| Вид документа | Керівництво користувача |
|---|---|
| Виробник | JCI |
| Код документа | fec26-extended-temperature-field-equipment-controller-installation-instructions |
| Група обладнання | FEC26 Field Equipment Controller |
| Сторінок | 16 |
| Мова документа | англійська |
| Розмір файлу | 0.4 МБ |
Текст документа
FEC26 Extended Temperature Field Equipment Controller
Installation Instructions
Part No. 24-10143-292, Rev. C
MS-FEC2611-0ET Issued June 20, 2014
Supersedes November 13, 2013
Applications United States
The FEC26 extended temperature controller is part of
This equipment has been tested and found to
the Metasys® system Field Equipment Controller
comply with the limits for a Class A digital device
(FEC) family. The FEC26 controller runs
pursuant to Part 15 of the FCC Rules. These limits
pre-engineered and user-programmed applications
are designed to provide reasonable protection
and provides the inputs and outputs required to monitor
against harmful interference when this equipment is
and control a wide variety of Heating, Ventilating, and
operated in a commercial environment. This
Air Conditioning (HVAC) equipment.
equipment generates, uses, and can radiate radio
FEC controllers operate on an RS-485 BACnet® MS/ frequency energy and, if not installed and used in
TP Bus as BACnet Application Specific Controllers (B- accordance with the instruction manual, may cause
ASCs) and integrate into the Web-based Metasys harmful interference to radio communications.
system. Operation of this equipment in a residential area
may cause harmful interference, in which case the
IMPORTANT: In Metasys system smoke control users will be required to correct the interference at
applications, use only the MS-FEU2610-0U and their own expense.
MS-FEU2620-0U models that are UL Listed, UUKL
864 Listed, Smoke Control Equipment. For Metasys Installation
system smoke control applications, you must refer to Observe these guidelines when installing an FEC
the Metasys System UL 864 UUKL Ninth Edition extended temperature controller:
Smoke Control System Technical Bulletin
(LIT-12011252) for detailed requirements and • Transport the FEC in the original container to
procedures for installing and operating UUKL 864 minimize vibration and shock damage.
Listed Metasys system devices. Failure to meet the • Verify that all parts shipped with the FEC.
requirements or follow the procedures in the
Metasys System UL 864 UUKL Ninth Edition Smoke • Do not drop the FEC or subject it to physical shock.
Control System Technical Bulletin (LIT-12011252)
Parts Included
can void the UUKL 864 listing for Smoke Control
Equipment. • one FEC26 controller with removable terminal
blocks
North American Emissions Compliance • one installation instructions sheet
Canada Materials and Special Tools Needed
• three fasteners appropriate for the mounting
This Class (A) digital apparatus meets all the
surface (M4 screws or #8 screws)
requirements of the Canadian Interference-Causing
Equipment Regulations. • one 20 cm (8 in.) or longer piece of 35 mm DIN rail
and appropriate hardware for DIN rail mount (only)
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel • small straight blade screwdriver for securing wires
brouilleur du Canada. in the terminal blocks
Mounting
Observe these guidelines when mounting an FEC:
• Ensure the mounting surface can support the FEC,
DIN rail, and any user-supplied enclosure.
FEC26 Extended Temperature Field Equipment Controller Installation Instructions 1
• Mount the FEC on 35 mm DIN rail whenever
possible.
• Mount the FEC in the proper mounting position
(Figure 1).
• Mount the FEC on a hard, even surface whenever
possible in wall-mount applications.
• Use shims or washers to mount the FEC securely
and evenly on the mounting surface.
• Mount the FEC in an area free of corrosive vapors
and observe the Ambient Conditions in the
Technical Specifications section.
• Provide for sufficient space around the FEC for
cable and wire connections, easy cover removal,
and good ventilation through the controller (50 mm Figure 2: Back of FEC26 Controller Showing
[2 in.] minimum on the top, bottom, and front of the Extended Mounting Clips, DIN Rail Channel, and
controllers).
• Do not mount the FEC on surfaces prone to DIN Rail Mount Applications
vibration, such as duct work, or in areas where DIN rail mounting is the preferred mounting method.
electromagnetic emissions from other devices or To mount an FEC on 35 mm DIN rail:
wiring can interfere with controller communication.
