Security Control Panel Assembly
Mounted in a 20 in. x 24 in. Enclosure Part No. 24-10613-12, Rev. C
Issued December 2017
Installation Instructions
SPA1B100-1B10, SPA1B200-1B10
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Applications Parts Included
The 20 in. x 24 in. Security Control Panel is a pre-wired, • 20 in. x 24 in. (50.8 cm x 61 cm) enclosure, Type 1 with keyed
preassembled standard control panel and enclosure that contains a lock, door tamper switch, and battery support brackets
CK721-A network controller and/or S300-DIN-RDR2SA (also called • CK721-A network controller and up to two RDR2S-A two-door
RDR2S-A) modules. The control panel is shipped complete, mounted interface modules
• S300-DIN-L-PS 24 VDC, 5 A power supply
in a steel enclosure. The panel is equipped with the required number
of 120 VAC/24 VDC power supplies. The power supply has
Uninterruptible Power Supply (UPS) capability with the addition of
factory-wired gel cell batteries (S300-BAT), which are sold separately.
These enclosures are designed specifically for security control
requirements, with battery brackets that do not need to be removed to
install the batteries, a lift-off door, a pre-wired door tamper switch, and
a lockable door with key. Space is reserved on specific models for the
addition of future components.
Repair Information
If the Security Control Panel Assembly fails to operate within its
specifications, replace the failed component. Contact Global Security
Solutions Technical Support at (866) 893-0423 or (414) 524-1214, or
by email at support.globalsecuritysolutions@jci.com. End users can
contact their local branch or authorized dealer. For the nearest office,
visit http://www.johnsoncontrols.com/location-finder.
Refer to the Security Enclosure Components Catalog Page Figure 1: Security Control Panel Mounted in a
(LIT-1900572) to order components separately. 20 in. x 24 in. Enclosure
Cable Requirements
Description Recommended Cable Type1, 2 Maximum Segment Length
CK721-A: RS485A, RS485B Listed, 22 AWG, stranded, copper, hook-up wire Limited to within cabinet.
RDR2S-A: RS485+/-
Listed, 18 AWG, 3-conductor, stranded, shielded, copper 4,000 ft (1,219 m) maximum
CK721-A: ICOM1, ICOM2 Belden® 8442, 22 AWG, 1 twisted pair, stranded, 500 ft (152 m)
RDR2S-A: Door Contact unshielded, copper
CK721-A: OUT1 Belden 9740, 18 AWG, 1 twisted pair, stranded, Depends on power requirements of the device. Voltage to
RDR2S-A: Door Strike, Shunt unshielded, copper the device must not be reduced more than 10% over the
18 AWG wire, measured when energized.
Request to Exit (RDR2S-A only) Belden 8442, 22 AWG, 1 twisted pair, stranded, 500 ft (152 m)
unshielded, copper
Reader Power (RDR2S-A only) Belden 9740, 18 AWG, 1 twisted pair, stranded, Refer to reader manufacturer’s specification for power
unshielded, copper requirements.
Reader Data0/Data1 Belden 9744, 22 AWG, 2 twisted pairs, stranded, 500 ft (152 m). Refer to reader manufacturer’s
(RDR2S-A only) unshielded, copper specification for data requirements.
RS232 A, RS232 B Listed DB9 F/F AT Null Modem cable 25 ft (7 m). Cable must remain in the same room as the
CK721-A.
Ethernet Listed, Category 5, 24 AWG, solid, 2 pair or 4 pair type 354 ft (100 m). Cable, RJ45 connector, and RJ45 crimp
tool to be supplied by customer.
1. All data cables should be physically separated from power lines. If conduit is used, do not run data cables in the same conduit as power cables or certain door
strike cables, such as strike voltage greater than 42 V or magnetic door locks without Electromagnetic Interference (EMI) suppression. All cables must conform
with National Electrical Code, NFPA 70; or for Canadian installations, refer to the Canadian Electric Code C22.1.
2. Shielded cable is not required but is strongly recommended to minimize the effects of electromagnetic interference or radio frequency noise.
UL 294 Performance Levels
Destructive Attack Line Security Endurance Standby Power
SPA1B100-1B10 Level I Level II Level IV Level II
SPA1B200-1B10 Level I Level II Level IV Level II
Security Control Panel Assembly Mounted in a 20 in. x 24 in. Enclosure Installation Instructions 1
Mounting and Connecting the Panels Technical Specification
• Mount the panel on a wall or other mounting surface located in a Security Control Panel Assembly Mounted in a 20 in. x 24 in.
restricted-access area.
