Product/Technical Bulletin W351
                                                                                        Issue Date May 31, 2014

                                     PRODUCT/TECHNICAL BULLETIN

    System 350 W351 Electrical On/Off Humidity Control

The W351 Electronic Humidity Control is an On/Off
humidity control. The control output is a Single-Pole,
Double-Throw (SPDT) relay with LED indication. It
features humidification and dehumidification modes of
operation and an adjustable differential.

The W351 control is designed to work with an
HE-67S3-0N0BT Room Sensor Humidity Transmitter
or HE-67S3-0N00P Duct Sensor Humidity Transmitter.

As with all System 350 products, the W351 control
housing is a compact NEMA 1, high-impact plastic
enclosure. The modular design provides easy,
plug-together connections for quick installation and
future expandability.
                                                              Figure 1: W351 Electronic On/Off Humidity Control

                                              Features and Benefits
                  Modular Design                      Provides the flexibility to add up to five S351
                                                       Humidity Stage Modules (nine with a 24 VAC
                                                       transformer), a D351 Humidity Display
                                                       Module, and a Y350R Power Module

                  Plug-together Connectors            Eliminates wiring between modules and
                      and 35 mm DIN Rail               reduces installation costs
                      Mounting

                  Adjustable Setpoint Range           Reduces inventory by covering the humidity
                      of 10-90% RH                     range required to support most humidity
                                                       applications

                  Wide Adjustable Differential Enables the user to match the equipment
                      of 2-10% RH                      cycle rate and sequencing for a given
                                                       application

                  Humidification or                   Works in a variety of humidification or
                      Dehumidification Modes of        dehumidification applications
                      Operation

                  Interchangeable Humidity            Increases versatility and serviceability
                      Transmitters

© 2014 Johnson Controls, Inc.                                                                                          1
  Part No. 24-7664-36, Rev. D                                                                     www.johnsoncontrols.com
  Code No. LIT-930060
                                                           •    HE-67S3-0N0BT Wall Mount or HE-67S3-0N00P
A   pplication                                                  Duct Mount Humidity Transmitter

IMPORTANT: Use this System 350 W351
Electronic On/Off Humidity Control only to control         O peration
equipment under normal operating conditions. Where         The W351 control has an external range scale and
failure or malfunction of the W351 control could lead      setpoint dial, a front panel LED indicating when the
to personal injury or property damage to the               relay is energized, and a SPDT relay output.
controlled equipment or other property, additional         (See Figure 2.) Features include:
precautions must be designed into the control
system. Incorporate and maintain other devices, such       •    adjustable setpoint
as supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against failure   •    adjustable differential
or malfunction of the W351 control.                        •    selectable mode of operation
                                                                (humidification/dehumidification)
IMPORTANT : Utiliser ce System 350 W351
Electronic On/Off Humidity Control uniquement pour
commander des équipements dans des conditions              Setpoint Adjustment
normales de fonctionnement. Lorsqu'une défaillance
ou un dysfonctionnement du W351 control risque de          Setpoint is the % RH at which the relay de-energizes.
provoquer des blessures ou d'endommager                    With the operation mode jumpers in either the
l'équipement contrôlé ou un autre équipement, la           humidification or dehumidification position, the relay
conception du système de contrôle doit intégrer des        de-energizes when the % RH at the transmitter
dispositifs de protection supplémentaires. Veiller dans    reaches the setpoint.
ce cas à intégrer de façon permanente d'autres
dispositifs, tels que des systèmes de supervision ou       Differential Adjustment
d'alarme, ou des dispositifs de sécurité ou de
limitation, ayant une fonction d'avertissement ou de       Differential is the change in % RH at the transmitter
protection en cas de défaillance ou de                     required to energize and de-energize the relay. The
dysfonctionnement du W351 control.                         differential is adjustable between 2-10% RH.
                                                                                  Setpoint Dial
The W351 Electronic On/Off Humidity Control can be
used as a standalone device or in conjunction with                                                      Mode of
System 350 Add-On Modules to control a wide variety                Differential                        Operation
                                                                                         J1         Jumper Positions:
of single or multiple stage humidity applications.                Potentiometer
Typical W351 control applications include humidity                                                Dehumidification
control for:
                                                                                                    Humidification
•   clean rooms
•   computer rooms
•   pharmaceutical manufacturing
•   fruit storage/ripening
                                                                 Figure 2: W351 Electronic On/Off Humidity
•   indoor swimming pools
                                                               Control; Setpoint and Differential Adjustments;
•   greenhouses                                                 Humidification and Dehumidification Modes
A typical System 350 Humidity Control scheme
includes the following:
                                                           Mode of Operation
•   W351 Humidity Control
                                                           When the dehumidification mode is selected, the
•   up to five S351 Humidity Stage Modules                 differential is above the setpoint. When the humidity
                                                           rises to the setpoint plus the differential setting, the
•   D351 Digital Humidity Display Module
                                                           relay energizes and the LED lights. When the humidity
•   Y350R Power Module (or 24 VAC transformer)             drops to the setpoint, the relay and LED indicator
                                                           de-energize. (See Figure 3.)