1. Securely mount a 20 cm (8 in.) or longer section of
On panel or enclosure mount applications, observe 35 mm DIN rail horizontal and centered in the
these additional guidelines: desired space so that the controller mounts in the
horizontal position shown in Figure 1.
• Do not install the FEC in an airtight enclosure.
2. Pull the two bottom mounting clips outward to the
• Mount the FEC so that the enclosure walls do not
extended position (Figure 2).
obstruct cover removal or ventilation through the
controller. 3. Hang the controller on the DIN rail by the hooks at
the top of the (DIN rail) channel on the back of the
• Mount the FEC so that the power transformer and controller (Figure 2), and position the controller
other devices do not radiate excessive heat to the snugly against the DIN rail.
controller.
4. Push the bottom mounting clips inward to secure
the controller on the DIN rail.
To remove the FEC from the DIN rail, pull the bottom
mounting clips out to the extended position and
carefully lift the controller off the DIN rail.
Figure 1: Controller Mounting Positions
2 FEC26 Extended Temperature Field Equipment Controller Installation Instructions
Wall Mount Applications 3. Drill holes in the wall at the locations marked in
To mount an FEC directly on a wall (or other flat vertical Step 2, and insert appropriate wall anchors in all
surface): three holes (if necessary).
1. Pull the two bottom mounting clips outward and 4. Hold the FEC in place, and insert the screws
ensure they are locked in the extended positions through the mounting clips and into the holes.
as shown in Figure 2. Carefully tighten all of the screws.
2. Mark the three mounting hole locations on the wall IMPORTANT: Do not overtighten the mounting
using the dimensions in Figure 2 and one of the screws. Overtightening the screws may damage the
mount positions shown in Figure 1 (or hold the mounting clips.
controller up to the wall/surface in a proper mount
position and mark the hole locations through the
mounting clips.)
FEC26 Extended Temperature Field Equipment Controller Installation Instructions 3
4
Binary Output Source Power
Selection Jumpers Configurable Outputs can be defined as: Analog Outputs can be defined as:
Voltage Analog Output (0-10 VDC) Voltage Analog Output (0-10 VDC)
(Live 24 VAC Binary Output (24 VAC Triac) Current Analog Output (4-20 mA)
on Exposed Jumper Pins.) Device Address
DIP Switch Block
24 VAC, Class 2
Binary Outputs Supply Power
24 VAC Triacs Terminal Block
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 COM HOT
OCOM1 OCOM2 OCOM3 OCOM4 OCOM5 OCOM6 OCOM7 OCOM8 OCOM9
Cover Lift
Tab BINARY SOURCE 24VAC ADDRESS CONFIGURABLE ANALOG 24V~ Cover Lift
Tab
FC Bus Port
POWER
RJ-12 6-Pin
Modular Jack FAULT Display
SA BUS
Navigation Buttons
(Not available on
FC BUS all FEC models.)
FC BUS
EOL
LED
Status Indicators FEC 2611
UNIVERSAL BINARY
+15V IN1 ICOM1 IN2 ICOM2 +15V IN3 ICOM3 IN4 ICOM4 +15v IN5 ICOM5 IN6 ICOM6 IN7 ICOM7 IN8 ICOM8
LCD
SABUS FC BUS Display Area
(Not available on
SENSOR COM POWER COM SHD all FEC models.)
FEC26 Extended Temperature Field Equipment Controller Installation Instructions
Universal Inputs can be defined as:
Voltage Analog Input (0-10 VDC)
Current Analog Input (4-20 mA) Mounting Clip
Figure 3: FEC2621 Controller Physical Features and Wiring Terminals
Resistive Analog Inputs (0-600k ohm): (One of Three) Binary Inputs can be defined as: FC Bus
0-2k Potentiometer Dry Contact Maintained Terminal
Sensor Port SA Bus
FIG:fec26_phys_feats
RTD: 1k Nickel, 1k Platinum, or A99B SI Pulse Counter Mode Block
(50 Hz at 50% duty cycle) (SA Bus) Terminal
NTC: 10k Type L 10k JCI Type II, or 2.252k Type II Block
RJ-12 6-Pin
Dry Contact Binary Input
Modular Jack
Wiring Wire the removable FC Bus terminal block plugs on the
FEC, and other field controllers in a daisy-chain
CAUTION: Risk of Electric Shock. configuration using 3-wire twisted, shielded cable as
Disconnect the power supply before shown in Figure 4. See Table 3 for more information.