Enclosure
• The horizontal distance between the mounting holes is 15 in.
(38.1 cm); the vertical distance is 21.88 in. (55.6 cm). Mounting Electrical Rating SPA1B100-1B10: 120 VAC, 1.8 A, 50/60 Hz
hole diameter is 0.31 in. (0.8 cm). SPA1B200-1B10: 120 VAC, 1.8 A, 50/60 Hz
• Ensure the door can swing fully open.
Enclosure Rating NEMA Type 1
• Mount the panel in a location where airflow is uninhibited over the
exposed surfaces. Ambient Operating 32 to 122°F (0 to 50°C), 10 to 85% RH,
• Remove the back plate before securing the panel to the mounting Condition noncondensing
surface and reinstall it when mounting is complete.
Dimensions (Width 20 in. x 24 in. x 6.62 in.
AC Power Connection x Height x Depth) (50.8 cm x 61 cm x 16.8 cm)
• Put the AC Ambient Storage -4 to 158°F (-20 to 70°C), 5 to 95% RH,
Wired at
power wiring Condition noncondensing
To AC power
the factory
BLU
G
through a N Compliance United States:
BRN
BLU
knockout. L N L L = Line UL Listed under UL 1076 for Proprietary Burglar
source
BRN
• Connect the AC N = Neutral Alarm Units and Systems, and under UL 294 for
power wiring to TB-1 Power supply G = Ground Access Control Systems Units;
terminal block This equipment has been tested and found to
TB-1. comply with the limits for a Class B digital device,
• Do not connect the DC power cable to the module until all wiring is pursuant to Part 15 of the FCC rules. These limits
complete are designed to provide reasonable protection
against harmful interference in a residential
installation. This equipment generates, uses and
WARNING: Risk of Electric Shock. can radiate radio frequency energy and, if not
Disconnect the power supply before making installed and used in accordance with the
electrical connections. Contact with components instructions, may cause harmful interference to
carrying hazardous voltage can cause electric shock radio communications. However, there is no
guarantee that interference will not occur in a
and may result in severe personal injury or death. particular installation. If this equipment does cause
harmful interference to radio or television reception,
S300-BAT Battery Connection which can be determined by turning the equipment
off and on, the user is encouraged to try to correct
The optional S300-BAT feature the interference by one or more of the following
RED
WHT BLK
uses two PowerSonic, Model measures:
PS-1270, 12 VDC, 7 Ah, + - + - + - + - GNL • Reorient or relocate the receiving antenna.
sealed lead acid batteries per DC • Increase the separation between the equipment
BAT
HIGH
power supply. The batteries B-1A B-1B OUT VOLT
AGE and receiver.
should be replaced every three
PS-1 • Connect the equipment into an outlet on a circuit
years to ensure proper
different from that to which the receiver is
operation. connected.
The RED (+), BLK (-), and WHT cables are provided with the • Consult the dealer or an experienced radio/TV
enclosure. technician for help.
Replace the batteries whether or not they have been placed into use The user is cautioned that changes and
by an AC power failure. Observe the polarity when connecting the modifications made to the equipment without
batteries. approval of the manufacturer could void the user's
authority to operate this equipment.
Field Devices Canada:
For information on wiring the CK721-A controller or the RDR2S-A CAN ICES-3 (B)/NMB-3(B);
module, refer to the documentation provided with these devices. Use cUL Listed under ULC/ORD-C1076 Proprietary
a separate Class 2 transformer or power supply for door strike power. Burglar Alarm Units and Systems
Under no circumstances connect a door strike to the enclosure
Europe:
power supply.
CE Mark – Johnson Controls, declares that this
Selection Chart product is in compliance with the EMC Directive and
the Low Voltage Directive.
Product Code Description
Number
SPA1B100-1B10 20 in. x 24 in. (50.8 cm x 61 cm) security control
panel with CK721-A controller, RDR2S-A module,
and one power supply
SPA1B200-1B10 20 in. x 24 in. (50.8 cm x 61 cm) security control
panel with CK721-A controller, two RDR2S-A
modules, and one power supply
Building Technologies & Solutions
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls
All other marks herein are the marks of their respective owners. © 2017 Johnson Controls
2 Security Control Panel Assembly Mounted in a 20 in. x 24 in. Enclosure Installation Instructions