| Вид документа | Керівництво користувача |
|---|---|
| Виробник | JCI |
| Код документа | fec16-extended-temperature-field-equipment-controller-installation-instructions |
| Група обладнання | FEC16 Field Equipment Controller |
| Сторінок | 16 |
| Мова документа | англійська |
| Розмір файлу | 0.4 МБ |
Текст документа
FEC16 Extended Temperature Field Equipment Controller
Installation Instructions
Part No. 24-10143-306, Rev. C
MS-FEC1611-0ET, MS-FEC1611-1ET Issued May 16, 2014
Supersedes November 13, 2013
Applications North American Emissions Compliance
The FEC16 extended temperature field controller is Canada
part of the Metasys® system Field Equipment
Controller (FEC) family. The FEC16 controller runs This Class (A) digital apparatus meets all the
pre-engineered and user-programmed applications requirements of the Canadian Interference-Causing
and provides the inputs and outputs required to monitor Equipment Regulations.
and control a wide variety of Heating, Ventilating, and
Cet appareil numérique de la Classe (A) respecte
Air Conditioning (HVAC) equipment.
toutes les exigences du Règlement sur le matériel
FEC extended temperature controllers operate on an brouilleur du Canada.
RS-485 BACnet® MS/TP Bus as BACnet Application
Specific Controllers (B-ASC) and integrate into the United States
Web-based Metasys system.
This equipment has been tested and found to
comply with the limits for a Class A digital device
IMPORTANT: In Metasys system smoke control pursuant to Part 15 of the FCC Rules. These limits
applications, use only the MS-FEU1610-0U model are designed to provide reasonable protection
that is UL/cUL Listed, UUKL 864 Listed, 9th Edition against harmful interference when this equipment is
Smoke Control Equipment. For Metasys system operated in a commercial environment. This
smoke control applications, you must refer to the equipment generates, uses, and can radiate radio
Metasys® System UL 864 9th Edition UUKL/ORD- frequency energy and, if not installed and used in
C100-13 UUKLC Smoke Control System Technical accordance with the instruction manual, may cause
Bulletin (LIT-12011252) for detailed requirements harmful interference to radio communications.
and procedures for installing and operating UUKL Operation of this equipment in a residential area
864 Listed Metasys system devices. Failure to meet may cause harmful interference, in which case the
the requirements or follow the procedures in the users will be required to correct the interference at
Metasys® System UL 864 9th Edition UUKL/ORD- their own expense.
C100-13 UUKLC Smoke Control System Technical
Bulletin (LIT-12011252) can void the UUKL 864 Installation
listing for Smoke Control Equipment. Observe these guidelines when installing an FEC
extended temperature controller:
• Transport the FEC in the original container to
minimize vibration and shock damage.
• Verify that all parts shipped with the FEC.
• Do not drop the FEC or subject it to physical shock.
FEC16 Extended Temperature Field Equipment Controller Installation Instructions 1
Parts Included On panel or enclosure mount applications, observe
• one FEC16 controller with removable terminal these additional guidelines:
blocks • Do not install the FEC in an airtight enclosure.
• one installation instructions sheet • Mount the FEC so that the enclosure walls do not
Materials and Special Tools Needed obstruct cover removal or ventilation through the
controller.
• three fasteners appropriate for the mounting
surface (M4 screws or #8 screws) • Mount the FEC so that the power transformer and
other devices do not radiate excessive heat to the
• one 20 cm (8 in.) or longer piece of 35 mm DIN rail
and appropriate hardware for DIN rail mount (only) controller.
• small straight blade screwdriver for securing wires
in the terminal blocks
Mounting
Observe these guidelines when mounting an FEC
extended temperature controller:
• Ensure the mounting surface can support the FEC,
DIN rail, and any user-supplied enclosure.
• Mount the FEC on 35 mm DIN rail whenever
possible. Figure 1: Controller Mounting Positions
• Mount the FEC in the proper mounting position
(Figure 1).