! making electrical connections to avoid
Note: The Shield terminal (SHLD) on the FC Bus
electric shock.
terminal block is isolated and can be used to connect
Mise En Garde: Risque de décharge the cable shields on the bus (Figure 4).
électrique: Débrancher l'alimentation
avant de réaliser tout raccordement
électrique afin d'éviter tout risque de
décharge électrique.
IMPORTANT: Do not connect supply power to the
controller before finishing wiring and checking all
wiring connections. Short circuits or improperly
connected wires can result in damage to the
controller and void any warranty.
IMPORTANT: Do not exceed the controller
electrical ratings. Exceeding controller electrical
ratings can result in permanent damage to the
controller and void any warranty.
Figure 4: FC Bus Terminal Block Wiring
IMPORTANT: Use copper conductors only. Make
all wiring in accordance with local, national, and SA Bus Terminal Block
regional regulations. The SA Bus terminal block is a brown, removable,
4-terminal plug that fits into a board-mounted jack.
IMPORTANT: Electrostatic discharge can damage
Wire the removable SA Bus terminal block plugs on the
FEC components. Use proper electrostatic
FEC and other SA Bus devices in a daisy-chain
discharge precautions during installation, setup, and
configuration using 4-wire twisted, shielded cable as
servicing to avoid damaging the FEC controller.
shown in Figure 5. See Table 3 for more information.
For detailed information on configuring and wiring an
MS/TP Bus, Field Controller (FC) Bus, and Sensor
Actuator (SA) Bus, refer to the MS/TP Communications
Bus Technical Bulletin (LIT-12011034).
FEC Terminal Blocks and Bus Ports
See Figure 3 for terminal block and bus port locations
on the FEC26 extended temperature controller.
Observe the following guidelines when wiring an FEC
controller.
Input and Output Terminal Blocks
All of the fixed input terminal blocks are mounted on
the bottom of the FEC. The output terminal blocks are
mounted on the top of the controller. See Table 1 for
more information.
Figure 5: SA Bus Terminal Block Wiring
FC Bus Terminal Block
The FC Bus terminal block is a blue, removable,
4-terminal plug that fits into a board-mounted jack.
FEC26 Extended Temperature Field Equipment Controller Installation Instructions 5
FC Bus Port
The FC Bus port on the front of the FEC is an RJ-12,
6-position modular jack that provides a connection for
the Bluetooth® Wireless Commissioning Converter,
ZigBee™ wireless dongle, or ZFR1811 Wireless Field
Bus Router.
The FC Bus port is connected internally to the FC Bus
terminal block. See Table 3 for more information. The
FC Bus Port pin assignment is shown in (Figure 6).
Figure 7: 24 VAC Supply Power
Terminal Block Wiring
The supply power wire colors may be different on
transformers from other manufacturers. Refer to the
transformer manufacturer’s instructions and the project
installation drawings for wiring details.
Figure 6: Pin Number Assignments for IMPORTANT: Connect 24 VAC supply power to the
Sensor, SA Bus, and FC Bus Ports on FEC and all other network devices so that
FEC, IOM, and VMA16 transformer phasing is uniform across the network
devices. Powering network devices with uniform
Sensor Port 24 VAC supply power phasing reduces noise,
The Sensor (SA Bus) port on the bottom of the FEC interference, and ground loop problems. The FEC
(Figure 3) is an RJ-12, 6-position modular jack that does not require an earth ground connection.
provides a connection for the Wireless Commissioning
Converter, the VAV Balancing Tool, specified network Wireless Network Applications
sensors, or other SA Bus devices with RJ-12 plugs. The FEC can also be installed in a wireless application.
To configure a controller for use with the ZFR1800
A DIS1710 Local Controller Display also can be Series Wireless Field Bus system:
connected to the SA Bus port (but only on FEC models
without an integral display and push buttons). 1. Wire the input/output terminals and SA Bus.
