Security Control Panel Assembly
Mounted in a 20 in. x 30 in. Enclosure                                                                                Part No. 24-10638-4, Rev. A
                                                                                                                                      Issued March, 2012
Installation Instructions
SPA1D10011G10, SPA0D10011G10, SPA1D100-1G10, SPA0D100-1G10

                                                                    Refer to the QuickLIT Web site for the most up-to-date version of this document.

Applications                                                                         Mounting and Connecting the Panels
The 20 in. x 30 in. Security Control Panel is a pre-wired,                           •   Mount the panel on a wall or other mounting surface located in a
preassembled standard control panel and enclosure that contains one                      restricted-access area.
S300-DIN-RDR8S (also called RDR8S) module, and , optionally, a                       •   Use the mounting template supplied with the panel.
CK721-A network controller. The control panel is shipped complete,                   •   The horizontal distance between the mounting holes is 17 in.
                                                                                         (43.2 cm); the vertical distance is 27.9 in. (70.9 cm). Mounting
mounted in a steel enclosure. The panel is equipped with a 120 VAC/
                                                                                         hole diameter is 0.436 in. (1.1 cm).
24 VDC power supply mounted on the panel door. The power supply                      •   Ensure the door can swing fully open.
has Uninterruptible Power Supply (UPS) capability. Using the factory                 •   Mount the panel in a location where airflow is uninhibited over the
cables, the UPS function is activated by connecting batteries (S300-                     exposed surfaces.
BAT). These enclosures are designed specifically for door access                     •   Remove the back plate before securing the panel to the mounting
control for up to 8 doors, with battery brackets, a wiring trough for                    surface and reinstall it when mounting is complete.
excess cables, a lift-off door, 5 A circuit breaker for controllers,                 •   Leave the 2 black plastic button caps in place until all pipe or
channels for wiring routing, quick disconnects for power, a pre-wired                    conduit connections are completed. The button caps prevent dust
                                                                                         and metal chips from accidently getting into the cabinet
door tamper switch, and a lockable door with key.                                        electronics.
Repair Information
If the Security Control Panel Assembly fails to operate within its
specifications, replace the failed component. For a replacement,
contact the nearest Johnson Controls® representative.
Refer to the Security Enclosure Components Catalog Page
(LIT-1900572) to order components separately.

Parts Included
•    20 in. x 30 in. (50.8 cm x 76.2 cm) enclosure, Type 1 with keyed
     lock, 120 VAC outlet (optional), 5 A circuit breaker, door tamper
     switch, and battery support brackets
•    CK721-A network controller (optional) and one RDR8S eight-door
     interface module
•    One S300-DIN-L-PS 24 VDC, 5 A power supply

                                                                                                 Figure 1: Security Control Panel Mounted in a
                                                                                                            20 in. x 30 in. Enclosure
Cable Requirements
    Description                 Recommended Cable                      Recommended Composite                Maximum Segment Length
                                Type1, 2                               Cable Type1
    CK721-A: RS485A, RS485B     Listed, 18 AWG, 3-conductor,           Listed, 18 AWG, 3-conductor,         4,000 ft (1,219 m) maximum
    RDR8S: RS485+/-             stranded, shielded, copper             stranded, shielded, copper
    CK721-A: ICOM1, ICOM2       Belden® 8761, 22 AWG, 1 twisted                                             500 ft (152 m)
    RDR8S: Door Contact         pair, stranded, unshielded, copper
    CK721-A: OUT1               Belden 8760, 18 AWG, 1 twisted                                              Depends on power requirements of the device. Voltage
    RDR8S: Door Strike, Shunt   pair, stranded, unshielded, copper                                          to the device must not be reduced more than 10% over
                                                                                                            the 18 AWG wire, measured when energized.
    Request to Exit             Belden 8761, 22 AWG, 1 twisted         Belden B558AFS Shielded Riser        500 ft (152 m)
    (RDR8S only)                pair, stranded, unshielded, copper     Rated or Belden B658AFS
                                                                       Shielded Plenum Rated
    Reader Power                Belden 8760, 18 AWG, 1 twisted                                              Refer to reader manufacturer’s specification for power
    (RDR8S only)                pair, stranded, unshielded, copper                                          requirements.
    Reader Data0/Data1          Belden 8723, 22 AWG, 2 twisted                                              500 ft (152 m). Refer to reader manufacturer’s
    (RDR8S only)                pairs, stranded, shielded, copper                                           specification for data requirements.
    RS232 A, RS232 B            Listed DB9 F/F AT Null Modem           Listed DB9 F/F AT Null Modem         25 ft (7 m). Cable must remain in the same room as the
                                cable                                  cable                                CK721-A.
    Ethernet                    Listed, Category 5, 24 AWG, solid,     Listed, Category 5, 24 AWG, solid,   354 ft (100 m). Cable, RJ45 connector, and RJ45 crimp
                                2 pair or 4 pair type                  2 pair or 4 pair type                tool to be supplied by customer.

1. All data cables should be physically separated from power lines. If conduit is used, do not run data cables in the same conduit as power cables or certain door
   strike cables, such as strike voltage greater than 30 V or magnetic door locks without Electromagnetic Interference (EMI) suppression. All cables must conform
   with National Electrical Code, NFPA 70; or for Canadian installations, refer to the Canadian Electric Code C22.1.
2. Shielded cable is not required but is strongly recommended to minimize the effects of electromagnetic interference or radio frequency noise.