• Mount the FEC on a hard, even surface whenever
possible in wall-mount applications.
• Use shims or washers to mount the FEC securely
and evenly on the mounting surface.
• Mount the FEC in an area free of corrosive vapors
and observe the Ambient Conditions in the
Technical Specifications section.
• Provide for sufficient space around the FEC for
cable and wire connections, easy cover removal,
and good ventilation through the controller (50 mm
[2 in.] minimum on the top, bottom, and front of the
controllers).
• Do not mount the FEC on surfaces prone to Figure 2: Back of FEC16 Controller Showing
vibration, such as duct work, or in areas where Extended Mounting Clips, DIN Rail Channel, and
electromagnetic emissions from other devices or
wiring can interfere with controller communication.
2 FEC16 Extended Temperature Field Equipment Controller Installation Instructions
DIN Rail Mount Applications Wall Mount Applications
DIN rail mounting is the preferred mounting method. To mount an FEC directly on a wall (or other flat vertical
To mount an FEC on 35 mm DIN rail: surface):
1. Securely mount a 20 cm (8 in.) or longer section of 1. Pull the two bottom mounting clips outward and
35 mm DIN rail horizontal and centered in the ensure they are locked in the extended positions
desired space so that the controller mounts in the as shown in Figure 2.
horizontal position shown in Figure 1.
2. Mark the three mounting hole locations on the wall
2. Pull the two bottom mounting clips outward to the using the dimensions in Figure 2 and one of the
extended position (Figure 2). mount positions shown in Figure 1 (or hold the
controller up to the wall/surface in a proper mount
3. Hang the controller on the DIN rail by the hooks at
the top of the (DIN rail) channel on the back of the position and mark the hole locations through the
mounting clips.)
controller (Figure 2), and position the controller
snugly against the DIN rail. 3. Drill holes in the wall at the locations marked in
Step 2, and insert appropriate wall anchors in all
4. Push the bottom mounting clips inward to secure
three holes (if necessary).
the controller on the DIN rail.
4. Hold the FEC in place, and insert the screws
To remove the FEC from the DIN rail, pull the bottom
through the mounting clips and into the holes.
mounting clips out to the extended position and
Carefully tighten all of the screws.
carefully lift the controller off the DIN rail.
IMPORTANT: Do not overtighten the mounting
screws. Overtightening the screws may damage the
mounting clips.
FEC16 Extended Temperature Field Equipment Controller Installation Instructions 3
4
Binary Output Source Power
Selection Jumpers Configurable Outputs can be defined as:
Device Address Voltage Analog Output (0-10 VDC)
(Live 24 VAC DIP Switch Block Binary Output (24 VAC Triac)
on Exposed Jumper Pins.)
Binary Outputs 24 VAC, Class 2
24 VAC Triacs Supply Power
Terminal
Block
COM HOT
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7
Cover Lift OCOM1 OCOM2 OCOM3 OCOM4 OCOM5 OCOM6 OCOM7
Cover Lift
Tab Tab
BINARY SOURCE 24VAC ADDRESS CONFIGURABLE 24V~
FC Bus Port
POWER
RJ-12 6-Pin
Modular Jack FAULT Display
SABUS
Navigation Buttons
(Not available
FCBUS on all FEC models)
FC BUS
EOL
LED
Status Indicators FEC1611
UNIVERSAL BINARY
+15V IN1 ICOM1 IN2 ICOM2 IN3 ICOM3
LCD
SA BUS FC BUS Display Area
(Not available
SENSOR COM POWER COM SHD on all FEC models.)