The Sensor port is connected internally to the SA Bus Note: In wireless network applications, do not
terminal block. See Table 3 for more information. The connect any wires to the FC Bus terminal block.
Sensor Port pin assignment is shown in Figure 6. 2. Connect the ZFR1811 Wireless Field Bus Router to
Supply Power Terminal Block the FC Bus port (RJ-12 modular jack) on the front
The 24 VAC supply power terminal block is a gray, of the FEC.
removable, 3-terminal plug that fits into a board- 3. Ensure that the FEC device address DIP switches
mounted jack on the top right of the FEC. are set to the correct device address. See Setting
the Device Address.
Wire the 24 VAC supply power wires from the
transformer to the HOT and COM terminals on the 4. Position DIP switch 128 to ON to enable wireless
terminal plug as shown in Figure 7. The middle operation on the FEC.
terminal on the supply power terminal block is not For more information on installing an FEC in a wireless
used. See Table 3 for more information. configuration, refer to the ZFR1811 Wireless Field Bus
Router Installation Instructions (Part No. 24-10325-1).
6 FEC26 Extended Temperature Field Equipment Controller Installation Instructions
FEC Terminal Functions, Ratings, • All input and output cables, regardless of wire size
Requirements, and Wiring Guidelines or number of wires, should consist of stranded,
insulated, and twisted copper wires.
Input and Output Wiring Guidelines
• Shielded cable is not required for input or output
Table 1 provides information and guidelines about the
cables.
functions, ratings, and requirements for the FEC input
and output terminals, and references guidelines for • Shielded cable is recommended for input and
determining proper wire sizes and cable lengths. output cables that are exposed to high
electromagnetic or radio frequency noise.
In addition to the wiring guidelines in Table 1, observe
these guidelines when wiring FEC inputs and outputs: • Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software
• Run all low-voltage wiring and cables separate
setup. Cable runs over 30 m (100 ft) may require
from high-voltage wiring.
an offset in the input/output software setup.
Table 1: I/O Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 1 of 3)
Terminal Block Terminal Function, Ratings, and Requirements Determine Wire Size and
Label Labels Maximum Cable Length1
UNIVERSAL +15 V 15 VDC Power Source for active (3-wire) input devices Same as (Universal) INn.
(Inputs) connected to the Universal INn terminals. Note: Use 3-wire cable for
Provides 100 mA total current. devices that source power
from the +15 V terminal.
INn Analog Input - Voltage Mode (0-10 VDC) See Guideline A in Table 2.
10 VDC maximum input voltage
Internal 75k ohm Pulldown
Analog Input - Current Mode (4-20 mA) See Guideline B in Table 2.
Internal 100 ohm load Impedance
Note: A current loop fail-safe jumper can be positioned
to maintain a closed 4-20 mA current loop even when
power to the controller is interrupted or off. See Binary
Output Source Power Selection Jumpers.
Analog Input - Resistive Mode (0-600k ohm) See Guideline A in Table 2.
Internal 12 V, 15k ohm pull up
Qualified Sensors: 0-2k potentiometer,
RTD (1k Nickel [Johnson Controls® sensor],
1k Platinum, and A99B Silicon Temperature Sensor)
Negative Temperature Coefficient (NTC) Sensor
(10k Type L, 10k JCI Type II, 2.252k Type II)
Binary Input - Dry Contact Maintained Mode See Guideline A in Table 2.
1 second minimum pulse width
Internal 12 V, 15k ohm pull up
ICOMn Universal Input Common for all Universal IN terminals Same as (Universal) INn.
Note: All Universal ICOMn terminals share a common,
which is isolated from all other commons.
BINARY INn Binary Input - Dry Contact Maintained Mode See Guideline A in Table 2.
(Inputs) 0.01 second minimum pulse width
Internal 18 V, 3k ohm pull up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 18 V, 3k ohm pull up
ICOMn Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common,
which is isolated from all other commons, except the
Configurable Output (CO) common (OCOMn) when the
CO is defined as an Analog Output.
FEC26 Extended Temperature Field Equipment Controller Installation Instructions 7
Table 1: I/O Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 3)
Terminal Block Terminal Function, Ratings, and Requirements Determine Wire Size and
Label Labels Maximum Cable Length1
ANALOG OUTn Analog Output - Voltage Mode (0-10 VDC) See Guideline A in Table 2.
