Security Control Panel Assembly
Mounted in a 20 in. x 24 in. Enclosure                                                                              Part No. 24-10613-12, Rev. C
                                                                                                                                    Issued December 2017
Installation Instructions
SPA1B100-1B10, SPA1B200-1B10

                                                                  Refer to the QuickLIT Web site for the most up-to-date version of this document.

Applications                                                                        Parts Included
The 20 in. x 24 in. Security Control Panel is a pre-wired,                          •   20 in. x 24 in. (50.8 cm x 61 cm) enclosure, Type 1 with keyed
preassembled standard control panel and enclosure that contains a                       lock, door tamper switch, and battery support brackets
CK721-A network controller and/or S300-DIN-RDR2SA (also called                      •   CK721-A network controller and up to two RDR2S-A two-door
RDR2S-A) modules. The control panel is shipped complete, mounted                        interface modules
                                                                                    •   S300-DIN-L-PS 24 VDC, 5 A power supply
in a steel enclosure. The panel is equipped with the required number
of 120 VAC/24 VDC power supplies. The power supply has
Uninterruptible Power Supply (UPS) capability with the addition of
factory-wired gel cell batteries (S300-BAT), which are sold separately.
These enclosures are designed specifically for security control
requirements, with battery brackets that do not need to be removed to
install the batteries, a lift-off door, a pre-wired door tamper switch, and
a lockable door with key. Space is reserved on specific models for the
addition of future components.
Repair Information
If the Security Control Panel Assembly fails to operate within its
specifications, replace the failed component. Contact Global Security
Solutions Technical Support at (866) 893-0423 or (414) 524-1214, or
by email at support.globalsecuritysolutions@jci.com. End users can
contact their local branch or authorized dealer. For the nearest office,
visit http://www.johnsoncontrols.com/location-finder.
Refer to the Security Enclosure Components Catalog Page                                         Figure 1: Security Control Panel Mounted in a
(LIT-1900572) to order components separately.                                                              20 in. x 24 in. Enclosure

Cable Requirements
 Description                             Recommended Cable Type1, 2                                    Maximum Segment Length
 CK721-A: RS485A, RS485B                 Listed, 22 AWG, stranded, copper, hook-up wire                Limited to within cabinet.
 RDR2S-A: RS485+/-
                                         Listed, 18 AWG, 3-conductor, stranded, shielded, copper       4,000 ft (1,219 m) maximum
 CK721-A: ICOM1, ICOM2                   Belden® 8442, 22 AWG, 1 twisted pair, stranded,               500 ft (152 m)
 RDR2S-A: Door Contact                   unshielded, copper
 CK721-A: OUT1                           Belden 9740, 18 AWG, 1 twisted pair, stranded,                Depends on power requirements of the device. Voltage to
 RDR2S-A: Door Strike, Shunt             unshielded, copper                                            the device must not be reduced more than 10% over the
                                                                                                       18 AWG wire, measured when energized.
 Request to Exit (RDR2S-A only)          Belden 8442, 22 AWG, 1 twisted pair, stranded,                500 ft (152 m)
                                         unshielded, copper
 Reader Power (RDR2S-A only)             Belden 9740, 18 AWG, 1 twisted pair, stranded,                Refer to reader manufacturer’s specification for power
                                         unshielded, copper                                            requirements.
 Reader Data0/Data1                      Belden 9744, 22 AWG, 2 twisted pairs, stranded,               500 ft (152 m). Refer to reader manufacturer’s
 (RDR2S-A only)                          unshielded, copper                                            specification for data requirements.
 RS232 A, RS232 B                        Listed DB9 F/F AT Null Modem cable                            25 ft (7 m). Cable must remain in the same room as the
                                                                                                       CK721-A.
 Ethernet                                Listed, Category 5, 24 AWG, solid, 2 pair or 4 pair type      354 ft (100 m). Cable, RJ45 connector, and RJ45 crimp
                                                                                                       tool to be supplied by customer.

1.   All data cables should be physically separated from power lines. If conduit is used, do not run data cables in the same conduit as power cables or certain door
     strike cables, such as strike voltage greater than 42 V or magnetic door locks without Electromagnetic Interference (EMI) suppression. All cables must conform
     with National Electrical Code, NFPA 70; or for Canadian installations, refer to the Canadian Electric Code C22.1.
2.   Shielded cable is not required but is strongly recommended to minimize the effects of electromagnetic interference or radio frequency noise.

UL 294 Performance Levels
                                         Destructive Attack             Line Security               Endurance                  Standby Power
 SPA1B100-1B10                           Level I                        Level II                    Level IV                   Level II
 SPA1B200-1B10                           Level I                        Level II                    Level IV                   Level II