2   System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin
When the humidification mode is selected, the
differential is below the setpoint. When the humidity
drops to the setpoint minus the differential setting, the
                                                                D imensions
relay energizes and the LED lights. When the humidity                   1/8         1/2
                                                                        (4)        (13)
rises to the setpoint, the relay and LED indicator
de-energize. (See Figure 3.)

                                                                               2-15/16                   5                W351
                                                                                 (75)                  (127)             ON
        (+)                                                                                                    4
                                                                                                             (102)
               Dehumidification
                         On
                               On = Relay & LED Energized             1-9/16     3/8                                             2-3/8
                                                                                          DIN Rail
                               Off = Relay & LED De-energized          (40)      (11)                                            (61)
                Differential                                                               Mount        1-3/16
                                                                     Mounting Slot                       (31)
  Setpoint                               Off                       for No. 6 Screws
  Relative
  Humidity      Off
                                                                                             3
                                                                                                     2-3/8
                                         Differential                                       (76)
                                                                                                     (61)

                                                 On                                                           7/8
                                                                                                                        1/2 in.
                                                                                                             (22)     Trade Size
                                       Humidification
                                                                                                                     Conduit Hole
        (-)
                                                                    Figure 4: W351 Control Dimensions, in./mm
              Figure 3: Modes of Operation

                                                                M ounting
                                                                The W351 Electronic Humidity Control housing is a
                                                                compact NEMA 1 plastic enclosure designed for
                                                                standard 35 mm DIN rail mounting. Four key-slot
                                                                mounting holes on the back of the control case are
                                                                provided for surface mounting.
                                                                The W351 control is not position sensitive but should
                                                                be mounted for convenient wiring and adjustment.
                                                                Note:    When mounting the W351 control (or any
                                                                         System 350 module) to rigid conduit, attach
                                                                         the hub to the conduit before securing the hub
                                                                         to the control enclosure.