(Outputs) 10 VDC maximum output voltage
10 mA maximum output current
Requires an external load of 1,000 ohms or more.
Note: The AO operates in Voltage Mode when
connected to devices with impedances greater than
1,000 ohms. Devices that drop below 1,000 ohms may
not operate as intended for Voltage Mode applications.
Analog Output - Current Mode (4-20 mA) See Guideline B in Table 2.
Requires an external load between 0-300 ohms.
Note: The AO operates in Current Mode when
connected to devices with impedances less than
300 ohms. Devices that exceed 300 ohms may not
operate as intended for Current Mode applications.
OCOMn Analog Output Signal Common for all Analog OUT Same as (Analog) OUTn.
terminals.
Note: All Analog OCOMn terminals share a common,
which is isolated from all other commons.
BINARY OUTn Binary Output - 24 VAC Triac (External Power) See Guideline C in Table 2.
(Outputs) Connects OUTn to OCOMn when activated.
Power Selection External Power Source:
Jumper positioned
to External (EXT). 30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220-BGx-3
40 mA minimum load current
OCOMn Binary Output Common (for OUTn terminal)
Note: Each Binary Output common terminal (OCOMn) is
isolated from all other commons, including other Binary
Output commons.
BINARY OUTn Binary Output - 24 VAC Triac (Internal Power) See Guideline C in Table 2.
(Outputs) Sources internal 24 VAC power (24~ HOT)
Power Selection
Jumper positioned OCOMn Binary Output - 24 VAC Triac (Internal Power)
to Internal (INT). Connects OCOMn to 24~ COM when activated.
Internal Power Source:
30 VAC maximum voltage to load
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220-BGx-3
40 mA minimum load current
8 FEC26 Extended Temperature Field Equipment Controller Installation Instructions
Table 1: I/O Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 3 of 3)
Terminal Block Terminal Function, Ratings, and Requirements Determine Wire Size and
Label Labels Maximum Cable Length1
CONFIGURABLE OUTn Analog Output - Voltage Mode (0-10 VDC) See Guideline A in Table 2.
(Outputs) 10 VDC maximum output voltage
10 mA maximum output current
Requires an external load of 1000 ohm or more
Binary Output 24 VAC Triac See Guideline C in Table 2.
Connects OUT to OCOM when activated.
External Power Source:
30 VAC maximum voltage to load
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220-BGx-3
40 mA minimum load current
OCOMn Analog Output Signal Common: All Configurable Same as (Configurable)
Outputs defined as Analog Outputs share a common, OUTn.
which is isolated from all other commons except the
Binary Input common.
Binary Output Signal Common: All Configurable
Outputs defined as Binary Outputs are isolated from all
other commons, including other Configurable Output
commons.
1. See Table 2 to determine wire size and cable lengths for cables other than the recommended cables.
Table 2 defines cable length guidelines for the various
wire sizes that may be used for input and output wiring.
Table 2: Cable Length Guidelines for Recommended Wire Sizes
Guideline Wire Size/Gauge and Type Maximum Cable Length Assumptions
and Type
A 1.5 mm2 (18 AWG) stranded copper 457 m (1,500 ft) twisted wire 100 mV maximum voltage drop
Depending on the cable length and
0.8 mm (20 AWG) stranded copper 297 m (975 ft) twisted wire
the connected input or output device,
183 m (600 ft) twisted wire you may have to define an offset in
0.6 mm (22 AWG) stranded copper
the setup software for the input or
N/A (24 AWG) stranded copper 107 m (350 ft) twisted wire output point.
B 1.5 mm2 (18 AWG) stranded copper 229 m (750 ft) twisted wire 100 mV maximum voltage drop
Depending on the cable length and
0.8 mm (20 AWG) stranded copper 137 m (450 ft) twisted wire
the connected input or output device,
91 m (300 ft) twisted wire you may have to define an offset in
0.6 mm (22 AWG) stranded copper
the setup software for the input or
N/A (24 AWG) stranded copper 61 m (200 ft) twisted wire output point.
C See Figure 8 to select wire size/gauge. See Figure 8 to determine N/A
Use stranded copper wire. cable length. Use twisted
wire cable.
