LN Series Variable Air Volume (VAV) and Variable Volume
Temperature (VVT) Controllers
  Installation Instructions                                                                Code No. LIT-12011297
                                                                                             Issued November 2017
 LN-VAVLF-2, LN-VAVLN-2, LN-VVTLF-2, LN-VAVCF-2

Application
The LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) controller line is designed to
control various types of Heating, Ventilating, and Air Conditioning (HVAC) equipment, such as baseboards, duct
heaters, multi-stage heaters and fans, coolers, valves, and lights.
The controllers are based on LONWORKS® technology for peer-to-peer communication between controllers and are
LONMARK® network certified.
North American Emissions Compliance
United States

 Compliance Statement (Part 15.19)
 This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
 1. This device may not cause harmful interference, and
 2. This device must accept any interference received, including interference that may cause undesired
    operation.
 Warning (Part 15.21)
 Changes or modifications not expressly approved by the party responsible for compliance could void the user’s
 authority to operate the equipment.

Canada

 The term IC before the certification/registration number only signifies that the Industry Canada technical
 specifications were met.
 Le terme « IC » précédant le numéro d'accréditation/inscription signifie simplement que le produit est conforme
 aux spécifications techniques d'Industry Canada.

                     LN Series Variable Air Volume (VAV) and Variable Volume Temperature
                                   (VVT) Controllers Installation Instructions
                                                       1
Installation
For proper installation and subsequent operation of the LN-VAV/VVT controller, follow these recommendations:
•     Upon unpacking your controller, inspect the contents of the carton for shipping damage. Do not install
      damaged devices.
•     Allow for proper clearance of device casing, wiring terminals, and service pin for easy access, hardware
      configuration, and maintenance. Record the Neuron® ID located on top of the device. You need it for
      commissioning the device.
•     The controllers are designed to operate under the following conditions:
      •   Ambient temperature between 32 to 122°F (0 to 50°C)
      •   Relative humidity from 0 to 90%, noncondensing
•     Ensure proper ventilation of devices and avoid areas where corroding, deteriorating, or explosive vapors,
      fumes, or gasses may be present.

    IMPORTANT: Work in a static-free area. Discharge any static electricity you may have accumulated. Discharge
    static electricity by touching a known, securely grounded object. Do not handle the controller without proper
    protection against static discharge. Use a wrist strap when handling the controller. Secure the wrist strap clamp
    to earth ground.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                            2
Dimensions

            Figure 1:   LN-VAVLF, LN-VAVCF, and LN-VVTLF Controller Dimensions, mm (in.)

                 Figure 2:   LN-VAVLF, LN-VVTLF, and LN-VAVCF Controller Components

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                      3
                                                                          190 [7. 48 ]

                                                                                                      54 [2.13 ]

                         61.5 [2.42]
                                            10                                               11
                                          [0.40]                                           [0.43 ]

                                                                                                                   5 [0.2]
                                                                        High pressure
                                                                                                                    Bracket
                                                                                                                    mouting kit
                                                                            Low pressure

                                                                                                                             26.5 [1.04]
                                                                                            3 mm
                                                                                           0. 12 in

                                                   Units Legend: mm [ inches]

                                       Figure 3:          LN-VAVLN Controller Dimensions, mm (in.)

                                           Figure 4:             LN-VAVLN Controller Components

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                                                     4
Mounting
Location Considerations
Use the provided screws and integrated mounting brackets on the LN-VAVLN-2 controller to mount.
This mounting procedure pertains to the controllers with built-in actuators (LN-VAVLF, LN-VVTLF, and
LN-VAVCF). Units with a damper actuator only have one screw.
The controllers are specially designed for mounting onto an air duct or within a panel using the integrated mounting
collar and the provided screw. This mounting arrangement opposes the torque applied to the damper shaft.
1. Place the controller into position on the damper shaft so wiring connections are easily assessable.
Note: The controller must be fitted onto the damper shaft so the base of the controller is parallel to the VAV box
and perpendicular to the damper shaft). If the damper shaft has an external bushing that prevents the controller
from being mounted flush to the side of the VAV box, ensure the controller is at a right-angle to the shaft to prevent
binding.

 IMPORTANT: Protect the controller from dripping water, condensation, and other moisture. Water or moisture
 could result in an electrical short, which may damage or affect the operation of the controller.

2. Using a power screwdriver, attach the controller to the VAV box with the provided screw through the controller’s
   mounting bracket. You may also mark the screw position on the VAV box, drill a hole, then attach the controller
   to the VAV box.

 IMPORTANT: Do not overtighten the screws. Overtightening may strip the threads and will void the warranty.

