Security Control Panel Assembly
Mounted in a 24 in. x 30 in. Enclosure Part No. 24-10613-39, Rev. C
Issued December 2017
Installation Instructions
SPA1B100-1D10, SPA1B200-1D10, SPA1B300-2D10, SPA1B400-2D10
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Applications Parts Included
The 24 in. x 30 in. Security Control Panel is a pre-wired, • 24 in. x 30 in. (61 cm x 76.2 cm) enclosure, Type 1 with keyed
preassembled standard control panel and enclosure that contains a lock, door tamper switch, and battery support brackets
CK721-A network controller and/or S300-DIN-RDR2SA (also called • CK721-A network controller and up to four RDR2S-A two-door
RDR2S-A) modules. The control panel is shipped complete, mounted interface modules
in a steel enclosure. The panel is equipped with the required number • One or two S300-DIN-L-PS 24 VDC, 5 A power supplies
of 120 VAC/24 VDC power supplies. The power supply has
Uninterruptible Power Supply (UPS) capability with the addition of
factory-wired gel cell batteries (S300-BAT), which are sold separately.
These enclosures are designed specifically for security control
requirements, with battery brackets that do not need to be removed to
install the batteries, a lift-off door, a pre-wired door tamper switch, and
a lockable door with key. Space is reserved on specific models for the
addition of future components.
Repair Information
If the Security Control Panel Assembly fails to operate within its
specifications, replace the failed component. Contact Global Security
Solutions Technical Support at (866) 893-0423 or (414) 524-1214, or
by email at support.globalsecuritysolutions@jci.com. End users can
contact their local branch or authorized dealer. For the nearest office,
visit http://www.johnsoncontrols.com/location-finder.
Refer to the Security Enclosure Components Catalog Page
(LIT-1900572) to order components separately. Figure 1: Security Control Panel Mounted in a
24 in. x 30 in. Enclosure
Cable Requirements
Description Recommended Cable Type1, 2 Maximum Segment Length
CK721-A: RS485A, RS485B Listed, 22 AWG, stranded, copper, hook-up wire Limited to within cabinet.
RDR2S-A: RS485+/-
Listed, 18 AWG, 3-conductor, stranded, shielded, copper 4,000 ft (1,219 m) maximum
CK721-A: ICOM1, ICOM2 Belden® 8442, 22 AWG, 1 twisted pair, stranded, 500 ft (152 m)
RDR2S-A: Door Contact unshielded, copper
CK721-A: OUT1 Belden 9740, 18 AWG, 1 twisted pair, stranded, Depends on power requirements of the device. Voltage to
RDR2S-A: Door Strike, Shunt unshielded, copper the device must not be reduced more than 10% over the
18 AWG wire, measured when energized.
Request to Exit (RDR2S-A only) Belden 8442, 22 AWG, 1 twisted pair, stranded, 500 ft (152 m)
unshielded, copper
Reader Power (RDR2S-A only) Belden 9740, 18 AWG, 1 twisted pair, stranded, Refer to reader manufacturer’s specification for power
unshielded, copper requirements.
Reader Data0/Data1 Belden 9744, 22 AWG, 2 twisted pairs, stranded, 500 ft (152 m). Refer to reader manufacturer’s
(RDR2S-A only) unshielded, copper specification for data requirements.
RS232 A, RS232 B Listed DB9 F/F AT Null Modem cable 25 ft (7 m). Cable must remain in the same room as the
CK721-A.
Ethernet Listed, Category 5, 24 AWG, solid, 2 pair or 4 pair type 354 ft (100 m). Cable, RJ45 connector, and RJ45 crimp
tool to be supplied by customer.
1. All data cables should be physically separated from power lines. If conduit is used, do not run data cables in the same conduit as power cables or certain door
strike cables, such as strike voltage greater than 42 V or magnetic door locks without Electromagnetic Interference (EMI) suppression. All cables must conform
with National Electrical Code, NFPA 70; or for Canadian installations, refer to the Canadian Electric Code C22.1.
2. Shielded cable is not required but is strongly recommended to minimize the effects of electromagnetic interference or radio frequency noise.
UL 294 Performance Levels
Destructive Attack Line Security Endurance Standby Power
SPA1B100-1D10 Level I Level II Level IV Level II
SPA1B200-1D10 Level I Level II Level IV Level II
SPA1B300-2D10 Level I Level II Level IV Level II
SPA1B400-2D10 Level I Level II Level IV Level II
Security Control Panel Assembly Mounted in a 24 in. x 30 in. Enclosure Installation Instructions 1
Mounting and Connecting the Panels Product Code Description
Number
• Mount the panel on a wall or other mounting surface located in a
restricted-access area. SPA1B300-2D10 24 in. x 30 in. (61 cm x 76.2 cm) security control
• The horizontal distance between the mounting holes is 16.75 in. panel with CK721-A controller, three RDR2S-A
(42.5 cm); the vertical distance is 27.5 in. (69.9 cm). Mounting modules, and two power supplies
hole diameter is 0.436 in. (1.1 cm). SPA1B400-2D10 24 in. x 30 in. (61 cm x 76.2 cm) security control
• Ensure the door can swing fully open. panel with CK721-A controller, four RDR2S-A
• Mount the panel in a location where airflow is uninhibited over the modules, and two power supplies
exposed surfaces.