FEC26 Extended Temperature Field Equipment Controller Installation Instructions 9
Maximum Cable Length versus Load Current
Use Figure 8 to estimate the maximum cable length
relative to the wire size and the load current (in mA)
when wiring inputs and outputs.
Figure 8: Maximum Wire Length by Current and Wire Size
FC and SA Bus and Supply Power Wiring • Run all low-voltage wiring and cables separate
Guidelines from high-voltage wiring.
Table 3 provides information about the functions, • All FC and SA Bus cables, regardless of wire size,
ratings, and requirements for the FEC communication should be twisted, insulated, stranded copper wire.
bus and supply power terminals; and provides
guidelines for wire sizes, cable types, and cable • Shielded cable is strongly recommended for all FC
lengths when wiring the FEC communication buses and SA Bus cables.
and supply power. • Refer to the MS/TP Communications Bus
In addition to the guidelines in Table 3, observe these Technical Bulletin (LIT-12011034) for detailed
guidelines when wiring the SA/FC Buses and supply information regarding wire size and cable length
power: requirements for the FC and SA buses.
Table 3: Communication Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and
Cables (Part 1 of 2)
Terminal Terminal Function, Electrical Ratings/Requirements Recommended Cable Type1
Block/Port Labels
Label
FC BUS2 + FC Bus Communications 0.6 mm (22 AWG) stranded, 3-wire
- twisted, shielded cable
recommended
COM Signal Reference (Common) for bus communications
SHLD Isolated terminal (optional shield drain connection)
10 FEC26 Extended Temperature Field Equipment Controller Installation Instructions
Table 3: Communication Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and
Cables (Part 2 of 2)
Terminal Terminal Function, Electrical Ratings/Requirements Recommended Cable Type1
Block/Port Labels
Label
FC Bus2 RJ-12 6-Position Modular Connector provides: Wireless Commissioning
(Port) FC Bus Communications Converter retractable cable or
FC Bus Signal Reference and 15 VDC Common 24 AWG 3-pair CAT 3 Cable
15 VDC, 240 mA, Power for Wireless Commissioning <30.5 m (100 ft)
Converter or ZFR1811 Wireless Router.
SA BUS2 + SA Bus Communications 0.6 mm (22 AWG) stranded, 4-wire
- (2 twisted-pairs), shielded cable
recommended
COM SA Bus Signal Reference and 15 VDC Common
Note: The + and - wires are one
SA PWR 15 VDC Supply Power for Devices on the SA Bus twisted pair and the COM and
(Maximum total current draw for SA Bus is 240 mA.) SA PWR are the second twisted
pair of wires.
SENSOR2 SENSOR RJ-12 6-Position Modular Connector provides: 24 AWG 3-pair CAT 3 Cable
SA Bus Communications <30.5 m (100 ft)
SA Bus Signal Reference and 15 VDC Common
15 VDC Power for devices on the SA Bus and
Wireless Commissioning Converter.
24~ HOT 24 VAC Power Supply - Hot 0.8 mm to 1.5 mm2
Supplies 20-30 VAC (Nominal 24 VAC) (20 to 16 AWG) 2-wire
COM 24 VAC Power Supply Common (Isolated from all other
Common terminals on controller)
1. See Table 2 to determine wire size and cable lengths for cables other than the recommended cables.
2. The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38.4k baud. For more
information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
Setup and Adjustments
Setting the Device Address
Metasys field controllers are master devices on
BACnet MS/TP (SA or FC) buses. Before operating
field controllers on a bus, you must set a valid and
unique device address for each controller on the bus.
Figure 9: Device Address Switches Set to 21
You set a field controller's device address by setting the
positions of the switches on the Device Address DIP Note: Metasys field controllers ship with switch 128
switch block at the top of the controller (Figure 3). ON and the remaining address switches off rendering
Device addresses 4 through 127 are the valid the controllers wired subordinate devices, which do
addresses for these controllers. not operate on MS/TP buses, but do not interfere with
The DIP switch block (Figure 9) has eight switches bus operation. Set a valid and unique device address
numbered 128, 64, 32, 16, 8, 4, 2, and 1. Switches 64 on the field controller before applying power to the
through 1 are device address switches. Switch 128 is a controller on the bus.
mode switch that enables a field controller to operate To set the device addresses on Metasys field
on a ZFR1800 Series Wireless Field Bus. Switch 128 controllers:
must be set to off for all hard-wired SA and FC Bus
applications. Set switch 128 to ON for wireless FC Bus 1. Set all of the switches on the field controller’s
applications only. device address DIP switch block (128 through 1) to
off.
