         7:00 A.M.                5:00 P.M.               12:00 P.M.1              12:00 P.M.1
 Wednesday                       7:00 A.M.                5:00 P.M.               12:00 P.M.1     