                                  System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin                          3
    !   WARNING: Risk of Electric Shock.                W iring
        Disconnect or isolate all power supplies        Install all wiring to conform to the National Electrical
        before making electrical connections. More      Code and to local regulations. For maximum electrical
        than one disconnection or isolation may be      rating of control, refer to the label inside the control
        required to completely de-energize              cover. Use only copper conductors.
        equipment. Contact with components
        carrying hazardous voltage can cause            See Figures 5 and 6 for proper wiring and terminal
        electric shock and may result in severe         designations.
        personal injury or death.
        AVERTISSEMENT : Risque de décharge              Transmitter Wiring
        électrique.
                                                        The W351 Humidity Control uses an HE-67S3-0N0BT
        Débrancher ou isoler toute alimentation
                                                        or HE-67S3-0N00P Humidity Transmitter, which is
        avant de réaliser un branchement électrique.
                                                        powered by the 12 VDC power supply from the W351
        Plusieurs isolations et débranchements sont
                                                        control. See TRUERH Series HE-67xx Humidity
        peut-être nécessaires pour -couper
                                                        Element with Temperature Sensor Installation
        entièrement l'alimentation de l'équipement.
                                                        Instructions (Part No. 24-9527-7 Rev. A) for more
        Tout contact avec des composants
        conducteurs de tensions dangereuses risque      information.
        d'entraîner une décharge électrique et de
        provoquer des blessures graves, voire           Connect the transmitter to the W351 control at the
        mortelles.                                      four-conductor screw terminal block, located at the
                                                        upper left of the circuit board. (See Figures 5 and 6.)
                                                        Note:   Set the output jumpers on the
                                                                HE-67S3-0N0BT and HE-67S3-0N00P
                                                                humidity transmitters for 0 to 10 VDC output.
                                                        Shielded cable is not generally required for transmitter
                                                        wiring on runs of less than 50 feet. When using
                                                        shielded cable, isolate and tape the shield at the
                                                        transmitter. Connect the shield to the Communications
                                                        Port (COM) terminal on the W351 control.
                                                        The maximum recommended length of 22 AWG 3-wire
                                                        shielded transmitter cable is 250 feet (76 meters).

4   System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin
             HE-67S3-0N00P                        HE-67S3-0N00P
      Duct Mount Humidity Transmitter      Wall Mount Humidity Transmitter

          0 to 10    PWR                                     0 to 10
                     COM
           VDC       OUT                                      VDC                       Humidity Transmitter
                                              PWR
                                               COM
                                                                                              PWR
                                                 OUT                                          COM
                                                                                              OUT

                             W351            Y350R                S351           S351            D351
                         Humidity Control Power Module        Stage Module   Stage Module   Display Module

                                      J1

               24V
               COM
               VDC
               SEN

              120 VAC

                               Load                                Load          Load

Figure 5: W351 Humidity Control (Dehumidification Mode) Powered by an External Transformer
           with the Humidity Transmitter Less Than 50 Feet from the W351 Control

                         System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin         5
                     HE-67S3-0N00P                     HE-67S3-0N00P
              Duct Mount Humidity Transmitter   Wall Mount Humidity Transmitter

                  0 to 10     PWR                                 0 to 10
                              COM                                  VDC                       Humidity Transmitter
                   VDC        OUT
                                                   PWR
                                                    COM                                            PWR
                                                      OUT                                          COM
                                                                                                   OUT

                                                                                                  Isolate and Tape
                            Shield
                                   W351            Y350R             S351             S351            D351
                               Humidity Control Power Module     Stage Module     Stage Module   Display Module

                     24V
                     COM
                     VDC
                     SEN

                    120 VAC

                                     Load                             Load            Load

                      Figure 6: System 350 Modules Powered by a Y350R Power Module
                       with the Humidity Transmitter 50-250 Feet from the W351 Control

A dd-On Modules
The S351 Stage Modules, D351 Digital Humidity                     See System 350 S350A Temperature, S351A
Display Modules, and Y350R Power Modules plug                     Humidity, and S352A Pressure Stage Modules
together and connect to the W351 Electronic Humidity              Product/Technical Bulletin (LIT-930080) for more
Control via connectors on the sides of each add-on                information.
module. The recommended order of the modules is
shown in Figures 5 and 6.
                                                                  D351 Digital Humidity Display Module
S351 Humidity Stage Modules                                       The D351 Display Module receives its power, sensor,
                                                                  and setpoint information from the W351 control. A
The S351 Stage Modules receive their power,                       3-digit Liquid Crystal Display (LCD) gives a continuous
setpoint, and sensor input from the W351 Electronic               display of the sensed humidity. Press the button to
Humidity Control.                                                 display the setpoint of the adjoining W351 control. See
When using a Y350R module, up to five additional                  System 350 Display Modules Product/Technical
S351 Stage Modules can be plugged into a W351                     Bulletin (LIT-930070) for more information.
Humidity Control. When using an external 24 VAC
(40 VA minimum) transformer, up to nine additional
S351 Stage Modules can be plugged in.