FEC16 Extended Temperature Field Equipment Controller Installation Instructions
Universal Inputs can be defined as: Mounting Clips
Figure 3: FEC1611 Controller Physical Features and Wiring Terminals
FC Bus
Voltage Analog Input (0-10 VDC) (Two of Three) Terminal
Current Analog Input (4-20 mA)
Binary Inputs can be defined as: Block
Resistive Analog Inputs (0-600k ohm): Sensor Port SA Bus
0-2k potentiometer Dry Contact Maintained
(SA Bus) Terminal
Pulse Counter Mode
FIG:fec16_phys_feas
RTD: 1k Nickel, 1k Platinum, or A99B SI RJ-12 6-Pin Block
NTC: 10k Type L,10k JCI Type II, or 2.252k Type II (50 Hz at 50% duty cycle)
Modular Jack
Dry Contact Binary Input
Wiring FC Bus Terminal Block
The FC Bus terminal block is a blue, removable,
CAUTION: Risk of Electric Shock. 4-terminal plug that fits into a board-mounted jack.
Disconnect the power supply before
! making electrical connections to avoid Wire the removable FC Bus terminal block plugs on the
FEC, and other field controllers in a daisy-chain
electric shock.
configuration using 3-wire twisted, shielded cable as
Mise En Garde: Risque de décharge shown in Figure 4. See Table 3 for more information.
électrique: Débrancher l'alimentation
avant de réaliser tout raccordement Note: The Shield terminal (SHLD) on the FC Bus
électrique afin d'éviter tout risque de terminal block is isolated and can be used to connect
décharge électrique. the cable shields on the bus (Figure 4).
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
! making electrical connections to avoid
electric shock.
Mise En Garde: Risque de décharge
électrique: Débrancher l'alimentation
avant de réaliser tout raccordement
électrique afin d'éviter tout risque de
décharge électrique.
IMPORTANT: Do not exceed the controller
electrical ratings. Exceeding controller electrical
ratings can result in permanent damage to the
controller and void any warranty. Figure 4: FC Bus Terminal Block Wiring
IMPORTANT: Use copper conductors only. Make SA Bus Terminal Block
all wiring in accordance with local, national, and
The SA Bus terminal block is a brown, removable,
regional regulations.
4-terminal plug that fits into a board-mounted jack.
IMPORTANT: Electrostatic discharge can damage Wire the removable SA Bus terminal block plugs on the
controller components. Use proper electrostatic FEC and other SA Bus devices in a daisy-chain
discharge precautions during installation, setup, and configuration using 4-wire twisted, shielded cable as
servicing to avoid damaging the controller. shown in Figure 5. See Table 3 for more information.
For detailed information on configuring and wiring an
MS/TP Bus, Field Controller (FC) Bus, and Sensor
Actuator (SA) Bus, refer to the MS/TP Communications
Bus Technical Bulletin (LIT-12011034).
FEC Terminal Blocks and Bus Ports
See Figure 3 for terminal block and bus port locations
on the FEC16 controller. Observe the following
guidelines when wiring an FEC controller.
Input and Output Terminal Blocks
All of the fixed input terminal blocks are mounted on
the bottom of the FEC. The output terminal blocks are
mounted on the top of the controller. See Table 1 for
more information.
Figure 5: SA Bus Terminal Block Wiring
FEC16 Extended Temperature Field Equipment Controller Installation Instructions 5
FC Bus Port
The FC Bus port on the front of the FEC is an RJ-12,
6-position modular jack that provides a connection for
the Wireless Commissioning Converter or ZFR1811
Wireless Field Bus Router.
The FC Bus port is connected internally to the FC Bus
terminal block. See Table 3 for more information. The
FC Bus Port pin assignment is shown in Figure 6.
Figure 7: 24 VAC Supply Power
Terminal Block Wiring
The supply power wire colors may be different on
transformers from other manufacturers. Refer to the
transformer manufacturer’s instructions and the project
installation drawings for wiring details.
Figure 6: Pin Number Assignments for IMPORTANT: Connect 24 VAC supply power to the
Sensor, SA Bus, and FC Bus Ports on FEC and all other network devices so that
FEC, IOM, and VMA16 transformer phasing is uniform across the network
devices. Powering network devices with uniform
Sensor Port 24 VAC supply power phasing reduces noise,
The Sensor (SA Bus) port on the bottom of the FEC interference, and ground loop problems. The FEC
(Figure 3) is an RJ-12, 6-position modular jack that does not require an earth ground connection.
provides a connection for the Wireless Commissioning
Wireless Network Applications
Converter, the VAV Balancing Tool, specified network
sensors, or other SA Bus devices with RJ-12 plugs. The FEC also can be installed in a wireless application.
