Security Control Panel Assembly
Mounted in a 20 in. x 30 in. Enclosure Part No. 24-10638-4, Rev. A
Issued March, 2012
Installation Instructions
SPA1D10011G10, SPA0D10011G10, SPA1D100-1G10, SPA0D100-1G10
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Applications Mounting and Connecting the Panels
The 20 in. x 30 in. Security Control Panel is a pre-wired, • Mount the panel on a wall or other mounting surface located in a
preassembled standard control panel and enclosure that contains one restricted-access area.
S300-DIN-RDR8S (also called RDR8S) module, and , optionally, a • Use the mounting template supplied with the panel.
CK721-A network controller. The control panel is shipped complete, • The horizontal distance between the mounting holes is 17 in.
(43.2 cm); the vertical distance is 27.9 in. (70.9 cm). Mounting
mounted in a steel enclosure. The panel is equipped with a 120 VAC/
hole diameter is 0.436 in. (1.1 cm).
24 VDC power supply mounted on the panel door. The power supply • Ensure the door can swing fully open.
has Uninterruptible Power Supply (UPS) capability. Using the factory • Mount the panel in a location where airflow is uninhibited over the
cables, the UPS function is activated by connecting batteries (S300- exposed surfaces.
BAT). These enclosures are designed specifically for door access • Remove the back plate before securing the panel to the mounting
control for up to 8 doors, with battery brackets, a wiring trough for surface and reinstall it when mounting is complete.
excess cables, a lift-off door, 5 A circuit breaker for controllers, • Leave the 2 black plastic button caps in place until all pipe or
channels for wiring routing, quick disconnects for power, a pre-wired conduit connections are completed. The button caps prevent dust
and metal chips from accidently getting into the cabinet
door tamper switch, and a lockable door with key. electronics.
Repair Information
If the Security Control Panel Assembly fails to operate within its
specifications, replace the failed component. For a replacement,
contact the nearest Johnson Controls® representative.
Refer to the Security Enclosure Components Catalog Page
(LIT-1900572) to order components separately.
Parts Included
• 20 in. x 30 in. (50.8 cm x 76.2 cm) enclosure, Type 1 with keyed
lock, 120 VAC outlet (optional), 5 A circuit breaker, door tamper
switch, and battery support brackets
• CK721-A network controller (optional) and one RDR8S eight-door
interface module
• One S300-DIN-L-PS 24 VDC, 5 A power supply
Figure 1: Security Control Panel Mounted in a
20 in. x 30 in. Enclosure
Cable Requirements
Description Recommended Cable Recommended Composite Maximum Segment Length
Type1, 2 Cable Type1
CK721-A: RS485A, RS485B Listed, 18 AWG, 3-conductor, Listed, 18 AWG, 3-conductor, 4,000 ft (1,219 m) maximum
RDR8S: RS485+/- stranded, shielded, copper stranded, shielded, copper
CK721-A: ICOM1, ICOM2 Belden® 8761, 22 AWG, 1 twisted 500 ft (152 m)
RDR8S: Door Contact pair, stranded, unshielded, copper
CK721-A: OUT1 Belden 8760, 18 AWG, 1 twisted Depends on power requirements of the device. Voltage
RDR8S: Door Strike, Shunt pair, stranded, unshielded, copper to the device must not be reduced more than 10% over
the 18 AWG wire, measured when energized.
Request to Exit Belden 8761, 22 AWG, 1 twisted Belden B558AFS Shielded Riser 500 ft (152 m)
(RDR8S only) pair, stranded, unshielded, copper Rated or Belden B658AFS
Shielded Plenum Rated
Reader Power Belden 8760, 18 AWG, 1 twisted Refer to reader manufacturer’s specification for power
(RDR8S only) pair, stranded, unshielded, copper requirements.
Reader Data0/Data1 Belden 8723, 22 AWG, 2 twisted 500 ft (152 m). Refer to reader manufacturer’s
(RDR8S only) pairs, stranded, shielded, copper specification for data requirements.
RS232 A, RS232 B Listed DB9 F/F AT Null Modem Listed DB9 F/F AT Null Modem 25 ft (7 m). Cable must remain in the same room as the
cable cable CK721-A.
Ethernet Listed, Category 5, 24 AWG, solid, Listed, Category 5, 24 AWG, solid, 354 ft (100 m). Cable, RJ45 connector, and RJ45 crimp
2 pair or 4 pair type 2 pair or 4 pair type tool to be supplied by customer.
1. All data cables should be physically separated from power lines. If conduit is used, do not run data cables in the same conduit as power cables or certain door
strike cables, such as strike voltage greater than 30 V or magnetic door locks without Electromagnetic Interference (EMI) suppression. All cables must conform
with National Electrical Code, NFPA 70; or for Canadian installations, refer to the Canadian Electric Code C22.1.