FEC26 Extended Temperature Field Equipment Controller Installation Instructions 11
2. Set one or more of the seven address switches (64 Table 4: SA/FC Bus Device Address Descriptions
through 1) to ON, so that the sum of the switch Device Address Description
numbers set to ON equals the intended device Address
address. See Table 4 for valid field controller
0 Reserved for FC Bus Supervisory Controller
addresses.
(Switch (not valid for field controllers).
Set the highest number switch that is less than or 128 Off)
equal to the intended device address to ON. Then 1 to 3 Reserved for peripheral devices (not valid for
continue setting lower numbered switches until the (Switch field controllers).
total equals the intended address. For example, if 128 Off)
the intended device address is 21, set switch 16 to 4 to 127 Valid for MS/TP Master field controllers on a
ON first, then set switch 4 ON, followed by switch 1 (Switch hard-wired SA Bus or FC Bus.
(16+4+1= 21). See Figure 9. 128 Off)
0 to 3 Reserved addresses for wired subordinate
3. Set switch 128 to ON only for controllers on a (Switch devices (not valid for field controllers).
ZFR1800 Series Wireless Field Bus application. 128 ON) Note:Metasys controllers ship with 128 ON and
For all hard-wired SA and FC Bus applications, the remaining address switches off, rendering the
ensure that switch 128 is set to off. controllers wired subordinate devices, which do
not operate on Metasys field buses.
Note: Do not connect a field controller with switch
4 to 127 Valid for MS/TP Master field controllers on
128 set to ON to an active (hard-wired) SA or FC
(Switch wireless FC Buses only.
Bus. When a controller with switch 128 set to ON 128 ON) Note: Do not connect a Metasys controller
and a device address from 4 to 127 is connected to with these device addresses to an active
a wired field bus, the entire field bus is rendered wired SA or FC Bus. When a controller with
inoperable until the controller is disconnected or one of these device address is connected to
switch 128 is set to off. a wired field bus, the field bus is rendered
inoperable until the controller is disconnected
Refer to the ZFR1800 Series Wireless Field Bus or switch 128 is set to off.
System Technical Bulletin (LIT-12011295) for more
information on device addresses in wireless Removing the FEC Housing Cover
applications.
IMPORTANT: Electrostatic discharge can damage
4. Set a unique and sequential device address for controller components. Use proper electrostatic
each of the field controllers connected on the SA or discharge precautions during installation, setup, and
FC Bus starting with device address 4. servicing to avoid damaging the controller.
To ensure the best bus performance, set
sequential device addresses with no gaps in the IMPORTANT: Disconnect all power sources to the
device address range (4, 5, 6, 7, 8, 9, and so on). controller before removing cover and changing the
The field controllers do not need to be physically position of any jumper or the EOL switch on the
connected on the bus in their numerical device controller. Failure to disconnect power before
address order. changing a jumper or EOL switch position can result
5. Write each field controller's device address on the in damage to the controller and void any warranties.
white label below the DIP switch block on the
The controller cover is held in place by four plastic
controller's cover.
latches that extend from the base and snap into slots
Refer to the MS/TP Communications Bus Technical on the inside of the housing cover. To remove the
Bulletin (LIT-12011034) for more information on field controller cover:
controller device addresses and how to set them on
1. Place your fingernails under the two cover lift tabs
MS/TP buses.
on the sides of the housing cover (Figure 3) and
Table 4 shows and describes the valid FC Bus and gently pry the top of the cover away from the base
SA Bus devices addresses for Johnson Controls® to release the cover from the two upper latches.
MS/TP communications bus applications.
2. Pivot the top of the cover further to release it from
the lower two latches.
Replace the cover by placing it squarely over the base,
and then gently and evenly push the cover on to the
latches until they snap into tПоказано початок документа. Повний текст — у PDF за посиланням вище.
Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.
