Security Control Panel Assembly
Mounted in a 24 in. x 30 in. Enclosure                                                                              Part No. 24-10613-39, Rev. C
                                                                                                                                    Issued December 2017
Installation Instructions
SPA1B100-1D10, SPA1B200-1D10, SPA1B300-2D10, SPA1B400-2D10

                                                                  Refer to the QuickLIT Web site for the most up-to-date version of this document.

Applications                                                                        Parts Included
The 24 in. x 30 in. Security Control Panel is a pre-wired,                          •   24 in. x 30 in. (61 cm x 76.2 cm) enclosure, Type 1 with keyed
preassembled standard control panel and enclosure that contains a                       lock, door tamper switch, and battery support brackets
CK721-A network controller and/or S300-DIN-RDR2SA (also called                      •   CK721-A network controller and up to four RDR2S-A two-door
RDR2S-A) modules. The control panel is shipped complete, mounted                        interface modules
in a steel enclosure. The panel is equipped with the required number                •   One or two S300-DIN-L-PS 24 VDC, 5 A power supplies
of 120 VAC/24 VDC power supplies. The power supply has
Uninterruptible Power Supply (UPS) capability with the addition of
factory-wired gel cell batteries (S300-BAT), which are sold separately.
These enclosures are designed specifically for security control
requirements, with battery brackets that do not need to be removed to
install the batteries, a lift-off door, a pre-wired door tamper switch, and
a lockable door with key. Space is reserved on specific models for the
addition of future components.
Repair Information
If the Security Control Panel Assembly fails to operate within its
specifications, replace the failed component. Contact Global Security
Solutions Technical Support at (866) 893-0423 or (414) 524-1214, or
by email at support.globalsecuritysolutions@jci.com. End users can
contact their local branch or authorized dealer. For the nearest office,
visit http://www.johnsoncontrols.com/location-finder.
Refer to the Security Enclosure Components Catalog Page
(LIT-1900572) to order components separately.                                                   Figure 1: Security Control Panel Mounted in a
                                                                                                           24 in. x 30 in. Enclosure

Cable Requirements
 Description                             Recommended Cable Type1, 2                                    Maximum Segment Length
 CK721-A: RS485A, RS485B                 Listed, 22 AWG, stranded, copper, hook-up wire                Limited to within cabinet.
 RDR2S-A: RS485+/-
                                         Listed, 18 AWG, 3-conductor, stranded, shielded, copper       4,000 ft (1,219 m) maximum
 CK721-A: ICOM1, ICOM2                   Belden® 8442, 22 AWG, 1 twisted pair, stranded,               500 ft (152 m)
 RDR2S-A: Door Contact                   unshielded, copper
 CK721-A: OUT1                           Belden 9740, 18 AWG, 1 twisted pair, stranded,                Depends on power requirements of the device. Voltage to
 RDR2S-A: Door Strike, Shunt             unshielded, copper                                            the device must not be reduced more than 10% over the
                                                                                                       18 AWG wire, measured when energized.
 Request to Exit (RDR2S-A only)          Belden 8442, 22 AWG, 1 twisted pair, stranded,                500 ft (152 m)
                                         unshielded, copper
 Reader Power (RDR2S-A only)             Belden 9740, 18 AWG, 1 twisted pair, stranded,                Refer to reader manufacturer’s specification for power
                                         unshielded, copper                                            requirements.
 Reader Data0/Data1                      Belden 9744, 22 AWG, 2 twisted pairs, stranded,               500 ft (152 m). Refer to reader manufacturer’s
 (RDR2S-A only)                          unshielded, copper                                            specification for data requirements.
 RS232 A, RS232 B                        Listed DB9 F/F AT Null Modem cable                            25 ft (7 m). Cable must remain in the same room as the
                                                                                                       CK721-A.
 Ethernet                                Listed, Category 5, 24 AWG, solid, 2 pair or 4 pair type      354 ft (100 m). Cable, RJ45 connector, and RJ45 crimp
                                                                                                       tool to be supplied by customer.

1.   All data cables should be physically separated from power lines. If conduit is used, do not run data cables in the same conduit as power cables or certain door
     strike cables, such as strike voltage greater than 42 V or magnetic door locks without Electromagnetic Interference (EMI) suppression. All cables must conform
     with National Electrical Code, NFPA 70; or for Canadian installations, refer to the Canadian Electric Code C22.1.
2.   Shielded cable is not required but is strongly recommended to minimize the effects of electromagnetic interference or radio frequency noise.

UL 294 Performance Levels
                                         Destructive Attack             Line Security               Endurance                  Standby Power
 SPA1B100-1D10                           Level I                        Level II                    Level IV                   Level II
 SPA1B200-1D10                           Level I                        Level II                    Level IV                   Level II
 SPA1B300-2D10                           Level I                        Level II                    Level IV                   Level II
 SPA1B400-2D10                           Level I                        Level II                    Level IV                   Level II