To configure a controller for use with the ZFR1800
A DIS1710 Local Controller Display also can be Series Wireless Field Bus system:
connected to the SA Bus port (but only on FEC models
without integral display and push buttons). 1. Wire the input/output terminals and SA Bus.
The Sensor port is connected internally to the SA Bus Note: In wireless network applications, do not
terminal block. See Table 3 for more information.The connect any wires to the FC Bus terminal block.
Sensor Port pin assignment is shown in Figure 6. 2. Connect the ZFR1811 Wireless Field Bus Router to
Supply Power Terminal Block the FC Bus port (RJ-12 modular jack) on the front
of the FEC.
The 24 VAC supply power terminal block is a gray,
removable, 3-terminal plug that fits into a board- 3. Ensure that the FEC device address DIP switches
mounted jack on the top right of the FEC. are set to the correct device address. See Setting
the Device Address.
Wire the 24 VAC supply power wires from the
transformer to the HOT and COM terminals on the 4. Position DIP switch 128 to ON to enable wireless
terminal plug as shown in Figure 7. The middle operation on the FEC.
terminal on the supply power terminal block is not For more information on installing an FEC in a wireless
used. See Table 3 for more information. configuration, refer to the ZFR1811 Wireless Field Bus
Router Installation Instructions (Part No. 24-10325-1).
6 FEC16 Extended Temperature Field Equipment Controller Installation Instructions
FEC Terminal Functions, Ratings, • All input and output cables, regardless of wire size
Requirements, and Wiring Guidelines or number of wires, should consist of stranded,
insulated, and twisted copper wires.
Input and Output Wiring Guidelines
• Shielded cable is not required for input or output
Table 1 provides information and guidelines about the
cables.
functions, ratings, and requirements for the FEC input
and output terminals; and references guidelines for • Shielded cable is recommended for input and
determining proper wire sizes and cable lengths. output cables that are exposed to high
electromagnetic or radio frequency noise.
In addition to the wiring guidelines in Table 1, observe
these guidelines when wiring FEC inputs and outputs: • Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software
• Run all low-voltage wiring and cables separate
setup. Cable runs over 30 m (100 ft) may require
from high-voltage wiring.
an offset in the input/output software setup.
Table 1: I/O Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 1 of 2)
Terminal Block Terminal Function, Ratings, and Requirements Determine Wire Size and
Label Labels Maximum Cable Length1
UNIVERSAL +15 V 15 VDC Power Source for active (3-wire) input devices Same as (Universal) INn.
(Inputs) connected to the Universal INn terminals. Note: Use 3-wire cable for
Provides 100 mA total current. devices that source power
from the +15 V terminal.
INn Analog Input - Voltage Mode (0-10 VDC) See Guideline A in Table 2.
10 VDC maximum input voltage
Internal 75k ohm Pulldown
Analog Input - Current Mode (4-20 mA) See Guideline B in Table 2.
Internal 100 ohm load Impedance
A current loop fail-safe jumper can be positioned to
maintain a closed 4-20 mA current loop even when power
to the controller is interrupted or off. See Universal Input
Current Loop Jumpers.
Analog Input - Resistive Mode (0-600k ohm) See Guideline A in Table 2.
Internal 12 V, 15k ohm pull up
Qualified Sensors: 0-2k potentiometer,
RTD (1k Nickel [Johnson Controls® sensor],
1k Platinum, and A99B Silicon Temperature Sensor)
Negative Temperature Coefficient (NTC) Sensor
(10k Type L, 10k JCI Type II, 2.252k Type II)
Binary Input - Dry Contact Maintained Mode See Guideline A in Table 2.