6   System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin
Y350R Power Module                                       3. Adjust the differential by rotating the differential
                                                            potentiometer to the desired setting.
The Y350R Power Module provides a convenient                (See Figure 2.) Rotate the potentiometer
method of powering System 350 modules from a                clockwise to increase the differential.
120 or 240 VAC power source.
                                                         4. Replace the cover, tighten the four captive cover
Plug the Y350R power module into the right side of the      screws, and adjust the setpoint by rotating the
W351 Electronic Humidity Control. The Y350R power           setpoint dial to the desired % RH setpoint.
supplies power for a W351 control, a D351 Display           (See Figure 2.)
Module, and up to five S351 Stage Modules.
                                                             Note:    Use the D351 Display Module for the most
See System 350 Power Module Product/Technical                        accurate setpoint selection.
Bulletin (LIT-930090) for more information.
                                                                      If using the D351 Display Module, press
                                                                      and hold the button on the D351 module
A djustments                                                          while rotating the setpoint dial.

   !    WARNING: Risk of Electric Shock.
                                                         S351 Stage Module
                                                         When the W351 control is used in conjunction with one
Do not touch any exposed metal parts with anything       or more S351 modules, the following adjustments
other than properly insulated tools or insulated         must be made to each S351 module. Additional
probes of the digital voltage meter. Failure to use      information about adjusting the stage module is
properly insulated tools and probes may result in        available in the S350 Temperature, S351 Humidity,
severe personal injury or death.                         and S352 Pressure Stage Modules Product/Technical
                                                         Bulletin (LIT-930080).
AVERTISSEMENT : Risque de décharge
électrique.                                              1. Remove the S351 module cover by loosening the
Ne jamais toucher une partie métallique exposée             four captive cover screws.
avec tout élément autre que des outils correctement
                                                         2. Set the humidification/dehumidification operation
isolés ou les sondes isolées du voltmètre
                                                            mode jumpers to the desired mode of operation.
numérique. L'utilisation d'outils et de sondes
incorrectement isolés risque de provoquer des                •   Select dehumidification mode for offset and
blessures graves, voire mortelles.                               differential above setpoint.
                                                                 (See Figures 7 and 8.)
                                                             •   Select humidification mode for offset and
IMPORTANT:            Verify that the humidification             differential below setpoint.
dehumidification operation mode jumpers are in the               (See Figures 7 and 8.)
proper position before powering System 350               3. Adjust the S351 stage module’s offset
components. If the operation mode jumpers on the            potentiometer to the desired offset value. The
control or the staging modules are left in the wrong        offset value is the difference in humidity from the
position, the device will activate the relay in             W351 control module’s setpoint that is required for
response to the opposite signal. The humidifying or         the S351 stage module’s relay to de-energize.
dehumidifying equipment may remain energized until          (See Figures 7 and 8.)
the error is corrected.

W351 Control
1. Remove the W351 control cover by loosening the
   four captive cover screws.
2. Position the jumpers on jumper block J1 vertically
   for humidification, or horizontally for
   dehumidification. (See Figure 2.) The jumpers are
   factory-set for humidification.

                             System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin         7
4. Adjust the differential potentiometer to the desired
   differential value. The differential value is the
   difference in humidity from the offset that is
                                                                             T roubleshooting
   required for the S351 stage module’s relay to                             Before applying power, make sure installation and
   energize. (See Figures 7 and 8.)                                          wiring connections are according to job specifications.
5. Reinstall the cover onto the enclosure base and                           After making necessary adjustments and electrical
   secure the cover to the enclosure base with the                           connections, put the system into operation and
   four cover screws.                                                        observe at least three complete operating cycles
                        Setpoint Dial
                                                                             before leaving the installation.