3. Locate the damper position by the marking typically found on the end of the damper shaft (Figure 5).

                                             Figure 5: Damper Shaft
                                                     Markings

4. Determine the direction required to close the damper Clockwise (CW) or Counterclockwise (CCW). Turn the
   damper shaft with a pair of pliers to fully close the damper for 90° VAV boxes or fully open the damper for 45°
   or 60° VAV boxes.
5. Press and hold down the Actuator Clutch for Manual Adjustment button and turn the controller’s shaft coupler
   until it touches the mechanical end-stop to either the fully closed position (90° VAV boxes) or the fully open
   position (45° or 60° VAV boxes). See Figure 5.
6. Position mechanical stops:
    a. For 90° VAV boxes: if the damper closes CCW, turn the coupler to the CCW mechanical stop limit. If the
       damper closes CW, turn the coupler to the CW mechanical stop limit. The open mechanical stop is factory
       preset for 90° VAV boxes.
    b. For 45° or 60° VAV boxes: the mechanical stops must be set for both the fully closed and fully open
       damper positions. By installing the controller at the fully open position, the controller provides the open
       mechanical stop for 45° and 60° VAV boxes. The closed damper seal provides the fully closed stop.
7. Tighten the U-Bolt clamp on to the damper shaft using an 8 mm (5/16 in.) wrench or socket. Tighten the bolts
   tween 11 and 15 N·m (100 and 130 lb·in).
8. Test for free damper shaft movement: Press and hold down the Actuator Clutch for Manual Adjustment button
   and manually turn the actuator coupling to ensure the actuator can rotate from fully closed to fully opened
   positions without binding.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                          5
9. Connect the VAV box flow sensor tubing to the controller’s Pressure Sensor Inputs. Create a condensation trap
   in the pneumatic tubing by forming it into a vertical loop.
10. Finalize the installation by rotating the damper to the full open position.

                         Figure 6:    Mounting a VAV or VVT Device on a Damper Shaft

Risk of Personal Injury and Property Damage.
Rotate the damper to the full-open position before starting the air handler. Failure to rotate the damper to the full-
open position may result in damage to the Variable Air Volume (VAV) box or ductwork when the air handler is
started.

Risque de blessure et dégâts matériels.
Faire pivoter le registre pour le placer en position d'ouverture complète avant de démarrer l'unité de traitement
d'air. Le non-respect de cette directive risque d'endommager le caisson de l'unité à volume d'air variable (VAV) ou
le réseau de conduites au démarrage de l'unité de traitement d'air.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                           6
Wiring

    Risk of Electric Shock.
    Disconnect the power supply before making electrical connections to avoid electric shock.

    Risque de décharge électrique.
    Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge
    électrique.

    IMPORTANT: Use copper conductors only. Make all wiring connections in accordance with local, national, and
    regional regulations. Do not exceed the control’s electrical ratings.

Recommendations:
•      Use the removable terminal connectors to make all wiring connections.
•      Disconnect the terminal connectors from the device for wiring.
•      Use a small flat screwdriver to tighten the terminal connector screws once you have inserted the wires.
•      Keep analog type cables (for power, voltage, current inputs, or triac outputs) apart from other types of wiring to
       avoid any ambient noise transmission among wires; however, unswitched power wiring can be in the same
       conduit as the LONWORKS communication cable.
•      The board connectors accept wires or flat cables ranging from 22 to 12 AWG (0.645 - 2.052 mm diameter) per
       pole; however, power cables must remain between 18 and 14 AWG (1.024 - 1.628 mm diameter).
•      The transformer powering the controller must be configured as a floating transformer. Do not ground the
       transformer.
•      Keep all wires away from high-speed data transmission cables (for example, Ethernet).

    IMPORTANT: Do not connect the analog/digital inputs or common terminals to ground (only if otherwise
    stated).

Power Wiring
Device power requirements: 24 VAC +/- 15%, Class 2
Note: To conform to Class 2 requirements in the United States, use transformers of 100 VA at 24 VDC or less to
power the controller.
For power and ground wiring, use the heaviest gauge wire based on a maximum of 14 AWG and a minimum of 18
AWG.
Input Wiring
The LN-VAVLF, LN-VAVCF, and LN-VVTLF controllers have physical connections for four inputs that are software
configurable from within the device’s LNS® plug-in. Each input can be configured for digital, resistive, current, or
voltage signals. You must configure the input types properly in the software plug-in or wizard to ensure proper input
readings.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                             7
Wiring Digital Inputs
Use this input configuration to monitor digital dry contacts, as well as pulsed contacts (LN-VAVCF-2 only).

                                 Figure 7:     Digital Dry Contact (NO and NC)

Resistive 10k ohm Inputs
Use this input configuration to monitor 100k ohm and 1000k ohmsRTDs, 10k ohm Type 2 and Type 3 thermistors,
and potentiometers (10k or 100k ohms on LN-VAVCF-2 only).

                                              RTD /                 U Ix
                                         Ther mis tor               C OM

                                        Figure 8:       RTD/Thermistor Input

                                   Figure 9:     10k ohm Potentiometer Input

When you use a 100k ohm input, keep the wire length short to avoid a possible temperature offset; for example,
18AWG wire, 25 feet (7.6 m) in length creates an offset of 2°F (1.1°C).