1 second minimum pulse width
Internal 12 V, 15k ohm pull up
ICOMn Universal Input Common for all Universal IN terminals Same as (Universal) INn.
Note: All Universal ICOMn terminals share a common,
which is isolated from all other commons.
BINARY INn Binary Input - Dry Contact Maintained Mode See Guideline A in Table 2.
(Inputs) 0.01 second min. pulse width
Internal 18 V, 3k ohm pull up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 18 V, 3k ohm pull up
ICOMn Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common,
which is isolated from all other commons, except the
Configurable Output (CO) common (OCOMn) when the
CO is defined as an Analog Output.
FEC16 Extended Temperature Field Equipment Controller Installation Instructions 7
Table 1: I/O Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 2)
Terminal Block Terminal Function, Ratings, and Requirements Determine Wire Size and
Label Labels Maximum Cable Length1
BINARY OUTn Binary Output - 24 VAC Triac (External Power) See Guideline C in Table 2.
(Outputs) Connects OUTn to OCOMn when activated.
Power Selection External Power Source:
Jumper positioned
to External (EXT) 30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220-BGx-3
40 mA minimum load current
OCOMn Binary Output Common (for OUTn terminal)
Note: Each Binary Output common terminal (OCOMn) is
isolated from all other commons, including other Binary
Output commons.
BINARY OUTn Binary Output - 24 VAC Triac (Internal Power) See Guideline C in Table 2.
(Outputs) Model FEC1611-0ET: Sources internal 24 VAC power
Power Selection (24~COM).
Jumper positioned Model FEC1611-1ET: Sources internal 24 VAC power
to Internal (INT) (24~HOT).
OCOMn Binary Output - 24 VAC Triac (Internal Power)
Model FEC1611-0ET: Connects OCOMn to 24~ HOT
when activated.
Model FEC1611-1ET: Connects OCOMn to 24~ COM
when activated.
Internal Power Source:
30 VAC maximum voltage to load
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220-BGx-3
40 mA minimum load current
CONFIGURABLE OUTn Analog Output - Voltage Mode (0-10 VDC) See Guideline A in Table 2.
(Outputs) 10 VDC maximum output voltage
10 mA maximum output current
Requires an external load of 1,000 ohm or more
Binary Output 24 VAC Triac See Guideline C in Table 2.
Connects OUT to OCOM when activated.
External Power Source:
30 VAC maximum voltage to load
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220-BGx-3
40 mA minimum load current
OCOMn Analog Output Signal Common: All Configurable Same as (Configurable)
Outputs defined as Analog Outputs share a common, OUTn.
which is isolated from all other commons except the
Binary Input common.
Binary Output Signal Common: All Configurable
Outputs (COs) defined as Binary Outputs are isolated
from all other commons, including other CO commons.
1. See Table 2 to determine wire size and cable lengths for cables other than the recommended cables.
8 FEC16 Extended Temperature Field Equipment Controller Installation Instructions
Table 2 defines cable length guidelines for the various
wire sizes that may be used for input and output wiring.
Table 2: Cable Length Guidelines for Recommended Wire Sizes
Guideline Wire Size/Gauge and Type Maximum Cable Length Assumptions
and Type
A 1.5 mm2 (18 AWG) stranded copper 457 m (1,500 ft) twisted wire 100 mV maximum voltage drop
Depending on the cable length and
0.8 mm (20 AWG) stranded copper 297 m (975 ft) twisted wire
the connected input or output device,
183 m (600 ft) twisted wire you may have to define an offset in
0.6 mm (22 AWG) stranded copper
the setup software for the input or
N/A (24 AWG) stranded copper 107 m (350 ft) twisted wire output point.
B 2
1.5 mm (18 AWG) stranded copper 229 m (750 ft) twisted wire 100 mV maximum voltage drop
Depending on the cable length and
0.8 mm (20 AWG) stranded copper 137 m (450 ft) twisted wire
the connected input or output device,
91 m (300 ft) twisted wire you may have to define an offset in
0.6 mm (22 AWG) stranded copper
the setup software for the input or
N/A (24 AWG) stranded copper 61 m (200 ft) twisted wire output point.