                                                Mode of
        Differential                           Operation
                                                                             Checkout
                                J1          Jumper Positions:
       Potentiometer
                                        Dehumidification                        !     WARNING: Risk of Electric Shock.
                                            Humidification                            Do not touch any exposed metal parts with
                                                                                      anything other than properly insulated tools
                                                                                      or insulated probes of the digital voltage
                                                                                      meter. Failure to use properly insulated tools
                                                                                      and probes may result in severe personal
    Figure 7: S351 Stage Module Adjustment and                                        injury or death.
               Potentiometer Locations
                                                                                      AVERTISSEMENT : Risque de décharge
          (+)
                                                                                      électrique.
                                        On                                             Ne jamais toucher une partie métallique
                                                                                      exposée avec tout élément autre que des
                                                                                      outils correctement isolés ou les sondes
                          On Differential        On = Energized
                                                Off = De-energized
                                                                                      isolées du voltmètre numérique. L'utilisation
                                                                                      d'outils et de sondes incorrectement isolés
                Differential Off                                                      risque de provoquer des blessures graves,
                                   Offset
    Setpoint                                                                          voire mortelles.
    Relative
                Off
    Humidity
                                                   Offset                    If the control system does not function properly, verify
                                             Off                   Offset
                                                                             that the proper mode is selected on each module (e.g.,
                                                             Off             humidification/dehumidification) and then use the
                                              Differential                   following procedures to determine the cause of the
                                                             Differential    problem:
                                                      On                     1. Check for proper voltage applied to the
        (-)
                                                                       On    W351 Humidity Control:
                 W351            S351           S351                S351         a. Connect a Digital Voltmeter (DVM) between
                Humidity        Stage          Stage               Stage
                Control         Module         Module              Module           the 24 V (+) and COM (-) terminals located on
                Stage 1                        Stage 3
                                                                                    the W351 control’s left-side terminal block.
                                Stage 2                            Stage 4
                                                                                    (See Figures 5 and 6.)
                       Dehumidify                      Humidify
                                                                                      •   If an external transformer is used, select
                                                                                          AC volts on the DVM and verify that the
            Figure 8: Typical Multistage
                                                                                          voltage is between 20-30 VAC.
    Humidification/Dehumidification Application
                                                                                      •   If a Y350R Power Module is used, select
                                                                                          DC volts on the DVM and verify that the
                                                                                          voltage is between 16-38 VDC.
                                                                                 b. Proceed to Step 2 if the DVM reading is within
                                                                                    the indicated voltage range.
                                                                                 c.   If the DVM reading is not within the indicated
                                                                                      voltage range, check wiring, then replace the