Wiring Current Inputs
Current inputs can have a range of 4 to 20 mA. Connect the current input if the transducer is externally powered.
Use a transducer with 2-wire, 4-20 mA. See Figure 10.

                                Figure 10: Current Input - 2 Wire Transducer

Connect the current input if the transducer is powered with 3-wire, 4-20 mA. See Figure 11.

                             Figure 11: Current Input with Internal Power Source

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                           8
For information on selecting mounting locations for the LN Series wireless controllers, refer to the LN Series
Wireless Solution Guide Technical Bulletin
(LIT-12011628).
Mounting the Wireless Receiver
You have three mounting options: on a wall or ceiling with double-sided tape, on a wall or ceiling with mounting
screws, or on a metal enclosure using a
1/2 inch National Pipe Thread (NPT) hub.
Regardless of the mounting method, the wireless receiver should be 16 inches (41 cm) or more away from the
controller or any other network cables.
Wall or Ceiling Mount with Double-Sided Tape
To mount on a wall using double-sided tape, first apply the tape to the back of the receiver and then stick the
receiver onto the desired wall or ceiling location.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                         9
Maintain consistent polarity when connecting controllers and devices to the transformer. Connect the COM of each
controller and each peripheral to the same terminal on the secondary side of the transformer.

                                             Figure 12: Power Wiring

 IMPORTANT: Maintain proper polarity and voltage or current ratings. Improper polarity or exceeding the
 voltage or current ratings will void the warranty.

Connect the current input according to Figure 13 if the transducer is powered by its own power source.

                                    Figure 13: Current Input - Transducer
                                         with Its Own Power Source

Wiring Voltage Inputs
Voltage inputs have a range of 0 to 10 VDC. Connect the voltage input according to Figure 14 if you are using a 3-
wire, 0-10 V transducer.

                                   Transduc er
                                                     0 -10V        UIx
                                          +
                                       C o mmo n                   COM
                                         24V A C

                                                   24V A C

                                      Figure 14: Voltage Input - 3-wire
                                                Transducer

Connect the voltage input according to Figure 15 if the transducer is powered by its own power source.

                               Figure 15: Voltage Input - Transducer with its
                                            own Power Source

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                             10
Output Wiring
The LN VAV/VVT controllers have physical connections for either digital outputs and universal outputs, depending
on the type and model. The power source type for digital outputs is hardware configurable and must be configured
by changing the jumper settings on the printed circuit board. The universal outputs are software configurable.
Note: For a wire length less than 75 ft (23 m), use either a shielded or unshielded 18 AWG wire.
Note: For a wire length up to 200 ft (61 m) long, we recommend using a shielded 18 AWG wire.
Note: The wire should be shielded on the controller side and keep the shield length as short as possible.
Wiring Digital Outputs (DOx)
You can configure the digital outputs as either powered outputs or non-powered outputs. When wiring:
•   the non-powered output type does not have any voltage on the output terminals when the output is active.
    Power must be supplied externally.
•   the powered output type has 24 VAC on the output terminals when the output is active. Power is therefore
    supplied internally by the controller.
Note: The LN VAV/VVT controllers are shipped with all digital outputs configured as powered outputs. Maximum
output current for all digital outputs (powered or non-powered) is 1 A.
DO1 and DO2 share the same C1-2 common terminal and are controlled by a single jumper; therefore, they must
be set identically. Similarly, DO3 and D04 share the same C3-4 common terminal and are controlled by a single
jumper and must be set identically. The jumpers specify whether an internal or external power source is being
used.
If a 24 VAC relay is being controlled, connect the digital output according to Figure 16 (external power supply) and
Figure 17 (internal power supply).
Ground external power supplies as shown in Figure 16 and Figure 17.

                                Figure 16: Digital Output with External Power
                                                    Supply

                                                     DOx              A2

                                  JUMPER             Cx-x             A1

                                 SETTINGS                         24VAC Relay
                                 Figure 17: Digital Output with Internal Power
                                                    Supply

Use an external fuse on the 24 VAC side (secondary side) of the transformer to protect all devices against power
line spikes (Figure 12).

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                            11
If a floating actuator is being controlled, connect the digital output according to Figure 18 and Figure 19.
                                                                                Actuator
                                                          DOx                   ~
                                    JUMPER                Cx-x
                                                                     2 4V A C
                                                          DOx                   ~
                                   SETTINGS
                                 Figure 18: Digital Output with External Power
                                           Supply - Floating Actuator

                                                                                 A ctuator

                                                           DO x                     ~
                                                           Cx -x
                                   JUM PE R
                                                           DO x                     ~
                                  S ETT ING S

                                      Figure 19: Digital Output with Internal
                                         Power Supply - Floating Actuator

Wiring Universal Outputs (UOx)
The universal outputs can be configured to provide either a linear signal ranging from 0 to 10 VDC or a discrete
signal of 0 to 12 VDC.
The discrete signal can be use to generate a Pulse Wave Modulation (PWM) signal or a simple two-state signal.
These outputs are protected by an auto-reset fuse.
Wiring Discrete Outputs
If a 12 VDC relay is being controlled, connect it to a universal output (Figure 21). When a relay with universal
output, a diode be connected in parallel to protect the controller from back-emf current, which occurs when the
relay is turned off. It is recommended to use diodes that are part of the 1N4004x family and place them close to the
relay.