C See Figure 8 to select wire size/gauge. See Figure 8 to determine N/A
Use stranded copper wire. cable length. Use twisted
wire cable.
Maximum Cable Length versus Load Current
Use Figure 8 to estimate the maximum cable length
relative to the wire size and the load current (in mA)
when wiring inputs and outputs.
Figure 8: Maximum Wire Length by Current and Wire Size
FEC16 Extended Temperature Field Equipment Controller Installation Instructions 9
FC and SA Bus and Supply Power Wiring • Run all low-voltage wiring and cables separate
Guidelines from high-voltage wiring.
Table 3 provides information about the functions, • All FC and SA Bus cables, regardless of wire size,
ratings, and requirements for the FEC communication should be twisted, insulated, stranded copper wire.
bus and supply power terminals; and provides
guidelines for wire sizes, cable types, and cable • Shielded cable is strongly recommended for all FC
lengths when wiring the FEC communication buses and SA Bus cables.
and supply power. • Refer to the MS/TP Communications Bus
In addition to the guidelines in Table 3, observe these Technical Bulletin (LIT-12011034) for detailed
guidelines when wiring the SA/FC Buses and supply information regarding wire size and cable length
power: requirements for the FC and SA buses.
Table 3: Communication Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and
Cables
Terminal Terminal Function, Electrical Ratings/Requirements Recommended Cable Type1
Block/Port Labels
Label
FC BUS2 + FC Bus Communications 0.6 mm (22 AWG) stranded, 3-wire
- twisted, shielded cable
recommended
COM Signal Reference (Common) for bus communications
SHLD Isolated terminal (optional shield drain connection)
FC BUS2 RJ-12 6-Position Modular Connector provides: Wireless Commissioning
(Port) FC Bus Communications Converter retractable cable or
FC Bus Signal Reference and 15 VDC Common 24 AWG 3-pair CAT 3 Cable
15 VDC Power for Wireless Commissioning <30.5 m (100 ft)
Converter or ZFR1811 Wireless Router.
SA BUS2 + SA Bus Communications 0.6 mm (22 AWG) stranded, 4-wire
- (2 twisted-pairs), shielded cable
recommended
COM SA Bus Signal Reference and 15 VDC Common
Note: The + and - wires are one
SA PWR 15 VDC Supply Power for Devices on the SA Bus twisted pair and the COM and
(Maximum total current draw for SA Bus is 240 mA.) SA PWR are the second twisted
pair of wires.
SENSOR2 RJ-12 6-Position Modular Connector provides: 24 AWG 3-pair CAT 3 Cable
(SA Bus Port) SA Bus Communications <30.5 m (100 ft)
SA Bus Signal Reference and 15 VDC Common
15 VDC Power for devices on the SA Bus and
Wireless Commissioning Converter.
24~ HOT 24 VAC Power Supply - Hot 0.8 mm to 1.5 mm2
Supplies 20-30 VAC (Nominal 24 VAC) (20 to 16 AWG) 2-wire
COM 24 VAC Power Supply Common (Isolated from all other
Common terminals on controller)
1. See Table 2 to determine wire size and cable lengths for cables other than the recommended cables.
2. The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38.4k baud. For more
information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
10 FEC16 Extended Temperature Field Equipment Controller Installation Instructions
Setup and Adjustments Set the highest number switch that is less than or
equal to the intended device address to ON. Then
Setting the Device Address continue setting lower numbered switches until the
Metasys field controllers are master devices on total equals the intended address. For example, if
BACnet MS/TP (SA or FC) buses. Before operating the intended device address is 21, set switch 16 to
field controllers on a bus, you must set a valid and ON first, then set switch 4 ON, followed by switch 1
unique device address for each controller on the bus. (16+4+1= 21). See Figure 9.