• Remove the back plate before securing the panel to the mounting
surface and reinstall it when mounting is complete. Technical Specification
AC Power Connection Security Control Panel Assembly Mounted in a 24 in. x 30 in.
Enclosure
• Put the AC Wired at
power wiring Electrical Rating SPA1B100-1D10: 120 VAC, 1.8 A, 50/60 Hz
To AC power
the factory
BLU
G
through a N SPA1B200-1D10: 120 VAC, 1.8 A, 50/60 Hz
BRN
BLU
knockout. L SPA1B300-2D10: 120 VAC, 3.6 A, 50/60 Hz
N L L = Line
source
BRN
• Connect the AC SPA1B400-2D10: 120 VAC, 3.6 A, 50/60 Hz
N = Neutral
power wiring to TB-1 Power supply G = Ground Enclosure Rating NEMA Type 1
terminal block
TB-1. Ambient Operating 32 to 122°F (0 to 50°C), 10 to 85% RH,
• Do not connect the DC power cable to the module until all wiring is Condition noncondensing
complete Dimensions (Width 24 in. x 30 in. x 6.62 in.
x Height x Depth) (61 cm x 76.2 cm x 16.8 cm)
WARNING: Risk of Electric Shock. Ambient Storage -4 to 158°F (-20 to 70°C), 5 to 95% RH,
!
Disconnect the power supply before making Condition noncondensing
electrical connections. Contact with components
Compliance United States:
carrying hazardous voltage can cause electric shock UL Listed under UL 1076 for Proprietary Burglar
and may result in severe personal injury or death. Alarm Units and Systems, and under UL 294 for
Access Control Systems Units;
S300-BAT Battery Connection This equipment has been tested and found to
comply with the limits for a Class B digital device,
The optional S300-BAT feature pursuant to Part 15 of the FCC rules. These limits
RED
WHT BLK
uses two PowerSonic, Model are designed to provide reasonable protection
PS-1270, 12 VDC, 7 Ah, sealed + - + - + - + - G N L against harmful interference in a residential
lead acid batteries per power DC installation. This equipment generates, uses and
BAT
HIGH
supply. The batteries should be B-1A B-1B OUT VOLT
AGE can radiate radio frequency energy and, if not
replaced every three years to installed and used in accordance with the
PS-1
ensure proper operation. instructions, may cause harmful interference to
The RED (+), BLK (-), and radio communications. However, there is no
RED
WHT BLK guarantee that interference will not occur in a
WHT cables are provided with
the enclosure. particular installation. If this equipment does cause
+ - + - + - + - G N L
harmful interference to radio or television reception,
Replace the batteries whether DC
BAT
HIGH
B-2A B-2B which can be determined by turning the equipment
or not they have been placed OUT VOLT
AGE
off and on, the user is encouraged to try to correct
into use by an AC power PS-2 the interference by one or more of the following
failure. Observe the polarity measures:
when connecting the batteries. • Reorient or relocate the receiving antenna.
• Increase the separation between the equipment
Field Devices and receiver.
• Connect the equipment into an outlet on a circuit
For information on wiring the CK721-A controller or the RDR2S-A
different from that to which the receiver is
module, refer to the documentation provided with these devices.
connected.
Use a separate Class 2 transformer or power supply for door strike
• Consult the dealer or an experienced radio/TV
power. Under no circumstances connect a door strike to the
technician for help.
enclosure power supply.
The user is cautioned that changes and
Selection Chart modifications made to the equipment without
approval of the manufacturer could void the user's
Product Code Description authority to operate this equipment.
Number Canada:
SPA1B100-1D10 24 in. x 30 in. (61 cm x 76.2 cm) security control CAN ICES-3 (B)/NMB-3(B);
panel with CK721-A controller, RDR2S-A module, cUL Listed under ULC/ORD-C1076 Proprietary
and one power supply Burglar Alarm Units and Systems
SPA1B200-1D10 24 in. x 30 in. (61 cm x 76.2 cm) security control Europe:
panel with CK721-A controller, two RDR2S-A CE Mark – Johnson Controls, declares that this
modules, and one power supply product is in compliance with the EMC Directive and
the Low Voltage Directive.
Building Technologies & Solutions
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls
All other marks herein are the marks of their respective owners. © 2017 Johnson Controls
2 Security Control Panel Assembly Mounted in a 24 in. x 30 in. Enclosure Installation Instructions
Published in U.S.A. www.johnsoncontrols.comПозиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.