                                       UOx                           A2

                                      COM                            A1

                                                                 12VDC Relay
                                    Figure 21: Discrete 0 or 12 VDC Universal
                                                 Output - Relay

Wiring Voltage Outputs
Connect the 0 to 10 VDC output according to Figure 22.

                                                 UOx               0-10 VDC

                                                COM                Common

                                           Figure 22: Voltage 0 to 10
                                            VDC Universal Output -
                                                Analog Actuator

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                          12
If an analog actuator is being controlled, connect the 0 to 10 VDC output, along with an external 24 VAC power
source, to the analog actuator (Figure 23).

                                                                      Actuator
                                                                        -
                                             COM                      ~ +
                                                           2 4V A C
                                              UOx                     0 - 10 V D C

                                         Figure 23: Voltage 0 to 10 VDC
                                            Universal Output - Analog
                                                    Actuator

Communications Wiring
Approved cable types for LONWORKS communications are 22 AWG (0.65 mm), twisted pair, unshielded. The
LONWORKS communication wire is polarity insensitive, and can be laid out in a bus, star, loop, or free topology. For
loop topology, polarity is important; take special care when connecting the LON network to avoid short circuit.
Note: We recommend the Bus topology network configuration because it allows for easy network troubleshooting
for LONWORKS communication wiring.
Connect both wires to the LON1 and LON2 terminals of the controller. If you are inserting multiple wires in the
terminals, make sure to properly twist wires together prior to inserting them in the terminal connectors (Figure 24).

                                                                 C ontr oller 1
                                                                           L ON1
                                    LON Netw ork
                                                                           L ON2

                                                                 C ontr oller 2
                                                                           L ON1
                                                                           L ON2

                                       Figure 24: Communications WIring

For additional information and detailed explanations on network topology and wire length restrictions, refer to the
Echelon® Junction Box and Wiring Guideline for Twisted Pair LONWORKS Networks
(Part No. 005-0023-01).
Note: Use proper network terminators depending on the type of network topology used. Failure to do so may
result in communication errors between controllers. Do not use multiple gauges of cable on the same
communication bus, as this may also result in communication errors.
Selecting Network Terminators
For bus topology, two network terminators are required
(one at each end of the bus topology channel). For a free topology, one network terminator is required. You can put
it anywhere on the channel.
LN-VSTAT Sensor for VAV Wiring
The LN-VAVLF-2 and LN-VVTLF-2 controllers are compatible with the LN-Sensor line of standard room sensors.
The LN-VAVCF-2 controller does not support the LN-VSTAT sensor. Refer to the LN-VSTAT Installation Instructions
(LIT-12011302).
Networking Guide
To commission a device and add it to a LONWORKS network, you need to use the device plug-in as well as the.xif
and.apb files. To obtain the files:

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                         13
If only one 24 VAC transformer is available, determine the maximum number of VAVs that can be supplied on a
single power cable supplied by a 100 VA transformer, according to the cable’s wire gauge and the total cable length
from Table 1. Avoid installation conditions that fall outside the parameters of Table 1.
Table 1: Maximum Number of VAV Devices on a Power Run
 AWG        Power Run           Maximum Number of              Maximum Number of               Maximum Number of
            Total Cable         Devices at 7 VA per            Devices at 10 VA per            Devices at 15 VA per
            Length              device1                        device2                         device3
 144         75 m (250 feet)                  4                              2                               1
 14          60 m (200 feet)                  5                              3                               2
 14          45 m (150 feet)                  5                              4                               3
 14          30 m (100 feet)                  5                              5                               4
 16          60 m (200 feet)                  3                              2                               1
 16          45 m (150 feet)                  5                              3                               2
 16          30 m (100 feet)                  5                              4                               3
 18          45 m (150 feet)                  3                              2                               1
 18          30 m (100 feet)                  5                              3                               2

1.    Typical VAV with 1 sensor and actuator active. No external loads.
2.    Typical VAV with 1 sensor, 2 triac loads (1.6 VA each), 1 analog output (20 mA), and actuator active.
3.    Typical VAV with 1 sensor, 4 triac loads (1.6 VA each), 2 analog outputs (20 mA each), and actuator active.
4.    Device terminals are not capable of accepting two 14 AWG wires (when daisy-chaining devices). Use a wire nut with a pig
      tail to make such a connection.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                              14
11. Disconnect the power to the controller and remove the jumper.