8    System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin
         Y350R power module or the external                                  10
         transformer.
                                                               Transmitter
Table 1: W351 Control Relay                                      Output
                                                                  VDC
Troubleshooting
 Mode of         LED       Normally        Setpoint
                                                                             5
 Operation       Status    Open Relay      Dial
                           Status          Setting*
 Humidify        On        Closed          (RHT) +
                                           differential
 Humidify        Off       Open            (RHT)
                                                                             00
 Dehumidify      On        Closed          (RHT) -                                            50           100
                                           differential
                                                                                  RHT Humidity (% RH)
 Dehumidify      Off       Open            (RHT)
* See Figure 9 for RHT vs. Humidity illustration.              Figure 9: Transmitter Voltage vs. Humidity
2. Check humidity transmitter for proper output
voltage:                                                   3. Check the W351 Electronic Humidity Control for
                                                              proper operation:
    a. Disconnect the transmitter OUT wire from the
       W351 control SEN terminal.                             Note:     Perform Steps 1 and 2 first.
    b. Take a humidity reading with a properly                a. Adjust the setpoint dial to at least 20% RH
       calibrated, accurate humidity measuring                   below the voltage conversion to % RH (RHT)
       device. This reading is the actual humidity.              as determined in Step 2.
    c.   Connect a DC voltmeter between the                   b. Increase the setpoint by slowly adjusting the
         transmitter OUT wire and the control COM                dial until the W351 control’s relay and LED
         terminal. Using Figure 9, convert the voltage           turn On and Off as shown in Table 1.
         to % RH. This is the humidity reading at the         c.   If the relay performs as expected, continue to
         transmitter (RHT).                                        Step 4.
         Note:   A transmitter output of 0-10 VDC             d. If the relay does not perform as indicated in
                 should correspond to a humidity of              Table 1, replace the W351 control.
                 0-100% RH (see Figure 9).
         •   If the RHT is close to the actual humidity,
             proceed to Step 2d.
         •   If the RHT deviates substantially from the
             actual humidity, replace the transmitter.
    d. Reconnect the transmitter OUT wire to the
       W351 control SEN terminal.

                               System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin        9
4. Check the S351 Stage Modules for proper                 5. Check the D351 Display Module for proper
operation (if applicable):                                 operation (if applicable):
     Note:    Perform Steps 1, 2, and 3 first.                 Note:   Perform Steps 1 through 4 first.

 IMPORTANT:          There is a possibility that a             a. Compare the voltage conversion to % RH at
 defect in one stage module could cause defective                 the transmitter (RHT) (as determined in Step 2)
 symptoms in all modules. Plug each S351 module                   with the display readout.
 into the W351 control individually and check its              b. If the D351 module does not read the correct
 performance as outlined in Step 4.                               transmitter RH (RHT), replace the
                                                                  D351 module.
     a. Turn the setpoint dial on the W351 control to
        10% RH (the extreme counterclockwise                   c.   Press the button on the D351 module to
        position).                                                  display the setpoint.

     b. Increase the setpoint by slowly adjusting the          d. If pressing the button results in an
        dial until the S351 module’s relay and LED                out-of-range reading (greater than 100% RH),
        turn On and Off as shown in Table 2.                      replace the D351 module.

     c.   If the relay does not perform as indicated in        e. If pressing the button results in a reading other
          Table 2, adjust the S351 module’s differential          than the expected setpoint value, check the
          and offset potentiometers to their minimum              setpoint dial setting on the W351 control and
          settings and try again.                                 correct if necessary. If the display continues to
                                                                  show an incorrect value, replace the display
     d. If the relay still does not turn On and Off,              module.
        replace the defective S351 Stage Module(s).
                                                               Note:   If the W351 control and add-on modules
Table 2: S351 Module Relay                                             all appear to be operating properly, but the
Troubleshooting                                                        field device still does not turn On and Off
                                                                       as expected, check the wiring from the
 Mode of         LED        Normally    Setpoint Dial
                                                                       W351 control or S351 module to the field
 Operation       Status     Open        Setting*
                                                                       device.
                            Relay
                            Status

 Humidify        On         Closed      (RHT) + offset +
                                        differential
                                                           R epairs and Replacement
                                                           Do not calibrate or make field repairs.
 Humidify        Off        Open        (RHT) + offset     HE-67S3-0N0BT and HE-67S3-0N00P humidity
 Dehumidify      On         Closed      (RHT) - offset -   transmitters and replacement controls are available
                                        differential       through local Johnson Controls representatives or
                                                           wholesale distributors.
 Dehumidify      Off        Open        (RHT) - offset
* See Figure 9 for RHT vs. Humidity illustration.