2. Shielded cable is not required but is strongly recommended to minimize the effects of electromagnetic interference or radio frequency noise.
Security Control Panel Assembly Mounted in a 20 in. x 30 in. Enclosure Installation Instructions 1
Door Termination Selection Chart
• Terminate door 1 to 4 first, since the connectors are located at the back
rows. Product Code Description
• Single Door Connector Termination (typical of 8): Number
SPA1D10011G10 20 in. x 30 in. (50.8 cm x 76.2 cm) security control
Output side Input side panel with a CK721-A controller, an RDR8S module, a
5 A circuit breaker, a 120 VAC outlet, and a power
Door Strike NO Contact Door Strike supply
Door Strike Common Door Strike Common
Door Strike NC Contact Request to Exit SPA0D10011G10 20 in. x 30 in. (50.8 cm x 76.2 cm) security control
Shunt NO Contact Red LED panel with an RDR8S module, a 5 A circuit breaker, a
120 VAC outlet, and a power supply
Shunt Common LED Common
Shunt NC Contact Green LED SPA1D100-1G10 20 in. x 30 in. (50.8 cm x 76.2 cm) security control
Input Tamper Reader Power (+12 VDC) panel with a CK721-A controller, an RDR8S module, a
Input Common Power Common 5 A circuit breaker, and a power supply
Input Spare Data 0/RS-485 SPA0D100-1G10 20 in. x 30 in. (50.8 cm x 76.2 cm) security control
Data 1/RS-485 panel with an RDR8S module, a 5 A circuit breaker,
and a power supply
AC Power Connection
• Put the AC Technical Specification
power wiring GREEN
To AC G Wired at
through a power N
BLUE the factory Security Control Panel Assembly Mounted in a 20 in. x 30 in.
knockout. source L
BROWN Enclosure
• Connect the AC
TB-1 L = Line Electrical Rating SPA1D10011G10: 120 VAC, 1.8 A, 50/60 Hz
power wiring to
N = Neutral SPA0D10011G10: 120 VAC, 1.8 A, 50/60 Hz
terminal block
G = Ground SPA1D100-1G10: 120 VAC, 1.8 A, 50/60 Hz
TB-1.
SPA0D100-1G10: 120 VAC, 1.8 A, 50/60 Hz
Enclosure Rating NEMA Type 1
WARNING: Risk of Electric Shock.
!
Disconnect the power supply before making Ambient Operating 32 to 122°F (0 to 50°C), 10 to 85% RH,
electrical connections. Contact with components Condition noncondensing
carrying hazardous voltage can cause electric shock Dimensions (Width 20 in. x 30 in. x 7.5 in.
and may result in severe personal injury or death. x Height x Depth) (50.8 cm x 76.2 cm x 19.1 cm)
Ambient Storage -4 to 158°F (-20 to 70°C), 5 to 95% RH,
S300-BAT Battery Connection Condition noncondensing
The optional S300-BAT feature Compliance United States:
RED
WHT BLK
uses two PowerSonic, Model UL Listed under UL 1076 for Proprietary Burglar
PS-1270, 12 VDC, 7 Ah, + - + - GNL
Alarm Units and Systems, and under UL 294 for
sealed lead acid batteries per + - + - Access Control Systems Units;
DC
BAT
HIGH
power supply. To ensure B-1A B-1B OUT VOLT
AGE
FCC compliant to the limits for a Class B digital
proper operation, the batteries device, pursuant to Part 15 of the FCC rules
should be replaced every three PS-1
Canada:
years whether or not they have
been placed into use by an AC Class B digital apparatus, complies with Canadian
power failure. ICES-003;
cUL Listed for Signaling Appliance
The RED (+), BLK (-), and WHT cables are provided with the
enclosure. Observe the polarity when connecting the batteries. Europe:
CE Mark – Johnson Controls, Inc., declares that this
Field Devices product is in compliance with the essential
requirements and other relevant provisions of the
For information on wiring the CK721-A controller or the RDR8S
EMC Directive 2004/108/EC and LVD 2006/95/EC.
module, refer to the documentation provided with these devices.
Use a separate Class 2 transformer or power supply for door strike Australia and New Zealand:
power. Under no circumstances connect a door strike to the C-Tick Mark, Australia/NZ Emissions Compliant
enclosure power supply.
Installation of Ferrite Clamps for CE Compliance
• Clamp the ferrite clamp
provided with the panel
to the panel input power
at the circuit breaker
(see the left picture).
• Wrap the Ethernet cable
once around the clamp,
and clamp it to the cable
(see the right picture).
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2012 Johnson Controls, Inc.
2 Security Control Panel Assembly Mounted in a 20 in. x 30 in. Enclosure Installation Instructions