                                    Figure 25: E-Blank Jumper (J22) Location

12. Reconnect the power. The service LED blinks twice and becomes solid indicating the controller is application-
    less.
13. Load the proper .apb file into the controller.
Note: If the device already exists in the LNS database, you must use the Load or Commission option in LN-
Builder 3 to download the .apb file. Do not use the Replace option.
Wall or Ceiling Mount with Screws
To mount the wireless receiver with screws:
1. Separate the front and back plates on the receiver to open it.
2. Use the mounting holes on the back plate to mark the wall or ceiling location.
3. Drill the holes.
4. Clean the holes, insert wall anchors, and fasten the back plate with the screws.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                       15
Metal Enclosure Mount
To mount onto a metal enclosure:
1. Affix the 1/2 inch NPT hub to the bottom of the Wireless Receiver. Ensure the cap of the NPT hub is undone.
2. Place the Wireless Receiver onto the metal enclosure and align the NPT hub to the hole.
3. Use the cap to tighten the Wireless Receiver onto the enclosure.

                                      Figure 26: Metal Enclosure Mount

Neuron ID and Service Pin
To commission a device and add it to a LONWORKS network, you need the Neuron ID of the device. To obtain the
Neuron ID:
•   manual entry: the Neuron ID address and bar code are located on a sticker on the device.
•   service pin: pressing the service pin on the device broadcasts the Neuron ID on the LONWORKS network.
Memory Erase Jumper
The LN VAV/VVT controllers feature an E-Blank jumper which can be used to erase the Neuron chip. If you load an
incorrect .apb file into the controller, the Neuron chip’s memory becomes corrupt. Use the E-blank jumper to correct
the problem by returning the chip to an application-less state. The E-Blank jumper is labelled J22 on the PCB
board.
To erase the Neuron chip’s memory using the E-Blank jumper:
1. Disconnect the power to the controller.
2. Place a jumper on the pins labelled J22 on the board (Figure 25).
3. Reconnect power to the controller.The amber colored service Light-Emitting Diode (LED) blinks rapidly
   indicating that it is erasing the Neuron chip’s memory. When the light becomes solid (and stops blinking), the
   erase procedure is complete.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                        16
Connecting the Wireless Receiver
Connect the wireless receiver to the controller with the included telephone cable (4P4C modular connectors).
Locate the telephone socket inside the device (Figure 27).

                                            Figure 27: Telephone Socket
                                                      Location

Connecting to the Controller Wireless Port
The wireless-option controllers have a wireless port where you connect the telephone cable. Locate the wireless
port on the bottom of the controller.

                                   Figure 28: Enable Wireless Jumper (J16)

To enable the wireless jumper, remove the jumper J16 between the left and middle Disable pins and connect it
between the middle and right Enable pins.
Disconnecting the Wireless Port
To disconnect the plugged-in telephone cable from the controller’s wireless port, pass a pointed object through the
hole above the wireless port and press on the top of the connector while gently pulling out the cable.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                        17
Typical Variable Air Volume Application Wiring
Diagram
Figure 29 shows the typical power and network connections with a floating actuator output and sensor. Figure 30
shows the typical power and network connections with a two-stage digital output.
                                                                                                                 Sensor

                                                      LON2
                                                      LON1                                   SMRT-
                                                     SMRT-                                   SMRT+
                                                     SMRT+                                   LON1
                                                        UI4                                  LON2
                                                        UI3
                                                       COM
                                                        UI2
                                                        UI1
                                                       UO6
                                                       COM
                                                       UO5
                                                       DO4

                                                       DO3                                            Heating
                                                       DO2                                            Floating
                                                                                                      Actuator
                                                       CO1
                                                     24 VAC
                                        PRESSURE   24V COM
                                        HIGH LOW

                                                                                                                120V/AC

                Figure 29: LN-VAVxx Typical Wiring Diagram and Network Connections -
                              Sensor Input and Floating Actuator Output

                                                                                                                 Sensor

                                                      LON2
                                                      LON1
                                                    SMRT-
                                                    SMRT+                     Connectors
                                                       UI4
                                                       UI3                                 COMMON
                                                      COM                                  TEMP
                                                       UI2                                 SETPOINT
                                                       UI1
                                                      UO6
                                                      COM
                                                      UO5
                                                       DO4

                                                       DO3                                            2-Stage
                                                       DO2                                            Digital
                                                                                                      Output
                                                       DO1
                                                     24 VAC
                                       PRESSURE    24V COM
                                       HIGH LOW

                                                                                                                120V/AC

                Figure 30: LN-VAVxx Typical Wiring Diagram and Network Connections -
                              Sensor Input and Two-Stage Digital Output