                           Security Control Panel Assembly Mounted in a 24 in. x 30 in. Enclosure Installation Instructions                                       1
Mounting and Connecting the Panels                                                         Product Code         Description
                                                                                           Number
•    Mount the panel on a wall or other mounting surface located in a
     restricted-access area.                                                               SPA1B300-2D10        24 in. x 30 in. (61 cm x 76.2 cm) security control
•    The horizontal distance between the mounting holes is 16.75 in.                                            panel with CK721-A controller, three RDR2S-A
     (42.5 cm); the vertical distance is 27.5 in. (69.9 cm). Mounting                                           modules, and two power supplies
     hole diameter is 0.436 in. (1.1 cm).                                                  SPA1B400-2D10        24 in. x 30 in. (61 cm x 76.2 cm) security control
•    Ensure the door can swing fully open.                                                                      panel with CK721-A controller, four RDR2S-A
•    Mount the panel in a location where airflow is uninhibited over the                                        modules, and two power supplies
     exposed surfaces.
•    Remove the back plate before securing the panel to the mounting
     surface and reinstall it when mounting is complete.                                   Technical Specification
AC Power Connection                                                                        Security Control Panel Assembly Mounted in a 24 in. x 30 in.
                                                                                           Enclosure
•    Put the AC                                            Wired at
     power wiring                                                                          Electrical Rating   SPA1B100-1D10: 120 VAC, 1.8 A, 50/60 Hz
                       To AC power
                                                           the factory
                                             BLU
                               G
     through a              N                                                                                  SPA1B200-1D10: 120 VAC, 1.8 A, 50/60 Hz
                                                   BRN
                               BLU
     knockout.              L                                                                                  SPA1B300-2D10: 120 VAC, 3.6 A, 50/60 Hz
                                                    N L     L = Line
                       source
                               BRN
•    Connect the AC                                                                                            SPA1B400-2D10: 120 VAC, 3.6 A, 50/60 Hz
                                                            N = Neutral
     power wiring to          TB-1           Power supply G = Ground                       Enclosure Rating    NEMA Type 1
     terminal block
     TB-1.                                                                                 Ambient Operating   32 to 122°F (0 to 50°C), 10 to 85% RH,
•    Do not connect the DC power cable to the module until all wiring is                   Condition           noncondensing
     complete                                                                              Dimensions (Width   24 in. x 30 in. x 6.62 in.
                                                                                           x Height x Depth)   (61 cm x 76.2 cm x 16.8 cm)
                 WARNING: Risk of Electric Shock.                                          Ambient Storage     -4 to 158°F (-20 to 70°C), 5 to 95% RH,

        !
                 Disconnect the power supply before making                                 Condition           noncondensing
                 electrical connections. Contact with components
                                                                                           Compliance          United States:
                 carrying hazardous voltage can cause electric shock                                           UL Listed under UL 1076 for Proprietary Burglar
                 and may result in severe personal injury or death.                                            Alarm Units and Systems, and under UL 294 for
                                                                                                               Access Control Systems Units;
S300-BAT Battery Connection                                                                                    This equipment has been tested and found to
                                                                                                               comply with the limits for a Class B digital device,
The optional S300-BAT feature                                                                                  pursuant to Part 15 of the FCC rules. These limits
                                       RED
                                                WHT             BLK
uses two PowerSonic, Model                                                                                     are designed to provide reasonable protection
PS-1270, 12 VDC, 7 Ah, sealed           +    -       +      -         + - + -      G N L                       against harmful interference in a residential
lead acid batteries per power                                               DC                                 installation. This equipment generates, uses and
                                                                      BAT
                                                                                  HIGH
supply. The batteries should be          B-1A            B-1B               OUT   VOLT
                                                                                  AGE                          can radiate radio frequency energy and, if not
replaced every three years to                                                                                  installed and used in accordance with the
                                                                            PS-1
ensure proper operation.                                                                                       instructions, may cause harmful interference to
The RED (+), BLK (-), and                                                                                      radio communications. However, there is no
                                       RED
                                                WHT             BLK                                            guarantee that interference will not occur in a
WHT cables are provided with
the enclosure.                                                                                                 particular installation. If this equipment does cause
                                        +    -       +      -         + - + -      G N L
                                                                                                               harmful interference to radio or television reception,
Replace the batteries whether                                               DC
                                                                      BAT
                                                                                  HIGH
                                         B-2A            B-2B                                                  which can be determined by turning the equipment
or not they have been placed                                                OUT   VOLT
                                                                                  AGE
                                                                                                               off and on, the user is encouraged to try to correct
into use by an AC power                                                     PS-2                               the interference by one or more of the following
failure. Observe the polarity                                                                                  measures:
when connecting the batteries.                                                                                 • Reorient or relocate the receiving antenna.
                                                                                                               • Increase the separation between the equipment
Field Devices                                                                                                     and receiver.
                                                                                                               • Connect the equipment into an outlet on a circuit
For information on wiring the CK721-A controller or the RDR2S-A
                                                                                                                  different from that to which the receiver is
module, refer to the documentation provided with these devices.
                                                                                                                  connected.
Use a separate Class 2 transformer or power supply for door strike
                                                                                                               • Consult the dealer or an experienced radio/TV
power. Under no circumstances connect a door strike to the
                                                                                                                  technician for help.
enclosure power supply.
                                                                                                               The user is cautioned that changes and
Selection Chart                                                                                                modifications made to the equipment without
                                                                                                               approval of the manufacturer could void the user's
    Product Code           Description                                                                         authority to operate this equipment.
    Number                                                                                                     Canada:
    SPA1B100-1D10          24 in. x 30 in. (61 cm x 76.2 cm) security control                                  CAN ICES-3 (B)/NMB-3(B);
                           panel with CK721-A controller, RDR2S-A module,                                      cUL Listed under ULC/ORD-C1076 Proprietary
                           and one power supply                                                                Burglar Alarm Units and Systems
    SPA1B200-1D10          24 in. x 30 in. (61 cm x 76.2 cm) security control                                  Europe:
                           panel with CK721-A controller, two RDR2S-A                                          CE Mark – Johnson Controls, declares that this
                           modules, and one power supply                                                       product is in compliance with the EMC Directive and
                                                                                                               the Low Voltage Directive.

                                                                                                                   Building Technologies & Solutions
                                                                                                           507 E. Michigan Street, Milwaukee, WI 53202
                                                            Metasys® and Johnson Controls® are registered trademarks of Johnson Controls
                                                   All other marks herein are the marks of their respective owners. © 2017 Johnson Controls