                            Security Control Panel Assembly Mounted in a 20 in. x 24 in. Enclosure Installation Instructions                                      1
Mounting and Connecting the Panels                                               Technical Specification
•    Mount the panel on a wall or other mounting surface located in a            Security Control Panel Assembly Mounted in a 20 in. x 24 in.
     restricted-access area.
                                                                                 Enclosure
•    The horizontal distance between the mounting holes is 15 in.
     (38.1 cm); the vertical distance is 21.88 in. (55.6 cm). Mounting           Electrical Rating    SPA1B100-1B10: 120 VAC, 1.8 A, 50/60 Hz
     hole diameter is 0.31 in. (0.8 cm).                                                              SPA1B200-1B10: 120 VAC, 1.8 A, 50/60 Hz
•    Ensure the door can swing fully open.
                                                                                 Enclosure Rating     NEMA Type 1
•    Mount the panel in a location where airflow is uninhibited over the
     exposed surfaces.                                                           Ambient Operating    32 to 122°F (0 to 50°C), 10 to 85% RH,
•    Remove the back plate before securing the panel to the mounting             Condition            noncondensing
     surface and reinstall it when mounting is complete.
                                                                                 Dimensions (Width    20 in. x 24 in. x 6.62 in.
AC Power Connection                                                              x Height x Depth)    (50.8 cm x 61 cm x 16.8 cm)

• Put the AC                                                                     Ambient Storage      -4 to 158°F (-20 to 70°C), 5 to 95% RH,
                                                        Wired at
  power wiring                                                                   Condition            noncondensing
                       To AC power
                                                        the factory
                                             BLU
                            G
  through a              N                                                       Compliance           United States:
                                                   BRN
                            BLU
  knockout.              L                       N L     L = Line                                     UL Listed under UL 1076 for Proprietary Burglar
                       source
                            BRN
• Connect the AC                                         N = Neutral                                  Alarm Units and Systems, and under UL 294 for
  power wiring to          TB-1           Power supply G = Ground                                     Access Control Systems Units;
  terminal block                                                                                      This equipment has been tested and found to
  TB-1.                                                                                               comply with the limits for a Class B digital device,
• Do not connect the DC power cable to the module until all wiring is                                 pursuant to Part 15 of the FCC rules. These limits
  complete                                                                                            are designed to provide reasonable protection
                                                                                                      against harmful interference in a residential
                                                                                                      installation. This equipment generates, uses and
                 WARNING: Risk of Electric Shock.                                                     can radiate radio frequency energy and, if not
                 Disconnect the power supply before making                                            installed and used in accordance with the
                 electrical connections. Contact with components                                      instructions, may cause harmful interference to
                 carrying hazardous voltage can cause electric shock                                  radio communications. However, there is no
                                                                                                      guarantee that interference will not occur in a
                 and may result in severe personal injury or death.                                   particular installation. If this equipment does cause
                                                                                                      harmful interference to radio or television reception,
S300-BAT Battery Connection                                                                           which can be determined by turning the equipment
                                                                                                      off and on, the user is encouraged to try to correct
The optional S300-BAT feature                                                                         the interference by one or more of the following
                                      RED
                                       WHT      BLK
uses two PowerSonic, Model                                                                            measures:
PS-1270, 12 VDC, 7 Ah,           + -      + -       + - + - GNL                                       • Reorient or relocate the receiving antenna.
sealed lead acid batteries per                                      DC                                • Increase the separation between the equipment
                                                              BAT
                                                                          HIGH
power supply. The batteries      B-1A      B-1B                     OUT   VOLT
                                                                          AGE                            and receiver.
should be replaced every three
                                                         PS-1                                         • Connect the equipment into an outlet on a circuit
years to ensure proper
                                                                                                         different from that to which the receiver is
operation.                                                                                               connected.
The RED (+), BLK (-), and WHT cables are provided with the                                            • Consult the dealer or an experienced radio/TV
enclosure.                                                                                               technician for help.
Replace the batteries whether or not they have been placed into use                                   The user is cautioned that changes and
by an AC power failure. Observe the polarity when connecting the                                      modifications made to the equipment without
batteries.                                                                                            approval of the manufacturer could void the user's
                                                                                                      authority to operate this equipment.
Field Devices                                                                                         Canada:
For information on wiring the CK721-A controller or the RDR2S-A                                       CAN ICES-3 (B)/NMB-3(B);
module, refer to the documentation provided with these devices. Use                                   cUL Listed under ULC/ORD-C1076 Proprietary
a separate Class 2 transformer or power supply for door strike power.                                 Burglar Alarm Units and Systems
Under no circumstances connect a door strike to the enclosure
                                                                                                      Europe:
power supply.
                                                                                                      CE Mark – Johnson Controls, declares that this
Selection Chart                                                                                       product is in compliance with the EMC Directive and
                                                                                                      the Low Voltage Directive.
    Product Code           Description
    Number
    SPA1B100-1B10          20 in. x 24 in. (50.8 cm x 61 cm) security control
                           panel with CK721-A controller, RDR2S-A module,
                           and one power supply
    SPA1B200-1B10          20 in. x 24 in. (50.8 cm x 61 cm) security control
                           panel with CK721-A controller, two RDR2S-A
                           modules, and one power supply

                                                                                                         Building Technologies & Solutions
                                                                                                 507 E. Michigan Street, Milwaukee, WI 53202
                                                            Metasys® and Johnson Controls® are registered trademarks of Johnson Controls
                                                   All other marks herein are the marks of their respective owners. © 2017 Johnson Controls

2         Security Control Panel Assembly Mounted in a 20 in. x 24 in. Enclosure Installation Instructions

Published in U.S.A.                                                                                                       www.johnsoncontrols.com

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.