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                              18
Troubleshooting
Table 1: Troubleshooting (Part 1 of 2)
 Problem                      Possible Cause                       Solution
 Device is powered but does   Fuse is blown.                       Check the fuse integrity; also ensure the green power LED
 not turn on.                                                      next to the service pin is on.
                              Power supply polarity                Verify consistent polarity is maintained between all
                                                                   controllers and the transformer.
 Device cannot                Absent or incorrect supply           Check power supply voltage between 24 VAC and COM
 communicate on an FTT        voltage                              pins to ensure it is within acceptable limits. Check for a
 network.                                                          tripped fuse or circuit breaker.
                              Overloaded power                     Verify the transformer used is powerful enough to supply all
                              transformer                          controlled devices.
                              Network not wired property           Double-check the wire connections are correct.
                              Absent or incorrect network          Check the network terminators.
                              terminators
 Device communicates well     Network length                       Check that the total wire length does not exceed the
 over a short network but                                          specifications of the FTT User’s Guide.
 does not communicate on a
                              Wire type                            Check that the wire type agrees with the specification of the
 large network.
                                                                   FTT User’s Guide. Verify your wire is UNSHIELDED.
                              Network wiring problem               Verify the wire connections are correct.
                              Absent or incorrect network          Check the network terminators. Incorrect or broken
                              terminators                          terminators make the communication integrity dependent
                                                                   upon a device’s location on the network.
                              Extra capacitance                    Verify that no extra capacitances are connected to the
                                                                   network other than the standard FTT circuit, and a
                                                                   maximum of 3 meter stub (in bus topology).
                              Number of devices on                 The number of devices on a channel should never exceed
                              network segment exceeded             64. Use a router or a repeater in accordance to the FTT
                                                                   User’s Guide.
                              Network traffic                      Query node statistics to check for errors. Use a LON
                                                                   protocol analyzer to check network traffic.
 Hardware input is not        Input wiring problem                 Check that the wiring is correct according to this manual
 reading the correct value.                                        and according to the peripheral device’s manufacturer.
                              Open circuit or short circuit        Using a voltmeter, check the voltage on the input terminal.
                                                                   Short circuit (0 V) and open circuit (10 V).
                              Configuration problem                Using a device configuration plug-in or wizard, check the
                                                                   configuration of the input. Refer to the device’s user guide
                                                                   for additional information.
 Hardware output is not       Output wiring problem                Check that the wiring is correct according to this manual
 operating correctly.                                              and according to the peripheral device’s manufacturer.
                              Configuration problem                Using the device configuration plug-in, check the
                                                                   configuration of the output. refer to the device user’s guide
                                                                   for more information.
                              0-10 V output, 24 VAC                Check the polarity of the 24 VAC power supply connected
                              powered actuator is not              to the actuator while connect to the device. Reverse the 24
                              moving                               VAC wire if necessary. Check the jumper setting for the
                                                                   external power supply as shown in Figure 18.
 Flow sensor is not giving    Tubing connection problem            Verify the tubing is installed properly and that the tubing is
 proper readings.                                                  not bent. Ensure the high and low pressure sensors are not
                                                                   inverted.
                              Device is not calibrated             Recalibrate the VAV controller. Refer to the controller user
                              properly                             guide for more information about VAV controller calibration.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                              19
Table 1: Troubleshooting (Part 2 of 2)
 Problem                         Possible Cause                       Solution
 Damper is not opening or        Mechanical stops not in              The two mechanical stops must be positioned to stop the
 closing properly                proper position                      damper motion when it is completely closed and
                                                                      completely opened. The mechanical stops can be moved
                                                                      by increments of 5°.
                                 Rotation time not set up             Ensure the external damper drive time is set to the correct
                                 correctly for external damper        value (in the plug-in or wizard).
                                 VAV still in Calibration mode        Complete the calibration process in LN-Builder 3.
                                 Controller in Override               Set the Override OFF in the object manage screen in
                                                                      LN-Builder 3.