You set a field controller's device address by setting the 3. Set switch 128 to ON only for controllers on a
positions of the switches on the Device Address DIP ZFR1800 Series Wireless Field Bus application.
switch block at the top of the controller (Figure 3). For all hard-wired SA and FC Bus applications,
Device addresses 4 through 127 are the valid ensure that switch 128 is set to off.
addresses for these controllers.
Note: Do not connect a field controller with switch
The DIP switch block (Figure 9) has eight switches 128 set to ON to an active (hard-wired) SA or FC
numbered 128, 64, 32, 16, 8, 4, 2, and 1. Switches 64 Bus. When a controller with switch 128 set to ON
through 1 are device address switches. Switch 128 is a and a device address from 4 to 127 is connected to
mode switch that enables a field controller to operate a wired field bus, the entire field bus is rendered
on a ZFR1800 Series Wireless Field Bus. Switch 128 inoperable until the controller is disconnected or
must be set to off for all hard-wired SA and FC Bus switch 128 is set to off.
applications. Set switch 128 to ON for wireless FC Bus
Refer to the ZFR1800 Series Wireless Field Bus
applications only.
System Technical Bulletin (LIT-12011295) for more
information on device addresses in wireless
applications.
4. Set a unique and sequential device address for
each of the field controllers connected on the SA or
FC Bus starting with device address 4.
Figure 9: Device Address Switches Set to 21 To ensure the best bus performance, set
sequential device addresses with no gaps in the
device address range (4, 5, 6, 7, 8, 9, and so on).
Note: Metasys field controllers ship with switch 128 The field controllers do not need to be physically
ON and the remaining address switches off rendering connected on the bus in their numerical device
the controllers wired subordinate devices, which do address order.
not operate on MS/TP buses, but do not interfere with
bus operation. Set a valid and unique device address 5. Write each field controller's device address on the
on the field controller before applying power to the white label below the DIP switch block on the
controller on the bus. controller's cover.
To set the device addresses on Metasys field Refer to the MS/TP Communications Bus Technical
controllers: Bulletin (LIT-12011034) for more information on field
controller device addresses and how to set them on
1. Set all of the switches on the field controller’s MS/TP buses.
device address DIP switch block (128 through 1) to
off. Table 4 shows and describes the valid FC Bus and
SA Bus devices addresses for Johnson Controls®
2. Set one or more of the seven address switches (64 MS/TP communications bus applications.
through 1) to ON, so that the sum of the switch
numbers set to ON equals the intended device
address. See Table 4 for valid field controller
addresses.
FEC16 Extended Temperature Field Equipment Controller Installation Instructions 11
Table 4: SA/FC Bus Device Address Descriptions Replace the cover by placing it squarely over the base,
Device Address Description and then gently and evenly push the cover on to the
Address latches until they snap into the latched position.
0 Reserved for FC Bus Supervisory Controller
(Switch (not valid for field controllers).
128 Off)
1 to 3 Reserved for peripheral devices (not valid for
(Switch field controllers).
128 Off)
4 to 127 Valid for MS/TP Master field controllers on a
(Switch hard-wired SA Bus or FC Bus.
128 Off)
0 to 3 Reserved addresses for wired subordinate
(Switch devices (not valid for field controllers).
128 ON) Note:Metasys controllers ship with 128 ON
and the remaining address switches off,
rendering the controllers wired subordinate
devices, which do not operate on Metasys field Figure 10: FEC16 with Cover Removed
buses. Showing Jumper and EOL Switch Positions
4 to 127 Valid for MS/TP Master field controllers on
(Switch wireless FC Buses only.
128 ON) Note: Do not connect a Metasys controller Setting the EOL Switch
with these device addresses to an active
wired SA or FC Bus. When a controller with Each field controller has an End-of-Line (EOL) switch,
one of these device address is connected to which, when set to ON/up, sets the field controller as a
a wired field bus, the field bus is rendered terminating device on the bus. See Figure 3 or
inoperable until the controller is disconnected Figure 10 for the EOL switch location on the field
or switch 128 is set to off.
controller. The default EOL switch position is off/down.