                            Security Control Panel Assembly Mounted in a 20 in. x 30 in. Enclosure Installation Instructions                                         1
Door Termination                                                                       Selection Chart
•     Terminate door 1 to 4 first, since the connectors are located at the back
      rows.                                                                                Product Code        Description
•     Single Door Connector Termination (typical of 8):                                    Number
                                                                                           SPA1D10011G10       20 in. x 30 in. (50.8 cm x 76.2 cm) security control
                               Output side      Input side                                                     panel with a CK721-A controller, an RDR8S module, a
                                                                                                               5 A circuit breaker, a 120 VAC outlet, and a power
    Door Strike NO Contact                                   Door Strike                                       supply
      Door Strike Common                                     Door Strike Common
    Door Strike NC Contact                                   Request to Exit               SPA0D10011G10       20 in. x 30 in. (50.8 cm x 76.2 cm) security control
         Shunt NO Contact                                    Red LED                                           panel with an RDR8S module, a 5 A circuit breaker, a
                                                                                                               120 VAC outlet, and a power supply
           Shunt Common                                      LED Common
         Shunt NC Contact                                    Green LED                     SPA1D100-1G10       20 in. x 30 in. (50.8 cm x 76.2 cm) security control
               Input Tamper                                  Reader Power (+12 VDC)                            panel with a CK721-A controller, an RDR8S module, a
             Input Common                                    Power Common                                      5 A circuit breaker, and a power supply
                 Input Spare                                 Data 0/RS-485                 SPA0D100-1G10       20 in. x 30 in. (50.8 cm x 76.2 cm) security control
                                                             Data 1/RS-485                                     panel with an RDR8S module, a 5 A circuit breaker,
                                                                                                               and a power supply
AC Power Connection
•    Put the AC                                                                        Technical Specification
     power wiring                                       GREEN
                                 To AC           G                    Wired at
     through a                   power           N
                                                        BLUE          the factory          Security Control Panel Assembly Mounted in a 20 in. x 30 in.
     knockout.                   source          L
                                                        BROWN                              Enclosure
•    Connect the AC
                                                TB-1                  L = Line             Electrical Rating      SPA1D10011G10: 120 VAC, 1.8 A, 50/60 Hz
     power wiring to
                                                                      N = Neutral                                 SPA0D10011G10: 120 VAC, 1.8 A, 50/60 Hz
     terminal block
                                                                      G = Ground                                  SPA1D100-1G10: 120 VAC, 1.8 A, 50/60 Hz
     TB-1.
                                                                                                                  SPA0D100-1G10: 120 VAC, 1.8 A, 50/60 Hz
                                                                                           Enclosure Rating       NEMA Type 1
                   WARNING: Risk of Electric Shock.

         !
                   Disconnect the power supply before making                               Ambient Operating      32 to 122°F (0 to 50°C), 10 to 85% RH,
                   electrical connections. Contact with components                         Condition              noncondensing
                   carrying hazardous voltage can cause electric shock                     Dimensions (Width      20 in. x 30 in. x 7.5 in.
                   and may result in severe personal injury or death.                      x Height x Depth)      (50.8 cm x 76.2 cm x 19.1 cm)
                                                                                           Ambient Storage        -4 to 158°F (-20 to 70°C), 5 to 95% RH,
S300-BAT Battery Connection                                                                Condition              noncondensing

The optional S300-BAT feature                                                              Compliance             United States:
                                          RED
                                      WHT     BLK
uses two PowerSonic, Model                                                                                        UL Listed under UL 1076 for Proprietary Burglar
PS-1270, 12 VDC, 7 Ah,                            + - + - GNL
                                                                                                                  Alarm Units and Systems, and under UL 294 for
sealed lead acid batteries per   + -     + -                                                                      Access Control Systems Units;
                                                                          DC
                                                                    BAT
                                                                                HIGH
power supply. To ensure          B-1A    B-1B                             OUT   VOLT
                                                                                AGE
                                                                                                                  FCC compliant to the limits for a Class B digital
proper operation, the batteries                                                                                   device, pursuant to Part 15 of the FCC rules
should be replaced every three                           PS-1
                                                                                                                  Canada:
years whether or not they have
been placed into use by an AC                                                                                     Class B digital apparatus, complies with Canadian
power failure.                                                                                                    ICES-003;
                                                                                                                  cUL Listed for Signaling Appliance
The RED (+), BLK (-), and WHT cables are provided with the
enclosure. Observe the polarity when connecting the batteries.                                                    Europe:
                                                                                                                  CE Mark – Johnson Controls, Inc., declares that this
Field Devices                                                                                                     product is in compliance with the essential
                                                                                                                  requirements and other relevant provisions of the
For information on wiring the CK721-A controller or the RDR8S
                                                                                                                  EMC Directive 2004/108/EC and LVD 2006/95/EC.
module, refer to the documentation provided with these devices.
Use a separate Class 2 transformer or power supply for door strike                                                Australia and New Zealand:
power. Under no circumstances connect a door strike to the                                                        C-Tick Mark, Australia/NZ Emissions Compliant
enclosure power supply.

                                                                                       Installation of Ferrite Clamps for CE Compliance
                                                                                       •     Clamp the ferrite clamp
                                                                                             provided with the panel
                                                                                             to the panel input power
                                                                                             at the circuit breaker
                                                                                             (see the left picture).
                                                                                       •     Wrap the Ethernet cable
                                                                                             once around the clamp,
                                                                                             and clamp it to the cable
                                                                                             (see the right picture).

                                                                                                                                    Building Efficiency
                                                                                                           507 E. Michigan Street, Milwaukee, WI 53202
                                                         Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                                All other marks herein are the marks of their respective owners. © 2012 Johnson Controls, Inc.