Service LED
Table 2: Service LED (Amber Color)
 Service LED                                        Operation Status
 OFF (does not apply to LN-VAVCF-2)                 The device is in normal operation.
 Repeated Blink (LN-VAVCF-2 only)                   The device is in normal operation. The LED blinks according to the device
                                                    code execution time.
 On                                                 The device is application-less. Reload the application file (.apb).
 Slow Blink                                         The device is unconfigured. Commission the device.
 (1 second On, 1 second Off)
 Fast Blink                                         Watchdog time out. Application corrupted. Use the E-Blank jumper to
 (0.3 second On, 1 second Off)                      wipe the Neuron chip’s memory. Then load the proper .apb into the device
                                                    using a LN-Builder 3.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                                 20
Technical Specification
Table 3: LN-VAVLF, LN-VAVLN, and LN-VVTLF (Part 1 of 2)
Product Codes                   LN-VAVLF-2, LN-VAVLN-2, and LN-VVTLF-2
Power Requirement               Voltage: 24 VAC/DC; +/- 15%, 50/60 Hz, Class 2
                                Protection: 3 A user-replaceable fuse for triac when using the internal power supply
                                Consumption: 18 VA
                                Maximum Consumption: 70 VA if internal power supply is used
Ambient Storage Conditions      Ambient Operating Temperature: 0 to 50°C, (32 to 122°F)
                                Ambient Storage Temperature: -20 to 50°C, (-4 to 122°F)
                                Ambient Relative Humidity: 0 to 90% noncondensing
General                         LONMARK Functional Profile: Space Comfort Controller (SCC) VAV #8502
                                Processor: Neuron® 3150™, 8 bits, 10 MHz
                                Memory: Nonvolatile Flash 64k (APB application)
                                Media Channel: TP/FT-10; 78 Kbps
                                Communication: LonTalk® protocol
                                LONMARK Interoperability Guidelines: Version 3.4
Enclosure                       Material: FR/ABS Resin
                                Dimensions (with screws):
                                   LN-VAVLN-2: 4.8 x 5.9 x 2.5 in. (122.7 x 149.1 x 63 mm)
                                   LN-VAV-LF-2/LN-VVT-LF-2: 4.8 x 8.4 x 2.5 in. (122.7 x 214.3 x 63 mm)
                                Shipping Weight:
                                   LN-VAVLN-2: 0.92 lb (0.42 kg)
                                   LN-VAV-LF-2/LN-VVT-LF-2: 2.30 lb (1.05 kg)
Inputs                          Universal software configurable
                                Input Types:
                                    Digital: Dry Contact
                                   Analog Voltage: 0 to 10 VDC
                                   Analog current: 4 to 20 mA with 249 ohmsexternal resistor (wired in parallel)
                                   Pulse: Dry contact; 500 milliseconds minimum ON/OFF
                                   Resistor Support:
                                     Thermistor: 10kohms Type 2, Type 3 (10k ohms at 25°C [77°F])
                                       Range: -40° to 153°C (-40° to 302°F)
                                     Platinum: PT1000 (1k ohms at 0°C [32°F])
                                       Range: -40 to 150°C (-40 to 302°F)
                                       PT100 (100 ohms at 0°C [32°F])
                                       Range: -40 to 135°C (-40 to 275°F)
                                      Potentiometer: Translation table configurable on several points
                                 Input Resolution: 16-bit analog/digital converter
                                 Differential: Range 0 to 250 Pa (0 to 1 in. H20)
                                 Resolution 0.000162 milli-inches H20, Accuracy ±0.3% full scale

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                         21
Table 3: LN-VAVLF, LN-VAVLN, and LN-VVTLF (Part 2 of 2) (Continued)
 Outputs                             Digital: 24 VAC Triac, digital (on/off), Pulse Width Modulation (PWM), or floating
                                        0.5 A continuous
                                        PWM control: adjustable period from 2 seconds to 15 minutes
                                        Floating control: requires two consecutive outputs
                                           Minimum pulse on/off: 500 milliseconds
                                           Adjustable drive time period
                                        External or internal power supply (jumper selectable)
                                     Digital LED Occupancy: 0 to 10 VDC dedicated output for occupancy sensor LED,
                                     Maximum 20 mA
                                     Universal: 0 to 10 VDC, digital 0 to 12 VDC (on/off), floating for PWM
                                        PWM control: adjustable period from 2 seconds to 15 minutes
                                        Floating control: requires two consecutive outputs
                                           Minimum pulse on/off: 500 milliseconds
                                           Adjustable drive time period
                                        20 mA maximum at 12 VDC
                                        Minimum load resistance 600 ohms
                                     Output Resolution: 10-bit digital/analog converter
 Damper Actuator                     Torque: 35 in·lb, 4 N·m
                                     Angle of Rotation: 95º adjustable
                                     Fits Shaft Diameter: 5/16 to 3/4 in. (8.5 to 18.2 mm)
                                     Power Supply: from controller
 Agency                              UL Listed: UL916 Energy management equipment
                                     Material: UL94-5VA1
 Electromagnetic Compatibility       CE Emission: EN61000-6-3: 2007; Generic standards for residential, commercial, and
                                                 light-industrial environments.
                                     CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and
                                                  light-industrial environments.

1.   All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical
     and Electronic Equipment (WEEE) directive.

Table 4: LN-VAVCF (Part 1 of 2)
 Product Code                  LN-VAVCF-2
 Power Requirements            Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
                               Protection: 3 A user-replaceable fuse for triac when using the internal power supply
                               Consumption: 18 VA; triac outputs (2 valves at 4 VA) and 2 outputs with
                               20 mA load at 12 VDC
                               Maximum Consumption: 70 VA if internal power supply is used
 Ambient Storage               Ambient Operating Temperature: 0 to 50°C (32 to 122°F)
 Conditions                    Ambient Storage Temperature: -20 to 50°C (-4 to 122°F)
                               Ambient Storage Conditions: 0 to 90% noncondensing
 General                       Processor: Neuron® 3150™, 8 bits, 10 MHz
                               Memory: Non-volatile Flash 128k (storage) Non-volatile Flash 64k (APB application)
                               Media Channel: TP/FT-10, 78 Kbps
                               Communication: LonTalk® protocol
                               LONMark Interoperability: Version 3.4
                               Device Class: Multi Input/Output (I/O) Module
                               LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1, Output Objects:
                               Open-Loop Sensor #3
 Enclosure (Housing)           Material: FR/ABS Resin
                               Dimensions (with screws): 4.8 x 8.4 x 2.5 in. (12.7 x 214.3 x 63.0 mm)
                               Shipping Weight: 2.30 lb (1.05 kg)