Removing the FEC Housing Cover
IMPORTANT: Disconnect all power sources to the
controller before removing cover and changing the
position of any jumper or the EOL switch on the Figure 11: EOL Switch Positions
controller. Failure to disconnect power before
changing a jumper or EOL switch position can result
To set the EOL switch on a field controller:
in damage to the controller and void any warranties.
1. Determine the physical location of the field
IMPORTANT: Electrostatic discharge can damage controller on the SA or FC Bus.
controller components. Use proper electrostatic 2. Determine if the field controller must be set as a
discharge precautions during installation, setup, and terminating device on the bus.
servicing to avoid damaging the controller.
Note: The EOL termination rules for SA Buses
The controller cover is held in place by four plastic and FC Buses are different. Refer to the
latches that extend from the base and snap into slots MS/TP Communications Bus Technical Bulletin,
on the inside of the housing cover. To remove the (LIT-12011034) for detailed information regarding
controller cover: EOL termination rules and EOL switch settings on
SA and FC Buses.
1. Place your fingernails under the two cover lift tabs
on the sides of the housing cover (Figure 3) and 3. If the field controller is a terminating device on the
gently pry the top of the cover away from the base SA Bus or FC Bus, set the EOL switch to ON. If the
to release the cover from the two upper latches. field controller is not a terminating device on the
bus, set the EOL switch to off.
2. Pivot the top of the cover further to release it from
the lower two latches. When a field controller is connected to power with its
EOL switch set to ON, the amber EOL Light-Emitting
Diode (LED) on the controller cover is lit.
12 FEC16 Extended Temperature Field Equipment Controller Installation Instructions
Setting the Input and Output Jumpers Universal Input Current Loop Jumpers
Binary Output Source Power Selection Jumpers The Universal Input (UI) current loop fail-safe jumpers
are on the circuit board under the housing cover near
CAUTION: Risk of Electric Shock. the UI terminals (Figure 10). When a UI is defined (in
Disconnect supply power to the FEC16 the system software) as a 4-20 mA analog input and
! controller before attempting to adjust the the UI’s current loop jumper is in the (default) Disabled
position (Figure 13), the 4-20 mA current loop circuit
Binary Output Source Power Selection
Jumpers. Failure to disconnect the opens whenever power to the FEC is interrupted or off.
supply power may result in electric shock. Setting the current loop jumper to the Enabled position
Mise En Garde: Risque de décharge (Figure 13) connects an internal 100 ohm resistor
électrique: Débrancher l'alimentation de across the UI terminals, which maintains the 4-20 mA
l'controller avant tout réglage du Binary current loop circuit even when power to the FEC is
Output Source Power Selection Jumpers. interrupted or off.
Le non-respect de cette précaution
risque de provoquer une décharge IMPORTANT: Current Loop jumpers must be in the
électrique. (default) Disabled position for all UIs that are not set
up to operate as 4-20 mA analog inputs.
IMPORTANT: Do not connect an external power
source to a Binary Output (BO) when the BO power
source jumper is in the internal power (INT) position.
Connecting external power to a BO that sources
internal power can damage the controller and void
any warranties.
The BO source power selection jumpers determine
whether a BO provides internal power (sourced from Figure 13: Current Loop Jumper Positions
the FEC) to the output load (INT position) or requires
an external power source (EXT position) for the output Table 5 identifies the current loop jumpers associated
load. Figure 12 shows an example of an FEC16 with each UI on the FEC16 controller.
controller BOs and the associated power selection
Table 5: FEC16 UI Inputs and Jumper Labels
jumpers to the right of the BOs terminal block.
Universal Input Jumper Label on Circuit
Label Board
IN1 J74
IN2 J73
Commissioning
CommissiПоказано початок документа. Повний текст — у PDF за посиланням вище.
Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.