10    System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin
O rdering Information
Table 3: Ordering Information
 Item                               Product Code          Description
                                    Number
 Electronic Humidity Control        W351AB-2C             Setpoint Range: 10-90% RH
                                                          Differential:     2-10% RH
                                                          (sensor not included)
                                    W351AA-1C             Setpoint Range: 10-90% RH
                                                          Differential:    2-10% RH
                                                          (includes Wall Mount Sensor HE-67S3-0N0BT)
                                    W351AA-2C             Setpoint Range: 10-90% RH
                                                          Differential:    2-10% RH
                                                          (includes Duct Mount Sensor HE-67S3-0N00P)
 Humidity Transmitter               HE-67S3-0N0BT         All-polymer, Wall Mount Humidity Transmitter
                                    HE-67S3-0N00P         All-polymer, Duct Mount Humidity Transmitter
 Display Module                     D351AA-1C             Digital Humidity Display Module
 Stage Module                       S351AA-1C             Humidity Stage Module with % RH Scale
 Power Module                       Y350R-1C              Rectified, Class 2, 24 VAC from 120/240 VAC Source
 Conduit Adapter                    ADP11A-600R           1/2-in. Snap-fit Connector (box of 10)
 DIN Rail Sections                  BKT287-1R             35 x 7.5 mm, 0.305 m (12 in.) long
                                    BKT287-2R             35 x 7.5 mm, 0.914 m (36 in.) long
 DIN Rail End Clamps                PLT344-1R             Consists of Two End Clamps
 Cable for Remote Mounting          WHA29A-600R           (0.9 m) 3 ft*
 of D351 Display Module
                                    WHA29A-603R           (7.6 m) 25 ft
                                    WHA29A-604R           (15.2 m) 50 ft
* WHA29A-600R can also be used to daisy chain S351 Stage Modules together.

                               System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin   11
S pecifications
 Product                             W351 Electronic On/Off Humidity Control
 Humidity Setpoint Range             10-90% RH
 Differential Range                  2-10% RH
 Input Signal                        0-10 VDC Corresponding to 0-100% RH
 VDC Power Supply                    12 VDC Provided to Power the Humidity Transmitter
 Supply Voltage*                     20-30 VAC Class 2; 50/60 Hz (or a Y350R Power Module: See Add-On Modules section)
 Power Consumption                   1.8 VA maximum
 Relay Electrical Ratings            Horsepower:     1/2 (120/240 VAC)
                                     Full Load Amperes:       9.8 (120 VAC)  4.9 (208/240 VAC)
                                     Locked Rotor Amperes: 58.8 (120 VAC) 29.4 (208/240 VAC)
                                     Non-inductive Amperes: 10 at 24/240 VAC
                                     Pilot Duty:     125 VA at 24/240 VAC
 Ambient Temperature                 Operating:          -30-150°F (-34-66°C)
                                     Shipping :          -40-185°F (-40-85°C)
 Ambient Humidity                    0-95% RH Non-Condensing; Maximum Dewpoint 85°F (29°C)
 Material                            Case, Cover:        NEMA 1 High-impact Thermoplastic
 Agency Listing                      UL Listed, File E27734, CCN XAPX
                                     cUL Listed, File E27734, CCN XAPX7
 Transmitter                         HE-67S3-0N0BT: All-Polymer, Wall-Mount Humidity Transmitter; 0 to 10 VDC,
                                                    0 to 100% RH
                                     HE-67S3-0N00P: All-Polymer, Duct-Mount Humidity Transmitter; 0 to 10 VDC,
                                                    0 to 100% RH
 Add-On Modules                      Supply Voltage:               Provided by the W351 control
                          S351       DIFF and OFFSET:              2-10% RH Differential; 2-30% RH Offset
                          Y350R      Supply Voltage:               Provided by the W351 control
                          D351       Display Range:                10-90% RH

* Only one input voltage source may be used.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/PENN Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.

                                                                                                                  Building Efficiency
                                                                                         507 E. Michigan Street, Milwaukee, WI 53202

                                            Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                   All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.

12    System 350 W351 Electronic On/Off Humidity Control Product/Technical Bulletin