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                              22
Table 4: LN-VAVCF (Part 2 of 2)
 Inputs                        Universal, software configurable
                               Input Types:
                               Voltage: 0 to 10 VDC
                               Digital: Dry Contact,
                               Analog current: 4-20 mA with 249ohmsexternal resistor
                               Resistor Support:
                               Thermistor: 10ohmsType, 2, 3 (1k ohms at 25°C [302°F])
                                   Range: -40 to 150°C (-40 to 302°F)
                                   Platinum: Pt1000 (1k ohms at 0°C [32°F])
                                   Range: -40 to 150°C (-40 to 302°F)
                                      Pt100 (1k ohms at 0°C [32°F])
                                   Range: -40 to 150°C (-40 to 302°F)
                                   Nickel: RTD Ni1000 (1k ohms at 0°C [32°F])
                                       Range: -40 to 150°C (-40 to 302°F)
                                   Potentiometer: translation table configurable on several points
                               Differential Pressure: Range 0 to 250 Pa (0 to 1 in. H20)
                               Resolution: 0.000162 milli-in. H20
                               Accuracy: ±3% full scale
                                Input Resolution: 16-bit analog/digital converter
 Outputs                       Digital: 24 VAC Triac, digital (on/off), PWM, or floating1, software configurable
                               0.5 A continuous
                               PWM control: adjustable period from 2 seconds to 15 minutes
                                 Floating control: requires two consecutive outputs1
                                 Minimum pulse on/off: 500 milliseconds
                                 Adjustable drive time period
                                 External or Internal power supply (jumper selectable)
                                 Digital LED occupancy output: 0-10 VDC dedicated output for occupancy sensor LED
                                 Maximum 20 mA
                                 Universal: 0-10 VDC linear, digital 0-12 VDC (on/off), floating or PWM
                               PWM control: adjustable period from 2 seconds to 15 minutes
                                   Floating control: requires two consecutive outputs1
                                   Minimum pulse on/off: 500 milliseconds
                                   Adjustable drive time period
                                   20 mA max at 12 VDC, Minimum load 600ohms
                                   Output Resolution: 10-bits digital/analog converter
 Damper Actuator               Torque: 35 in·lb, 4 N·m
                               Degree of Rotation: 95º adjustable
                               Fits Shaft Diameter: 5/16 to 3/4 in. (8.5 to 18.2 mm)
 Wireless Receiver             Communication: EnOcean wireless standard2, Wireless Inputs: 143
                               Wireless Receivers: Wireless Receiver 315, Wireless Receiver 868
                               Cable: telephone cord, connector: 4P4C modular jack, length: 6.5 ft (2m)
 Electromagnetic               CE Emission: EN61000-6-3: 2007; generic standards for residential, commercial, and light-
 Compatibility                 industrial environments
                               CE Immunity: EN61000-6-1: 2007; generic standards for residential, commercial, and
                               light-industrial environments
 Compliance                    UL Listed (US and CDN): UL916 Energy Management Equipment, Material: UL94-5VA

1.   Floating only available when controller is programmed with LN GPI software.
2.   Available when an optional external Wireless Receiver is connected to the controller. Refer to the LN Wireless Location
     Guide for a list of supported EnOcean wireless modules.
3.   Some wireless sensors may use more than one input from the controller.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

                                                               23
 The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
 specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
 or misuse of its products.

European Single Point of Contact:             NA/SA Single Point of Contact:               APAC Single Point of Contact:
JOHNSON CONTROLS                              JOHNSON CONTROLS                             JOHNSON CONTROLS
WESTENDHOF 3                                  507 E MICHIGAN ST                            C/O CONTROLS PRODUCT MANAGEMENT
45143 ESSEN                                   MILWAUKEE WI 53202                           NO. 22 BLOCK D NEW DISTRICT
GERMANY                                       USA                                          WUXI JIANGSU PROVINCE 214142
                                                                                           CHINA

                                                                                                    Building Technologies & Solutions
                                                                                            507 E. Michigan Street, Milwaukee, WI 53202
                                                  Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
                                         All other marks herein are the marks of their respective owners. © 2017 Johnson Controls.

LN Series Variable Air Volume (VAV) and Variable Volume Temperature (VVT) Controllers Installation Instructions

Published in U.S.A.                                                    24                                          www.johnsoncontrols.com